background image

4.1

FILLING THE WATER SYSTEM

– Loosen the automatic air vent cap (10 fig. 2).
– Open all radiator valves and system air vents. Close all air

vents. Do not close the A.A.V. the one near the pump!

– Check the system for water soundness.
– Completely drain the appliance and heating system, thorough-

ly flush the system, and refill the system design pressure.

– Open the D.H.W. inlet valve, open any hot tap, clear of air

bubbles. Close hot tap.

4.2

COMMISSIONING THE BOILER

– Remove  the  screw  and  connect  a  pressure  gauge  to  the

burner pressure test point on the gas valve (fig. 13).

– Ensure that the rotary switch on the facia panel is set to the

SUMMER position  “

”  (D.H.W.  Only),  turn  the  D.H.W.  ther-

mostat to maximum (fully clockwise), and turn on the electri-
cal supply. Fully open any D.H.W. tap and the burner will light.

– Allow  the  boiler  to  run  for  at  least  5  minutes  and  check

that  the  burner  pressure  is  as  stated  in  section  1.3.  The
D.H.W.  burner  pressure  is  factory  set  and  should  not
require adjusting. If the burner pressure is low, check that
the appliance has not begun to modulate (this will occur if
the D.H.W. flow rate is low. If modulation is suspected, open
all D.H.W. taps to maximise flow and recheck burner pres-
sure).  If  it  is  necessary  to  adjust  the  D.H.W.  burner  pres-
sure the method is described in section 8.6.

– Reduce  the  D.H.W.  draw  off  rate  to  the  minimum  neces-

sary  to  maintain  the  burner  alight  by  carefully  adjusting
the D.H.W. inlet valve and check that the burner pressure
decreases  in  response  to  D.H.W.  temperature  rise.  Fully
open the inlet valve.

– Close the D.H.W. tap and ensure that the burner is extin-

guished and the pump stops.

4.3

SETTING THE C.H. INPUT

– Turn  the  rotary  switch  to  the  WINTER position  “

"  and

ensure  that  the  room  thermostat  (if  fitted)  is  calling  for
heat.  Turn  the  C.H.  thermostat  knob  to  maximum  (fully
clockwise) and the burner will light.

– Allow  the  boiler  to  run  for  at  least  5  minutes  and  check

the  burner  pressure.  The  heating  input  is  factory  set  as
stated in 

Table 4.

– If the heating output is to be adjusted, proceed as follows:

– refer  to  section  1.3  and  establish  the  desired  burner

pressure;

– remove  (pull  forwards)  the  C.H.  knob  protecting  the

potentiometer;

– set  the  burner  pressure  as  required  using  a  small

screwdriver  on  potentiometer  (1  fig.  14).  Rotate  the
screw anti-clockwise to reduce the burner pressure;

– operate the rotary switch between SUMMER and WIN-

TER  position  a  few  times  and  check  that  the  correct
burner pressure is maintained.

– Replace the C.H. knob over potentiometer.
– To set the time clock see the user instructions.

4.4

SETTING THE D.H.W. FLOWRATE

A restrictor nut is fitted into the diverting valve to reduce the
D.H.W. flow to that which will give an acceptable D.H.W. tem-
perature. To set the D.H.W. flow, procede as follows:
– select Summer position “

” and turn the D.H.W. thermo-

stat to max.;

– fully open the D.H.W. tap furthest from the boiler;
– check that the boiler is firing at maximum burner pressure;
– adjust  the  D.H.W.  flowrate  by  turning  the  restrictor  lever

on  the  divertor  valve  until  a  D.H.W.  temperature  rise  of
appr ox  35° C  is  achieved.  This  corr esponds  t o  t he
flowrates shown in 

Table 4;

– turn off the tap;
– remove the pressure gauge and refit the sealing screw;

Remember that the flow rates and corresponding temperatures
of use of hot water, given in 

Table 4, have been obtained by posi-

tioning the selector of the circulation pump on the maximum value.

Should there be any reduction in the D.H.W. flow rate, the filter
installed  on  the  inlet  to  the  pressure  switch  valve  may  need
cleaning. 
To gain access to the filter, first close the cold water, drain the
D.H.W.  circuit  via  the  lowest  tap,  make  provision  to  collect  a
small discharge of water, then loosen the brass swivel connec-
tion to access the filter.

12

4

COMMISSIONING AND TESTING

BURNER PRESSURE
TEST POINT

Fig. 13

1

6

KEY

1 “Heating output” trimmer

6 “Ignition pressure” trimmer

NOTE:  To  gain  access  to  trimmers  (1)  and  (6),

take off the central heating potentiometer knob. 

Fig. 14

Содержание FORMAT 34E BF

Страница 1: ...Format 34I 34E BF AUS ...

Страница 2: ......

Страница 3: ...showing on the pressure gauge Is the Auto Air Vent open Has the pump been rotated manually Is the gas supply working pressure correct Is the boiler wired correctly See installation manual Has the D H W flow rate been set to the customer requirements Has the customer been fully advised on the correct use of the boiler system and controls 1 TECHNICAL FEATURES AND DIMENSIONS 2 2 GENERAL REQUIREMENTS ...

Страница 4: ...tput has an adjustable output of 11 2 34 kW NOTE The boilers must not to be used for pool or spa heating The boilers must be installed only by an autho rised person 1 TECHNICAL FEATURES AND DIMENSIONS TABLE 2 Minimum clearances For ventilation For servicing ABOVE THE APPLIANCE CASING 400 mm 300 mm AT THE R H S 15 mm 15 mm AT THE L H S 15 mm 15 mm BELOW THE APPLIANCE CASING 200 mm 200 mm IN FRONT O...

Страница 5: ...kPa 0 5 Static head Maximum bar psi 3 0 43 5 Minimum bar psi 0 5 7 3 D H W pressure Minimum bar psi 1 0 14 6 Maximum bar psi 6 0 87 Weight Empty kg lb 40 88 Total full kg lb 44 7 98 Electrical supply 230 V 50 Hz Fused at 3 A Internal fuse Line F 1 6 A Maximum power consumption Watt 160 Maximum gas consumpt Natural gas m3 h 3 68 Maximum gas consumpt Propane kg h 2 74 2 70 Max working temperature C ...

Страница 6: ...lve 14 Drain plug 15 Water flow switch 16 Temperature and pressure gauge 17 Automatic by pass 18 D H W filter Fig 2 6 12 11 10 9 8 7 5 4 3 2 1 13 14 19 1 5 INTERNAL VIEW KEY 1 Control panel 2 Ignition transformer 3 Combustion chamber 4 Fan 5 Combustion analysis intakes 6 Negative pressure intake 7 Positive pressure intake 8 Air pressure switch 9 C H sensor SM 10 Main exchanger 11 100 C safety stat...

Страница 7: ...ULATIONS WHICH MAY BE APPLICABLE For installations where the heater is connected to larger systems the additional volume will need to be taken into account A temperature pressure relief valve may be needed An adhesive data plate is sticked inside the front panel it con tains all the technical data identifying the boiler and the type of gas for which the boiler is arranged 2 3 CHARACTERISTICS OF FE...

Страница 8: ... system heads H greater than 3 m The maximum flow through the by pass is about 300 l h If thermostatic radiator valves are to be installed at least one radiator should be without a thermostatic valve usu ally the bathroom radiator c The following paragraphs outline the specifications of the items fitted to the boiler 2 7 1 Pump The available head shown in fig 5 is that in excess of the appliance h...

Страница 9: ... say over 150 ppm the fitting of an in line scale inhibitor may be an advantage Consult the Local Water Undertaking if in doubt Devices capable of preventing the flow of expansion water e g non return valves and or loose jumpered stop cocks should not be fitted unless separate arrangements are made for expansion water For specific information relating to fittings eg Showers washing machines etc su...

