68
and act on the boiler drain (5 fig. 6).
NB: In “T” vers. loading is achieved by the
appropriate connection (10 fig. 6).
2.7
INSTALLATION OF
COAXIAL DUCT
(ø 60/100 - ø 80/125)
The axial suction and discharge pipes are
supplied in a special kit (that can be purcha-
sed separ at el y) along wit h assembl y
instructions.
The diagrams of fig. 8 illustrate some
examples of different types of discharge
modalities allowed and t he maximum
lengths that can be reached.
2.8
INSTALLATION OF SEPARATE
DUCTS (ø 80 - ø 60)
The kit with dedicated pipes enables to
separate the exhaust fumes pipes from the
air suction pipes (fig. 9):
- for ø 80 pipes, divider code 8093050 is
provided upon request.
- for ø 60 pipes, divider code 8093060 is
provided upon request.
The maximum overall length, resulting
fr om the sum of all the suction and
discharge pipes, is determined by the
load losses of the single connected acces-
sories and should not exceed 10 mm H
2
O
(version 12) - 13 mm H
2
O (version 20) -
15 mm H
2
O (version 25-30-35)
(ATTENTION: the total length of each pipe
should not exceed 50 m, even if the total
loss is below the maximum applicable
loss.)
See
Table 1-1/a
for information on the
load losses of single accessories and the
example of fig. 9/a for information on how
to calculate load losses.
2.8.1
Separate ducts kit
The diagrams of figure 10 show a few
examples of the permitted exhausts confi-
gurations.
2.8.2
Connection to existing flues
The ø 80 or ø 60 exhaust pipe can also be
connected to existing flues.
When the boiler runs at low temperature,
it is possible to use standard flues provided
that:
- The flue is not be used by other boilers.
- The interior of the flue is protected to
prevent a direct contact with condensa-
tion from the boiler. The products of
combustion must be conveyed through a
flexible or rigid plastic pipe around 100
to 150 mm in diameter, and condensa-
tion must be siphoned off at the foot of
the pipe. The usable height of the water
trap must be at least 150 mm.
C33
6
5
3
2
C43
3
4
2
x
y
x + y = L (m)
H (m)
C13
1
2
1
L (m)
2
Fig. 8
LIST OF ø 60/100 ACCESSORIES
1
Coaxial duct kit code
8096250
2a
Extension L. 1000 code
8096150
2b
Extension
L. 500 code 8096151
3
Vertical extension
L. 140
with coupling code
8086950
4a
Additional 90° curve code
8095850
4b
Additional 45° curve code
8095950
5
Tile for joint code
8091300
6
Terminal for roof exit L.
1285 code 8091205
IMPORTANT:
- The insertion of each additional 90° bend
with a diameter of 60/100 reduces the
available section by 1.5 meters.
- The insertion of each additional 90° bend
with a diameter of 80/125 reduces the
available section by 2 meters.
- Each additional 45° curve installed redu-
ces the available length by 1.0 metres.
- During assembly it is important to make
sure that the kit with axial pipes. (1) is
positioned horizontally.
NOTE
Before connecting accessories, it is always
advisable to lubricate the internal part of
the gaskets with silicon products. Avoid
using oils and greases.
Model
Length of pipe
Length of pipe
ø 60/100
ø 80/125
L
H
L
H
Min
Max
Min
Max
12 T
6 m
1.3 m
8 m
12 m
1.2 m
15 m
20 T
6 m
1.3 m
8 m
12 m
1.2 m
15 m
25
6 m
1.3 m
8 m
12 m
1.2 m
15 m
30
5 m
1.3 m
7 m
10 m
1.2 m
13 m
35
4 m
1.3 m
6 m
8 m
1.2 m
13 m
LIST OF ø 80/125 ACCESSORIES
1
Coaxial duct kit code
8096253
2a
Extension
L. 1000 code 8096171
2b
Extension
L. 500 code 8096170
3
Adapter for
ø 80/125 code 8093150
4a
Additional 90° curve code
8095870
4b
Additional 45° curve code
8095970
5
Tile for joint code
8091300
6
Terminal for roof exit L.
1285 code 8091205