background image

12

instructions given in section 4.3. The
gas  feed  pressure  must  under  no
circumstances exceed 50 mbar.

– after have ultimated the conversion

of  the  boiler,  please  stick  onto  the
casing  panel  the  plate  showing  the
relevant  feeding  gas  which  is  inclu-
ded into the conversion kit.

NOTE:  After  assembling  all  the  gas
connections, a test for gas tightness
must  be  carried  out  using  soapy
water  or  special  products.  DO  NOT
USE NAKED FLAMES.

4.6

DISASSEMBLY OF 
EXPANSION VESSEL

To  disassemble  the  boiler  expansion
vessel, proceed as follows:
– make sure that the water has been

emptied out of the boiler;

– unscrew  the  connection  connecting

the  expansion  vessel  to  the  boiler
and the two self-tapping screws that
fasten the system to the bracket.

NOTE:  Before  refilling  the  system,
make sure that the expansion vessel
is pre-loaded at 1 bar pressure.

4.7

CLEANING AND 
MAINTENANCE

At the end of each heating season, it is
essential to have the boiler thoroughly
checked  and  cleaned  out.  Proceed  as
follows:
– turn the switching knob to OFF to stop

electric power reaching the boiler;

– close the gas feed cock;
– disassemble the outer casing;
– remove  the  smoke  chamber,

unscrewing the screws that fasten it

to the combustion chamber;

– disassemble the gas burner-manifold

unit, as described in Section 4.5;

– to clean the burners, blow in a jet of

air,  so  as  to  remove  any  dust  parti-
cles that may have accumulated;

– clean  the  heat  exchanger,  removing

any dust or residue from combustion;

– when cleaning the heat exchanger or

the  burners,  chemical  products  or
steel brushes MUST NOT BE USED;

– make sure that the tops of the bur-

ners  with  the  holes  are  free  from
encrustations;

– reassemble the items removed from

the boiler, making sure to follow the
correct sequence;

– check  the  chimney  to  make  sure

that the flue is clean;

– check  operation  of  the  equipment

and of the main burner.

Preventive maintenance and checking
of  efficient  operation  of  equipment
and  safety  devices  must  be  carried
out at the end of each season.

4.8

FAULT FINDING

Main burner does not start either to
draw off D.H.W. or heating.

– Check operation of smoke pressure

switch.

– Check,  and  if  necessary  replace,

smoke pressure switch.

– Replace electronic card.
– Check if SM is interrupted.

Fan turns but burner does not start.

– Check  whether  connection  tubes  of

smoke  pressure  switch  PF  are
obstructed  and,  if  necessary,  clean
away impurities or condensate.

– Smoke  pressure  switch  PF  needs

recalibrating or, better still, replacing
with a new factory-calibrated one.

Fan fails to turn.

– Check whether electric power is rea-

ching  the  terminals  of  the  activator
motor.

– Motor winding is burnt out; replace.
– Replace electronic card.

Main burner fails to modulate both in
D.H.W. phase and in heating phase.

– Modulator M has a break in winding;

replace.

– Electronic card is faulty; replace.

Boiler  makes  noises  and  a  sizzling
sound.

– Check  whether  circulating  pumps

are  obstructed;  if  necessary,  clear

them out.

– Unclog impeller of circulating pump,

clearing away any impurities or sedi-
ments.

– Circulating pump is burnt out; replace.
– Check  boiler  output  is  adequate  for

actual needs of heating system.

Boiler  safety  valve  keeps  going  into
action.

– Check  whether  system  cold  charge

pressure is too high; keep to recom-
mended values.

– Check whether safety valve is out of

calibration; if necessary, replace.

– Check  pre-loading  pressure  of

expansion vessel.

– Replace expansion vessel if faulty.

Radiators fail to heat up in winter.

– Knob  is  set  to  SUMMER.  Turn  it  to

WINTER.

– Room stat TA is set too low or needs

replacing because faulty.

– Electrical  connections  of  room  stat

TA are wrong.

Radiators warm up also in summer.

– Check for right setting of knob.
– Check  no  impurities  are  present  in

the non-return valve seat.

– Non-return valve is faulty; replace.
– Install  non-return  valve  on  system

return pipe.

Main burner burns badly: flames too
high, too yellow.