Страница 10: ...in position using the screws provided Ensure that it is the correct way up as indicated in fig 6 3 2 HANGING THE BOILER Lift the appliance into position The upper cross member locates onto the wall mounting bracket Screw in the wall mounting bracket adjusting screws until the appliance is secure and vertical 3 3 FLUE DUCTS MODEL 34I BF The air inlet smoke outlet assembly ø 60 100 is supplied in a ...

Страница 11: ...al flue is less than 1 5 metres With outlet type C32 use the following diaphragms depending on flue length and without any additional curves Installations with vertical extension L 200 Installations with condensation code 8086908 collector code 8092803 Optional Standard Standard None diaphragm ø 86 diaphragm ø 87 5 diaphragm ø 87 5 diaphragm cód 6028623 L min 1 3 m L min 2 5 m L max 2 5 m L min 2 ...

Страница 12: ...ig 12 Disconnect the electric power supply before performing any work Warning all components in the control panel are fed with 240V Remove the three screws 7 locking the control panel in place and pull the panel forward until it can be tilted downward To access the components of the electrical panel unscrew the four screws holding the protective guard in place 5 To gain access to connector TA remo...

Страница 13: ...ving removed the three fixing screws tilt the panel downward to gain access KEY 1 Temperature and pressure gauge 2 Time programmer housing 3 Rotary switch 4 Main PCB 5 Earth faston 6 Control panel protection 7 Cover TA 8 Connector TA 9 Fixing screw ...

Страница 14: ... at least 5 minutes and check the burner pressure The heating input is factory set as stated in Table 4 If the heating output is to be adjusted proceed as follows refer to section 1 3 and establish the desired burner pressure remove pull forwards the C H knob protecting the potentiometer set the burner pressure as required using a small screwdriver on potentiometer 1 fig 14 Rotate the screw anti c...

Страница 15: ...r Explain and demonstrate the lighting and shutdown proce dures Advise the householder on the efficient use of the system including the use and adjustment of all system controls for both D H W and C H Advise the user of the precautions necessary to prevent damage to the system and to the building in the event of the system remaining inoperative during frost conditions Explain the function of the b...

Страница 16: ...care not to dam age the insulation Remove the electrode by unscrewing it from the burner manifold Unscrew the burner manifold union and locking nut Lift the front of the burner to disengage manifold thread and then lift the burner clear Remove the burner manifold by disconnecting the four screws Inspect and if necessary clean the injectors electrodes and the main burner bars 5 1 2 Model FORMAT 34E...

Страница 17: ...e maximum temperature always with the primary controlled between 80 C and 70 C During the entire duration of the testing the hot water taps must remain open After verifying the combu stion the boiler should be switched off by placing the selector on the OFF position then return the selector to the desired function ATTENTION After about 15 minutes or once the hot water request has been fulfilled th...

Страница 18: ... 5 8 CLEANING THE C H WATER FILTER fig 18 To clean the filter close the delivery return on off taps turn off the power to the control panel remove the casing and empty the boiler using the drain provided 14 fig 2 until the hydrometer shows zero Place a container for collection underneath the filter unscrew the cap and proceed to clean the filter removing impurities and limestone deposits Check the...

Страница 19: ...al block Test leads from L to N meter reads approx 240 V ac Test leads from L to E meter reads approx 240 V ac Test leads from N to E meter reads from 0 to 15 V ac 6 4 RESISTANCE TO EARTH CHECK Appliance must be disconnected from main supply and meter on Ω ohm x 100 scale All switches including thermostat on test leads from L to E if meter reads other than infinity there is a fault which should be...

Страница 20: ...n transformer Does it spark now Turn the clock to the right position Close room thermostat contact Replace the fan Is there voltage available to the pump Replace the clock Check pump connection Is pump shaft free to rotate Replace the pump Make it free to rotate Has the PCB ignition locked out after 10 seconds without flame at the burner Has the PCB ignition locked out after 10 seconds with flame ...

Страница 21: ... there 230V ac available at the fan terminals Replace the PCB Replace the pump Replace the divertor valve Replace the fan Check filter at inlet of hydraulic group Has the PCB ignition locked out after 10 seconds without flame at the burner Has the PCB ignition locked out after 10 seconds with flame at the burner before lock Is the gas available Open the gas cock Is the safety thermostat OK Replace...

Страница 22: ...ng removed the link To remote control the boiler connect an external clock to the terminals 10 11 24 V of the TA connector and set the built in clock to constant mode see user instructions for details JUMPERS POSITION AND FEATURES JUMPER POSITION AND FEATURE SUPPLY POSITION CLOSED OPEN J7 METANO GPL Ready to function with LPG Ready to function with natural gas Open J8 ANN RIT Ignition delay cancel...

Страница 23: ...5 1 Disconnect the electrical connections and the pressure sensing pipes to the fan Note the position of the earth conductor Unscrew the three screws securing the fan Drop and tilt the fan forwards and remove in a down wards direction Re assemble in reverse order Ensure that the earth con nection is correctly refitted Note that the polarity Line and Neutral is immaterial 8 4 MAIN BURNER Remove the...

Страница 24: ...e in reverse order referring to the wiring dia grams section 7 if necessary Ensure that the pressure sensing lead is correctly connected to the low pressure connection on the pressure switch marked P2 8 8 OVERHEAT THERMOSTAT The overheat thermostat is situated on the flow pipe below the sealed chamber 11 fig 3 Remove the casing front panel as described in section 5 1 Disconnect the two overheat th...

Страница 25: ...rarily Refer to section 3 5 Remove the adjusting screws on the wall mounting brack et thereby allowing the appliance to move slightly for wards at the top Lift the expansion vessel out of the appliance through the top Replace the expansion vessel and re assemble in reverse order Re pressurise and re commission the system as described in section 4 1 8 16 PRESSURE TEMPERATURE GAUGE Remove the casing...

Страница 26: ...24 1 1 INTRODUCTION 25 1 3 OPERATING INSTRUCTIONS 1 4 MINIMUM CLEARANCES 1 5 ROUTINE SERVICING 26 1 6 GENERAL INFORMATION 1 7 SAFETY 1 8 TIME CLOCKS optional CONTENTS User instructions ...

Страница 27: ...ly then turn it to the SUMMER position the burner should now light Turn off the tap Check that the room thermostat and time clock are call ing for heat Turn the heating potentiometer D to maxi mum fully clockwise Turn the selector switch summer winter to the WINTER position and the burner will light to serve the heating load Set the required temperature for the C H and D H W by rotating the potent...

Страница 28: ...ch is coloured green and yellow must be con nected to the terminal in the plug which is marked with the letter E or by the earth symbol or coloured green and yel low the wire which is coloured blue must be connected to the terminal marked with the letter N or coloured black the wire which is coloured brown must be connected to the ter minal marked with the letter L or coloured red 1 6 5 Ventilatio...

Страница 29: ...f the dial The tappets that remain at the centre of the dial will be the OFF periods N B The smallest switching time ON or OFF is 15 minutes To select Timed mode move the selector switch in the middle of the clock face to the position To select Constant mode move the selector switch in the middle of the clock face to the I position To select OFF mode move the selector switch in the mid dle of the ...

Страница 30: ...od of twelve months commencing from the date of commissioning of the boiler The Licensed Installer must complete the following informa tion Failure to do so may cause the above Warranty to beco me null and void MODEL NO __________________________________________________________________________ SERIAL NO __________________________________________________________________________ GAS TYPE ___________...

Страница 31: ... and illustrations provided in this manual have been carefully prepared but we reserve the right to make changes and improvements in our products that may affect the accuracy of the information contained in this manual ...

Страница 32: ...Cod 6272266 A 05 09 Documentation Dpt HYDRONIC SYSTEMS Australia PTY Ltd 11 Fiveways Boulevard Keysborough Victoria 3173 Telephone 1300 00 1800 Facsimile 9798 5133 www huntheat com au HUNT HEATING ...

Отзывы: