![Sime Planet Dewy 100 BFR Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/sime/planet-dewy-100-bfr/planet-dewy-100-bfr_installation-and-servicing-instructions_1275089006.webp)
6
1.1 INTRODUCTION
“PLANET DEWY BFR”
boilers are pre-
mixed condensation heating modules inten-
ded only for heating, designed to work sin-
gularly or in sequence/cascade autono-
mously. They are supplied as
class B
devi-
ces, but can easily be converted to
class C
(room sealed) with the addition of a air
intake pipe. They are designed and con-
structed to meet European directives
2009/142/CEE, 2004/108/CEE,
2006/95/CEE and 92/42/CEE.
As a single boiler it can be controlled by a
simple timer/thermostat or with Logica.
A RVA controller is available to manage up
to 6 boilers in sequence or cascade.
1
DESCRIPTION OF THE BOILER
1.2
DIMENSIONS
1.2.1
PLANET DEWY 60 BFR (fig. 1)
275
55
120
60
12
0
265
170
75
230
M
R C
S3
G
409
=
20
87
0
455
500
865
120 150
13
5
CS
CA
R3
=
Fig. 1
R
C.H. return
G 1” (UNI-ISO 228/1)
M
C.H. flow
G 1” (UNI-ISO 228/1)
G
Gas connection
G 3/4” (UNI-ISO 228/1)
C
Filling system
G 1/2” (UNI-ISO 228/1)
R3 Tank return
G 1” (UNI-ISO 228/1)
S3
Condensation outlet
ø 25
CA
Air inlet
ø 80
CS
Exhaust
ø 80
ATTENTION: the boiler is supplied as Class B device. To
install the boiler as Class C device, remove the termi-
nal inserted in the flange before connecting the intake.
203
M
R
G
R3
15
6
S3
65
115
281
12
0
235
865
500
CS
CA
120 160
13
5
600
405
1
8,5
87
0
=
=
Fig. 1/a
1.2.2
PLANET DEWY 100 BFR (fig. 1/a)
R
C.H. return
G 1 1/2” (UNI-ISO 228/1)
M
C.H. flow
G 1 1/2” (UNI-ISO 228/1)
G
Gas connection
G 3/4” (UNI-ISO 228/1)
R3 Tank return
G 1 1/2” (UNI-ISO 228/1)
S3
Condensation outlet
ø 25
CA
Air inlet
ø 80
CS
Exhaust
ø 80
ATTENTION: the boiler is supplied as Class B device. To
install the boiler as Class C device, remove the terminal
inserted in the flange before connecting the intake.
MINIMUM CLEARANCES
(when installed as a single boiler)
Above the appliance
200mm (see note 1)
At the R.H.S
15mm
At the L.H.S
15mm
Below the appliance
300 mm (see note 2)
In front of the appliance 600mm
NOTE 1:
This will increase dependant on the flue option chosen
NOTE 2:
See fig 3 for clearances when using the hydraulic separator
MINIMUM CLEARANCES
(when installed as a single boiler)
Above the appliance
200mm (see note 1)
At the R.H.S
15mm
At the L.H.S
15mm
Below the appliance
300 mm (see note 2)
In front of the appliance 600mm
NOTE 1:
This will increase dependant on the flue option chosen
NOTE 2:
See fig 3 for clearances when using the hydraulic separator
Содержание Planet Dewy 100 BFR
Страница 3: ......
Страница 29: ...29 For 100 BFR and boilers in cascade ...
Страница 30: ...30 ...
Страница 32: ...32 5 EXPLODED VIEWS COD TYPE DATE PAGE 3830005 345 PLANET DEWY 60 BFR UK 20 01 2010 1 4 ...
Страница 33: ...33 COD TYPE DATE PAGE 3830005 345 PLANET DEWY 60 BFR UK 20 01 2010 2 4 ...
Страница 36: ...36 COD TYPE DATE PAGE 3830037 212 Planet Dewy 100 BFR UK 20 01 2010 1 4 ...
Страница 37: ...37 COD TYPE DATE PAGE 3830037 212 Planet Dewy 100 BFR UK 20 01 2010 2 4 ...