– Check that pressure of gas reaching

burner is regular.

– Check burners are clean.

Water  from  boiling  unit  isn’t  suffi-
ciently hot.

– Air  is  still  present  at  the  top  of  the

boiler.  Purge  off  through  air  relief
valve.

– Reduce hot-water drawing-off rate.

Smell of unburnt gases.

– Check boiler is properly clean.
– Check draught is sufficient.
– Check  whether  gas  consumption  is

too high.

Boiler  operates  but  does  not  increa-
se temperature.

– Check  whether  gas  consumption  is

not lower than it should be.

– Check boiler is clean.
– Check boiler is sized in proportion to

system.

KEY

1

Burner manifold

2

Copper washer ø 6.1

3

Nozzle M6

4

Burner unit

5

Screw TCB M4 x 6

Fig. 19

Содержание Super four

Страница 1: ...Super four Installation and servicing instructions GB...

Страница 2: ...Open the gas tap and check the soundness of the connections including that of the burner Purge the system bleeding off the air present in the gas pipe by operating the air relief valve on the gas valv...

Страница 3: ...uct 60 100 Fig 1 The gas consumptions refer to the calorific value at standard conditions at 15 C 1013 mbar SUPER FOUR Heat output Maximum kW 28 5 Minimum kW 15 1 Heat input Maximum kW 31 6 Minimum kW...

Страница 4: ...n vessel 23 Magnesium anode 24 Air relief valve 25 Boiler unit safety valve 26 Frost stat 27 D H W isolation valve 28 Gas cock 29 C H return isolation valve 30 C H flow isolation valve 1 4 FUNCTIONAL...

Страница 5: ...e boiler with serious consequences IT IS ABSOLUTELY ESSENTIAL THAT THE WATER USED FOR THE CENTRAL HEATING SYSTEM SHOULD BE TREA TED IN THE FOLLOWING CASES very extensive system with high con tents of...

Страница 6: ...cations of possible solutions Table 1 gives the minimum distances to be observed with refe rence to the type of building shown in fig 6 4 Fig 6 KEY A Elbow flange B Junction collar C Outer duct D Alum...

Страница 7: ...V 50 Hz single phase through a fused main switch with at least 3 mm spacing between contacts You are recommended to install a room temperature thermostat to ensure bet ter regulation of temperature a...

Страница 8: ...rode TS 100 C safety stat TA Room stat M Modulating coil PA Water pressure switch PI C H circulating pump PB D H W circulating pump SM Heating sensor blue SS D H W sensor red C Four way switch FA EMC...

Страница 9: ...ated so as to obtain a pressure of approx 3 5 mbar at the burner for natural gas and 7 mbar for L P G G30 G31 To increase pressure turn the trimmer clockwise to reduce pres sure turn the trimmer count...

Страница 10: ...ic power to the ignition electrode The electrode continues spark discharge for a maximum of 10 sec If the burner does not ignite the equipment locks out This may occur upon first ignition or after lon...

Страница 11: ...00 Portata l h Prevalenza residua mbar MURELLE BN AVANT BF RESIDUAL HEAD mbar FLOW RATE l h Fig 14 Fig 13 KEY 1 Gas cock 2 Union 3 C H return cock 4 C H flow cock 5 D H W inlet cock 6 D H W safety val...

Страница 12: ...ream of the gas valve remove the plastic cap 1 set the switching knob to SUMMER and open the D H W tap at a high flow rate with the boiler lit using a 10 span ner turn the nut 3 to arrive at the maxim...

Страница 13: ...e main nozzles 3 located on the burner manifold 1 inserting the copper washer 2 Use a 7 span ner to perform this operation reassemble all the parts proceeding in reverse order remove the L P G MET con...

Страница 14: ...moke pressure switch Replace electronic card Check if SM is interrupted Fan turns but burner does not start Check whether connection tubes of smoke pressure switch PF are obstructed and if necessary c...

Страница 15: ......

Страница 16: ...Cod 6258908A Documentation Dpt Sime Ltd Unit D2 Enterprise Way Bradford Road Idle Bradford BD10 8EW Tel 0870 9911114 Fax 0870 9911115 www sime ltd uk e mail enquiries sime ltd uk...

Отзывы: