background image

Supplied By www.heating spares.co  Tel. 0161 620 6677

8

The  system  design  should  incorporate  the  connections
appropriate to one of these methods.

e) The following paragraphs outline the specifications of the

items fitted to the boiler.

2.9.1

Pump

The available head shown in fig. 5 is that in excess of the appli-
ance hydraulic resistance, i.e. that available for the system at
any  given  heating  load  up  to  the  maximum  output  in  C.H.
mode. Never reduce the pump speed below maximum as this
will reduce D.H.W. output. The pump speed is indicated on the
side of the pump speed selector switch (if fitted).

2.9.2

System volume (total water content)

The  following  Table  gives  the  maximum  system  volume  that
the  integral  expansion  vessel  can  sustain  under  different
charge pressure conditions. 
If the system volume exceeds that shown, an additional expan-
sion vessel must be fitted and connected to the heating system
primary return pipe as close as possible to the appliance. 
If an extra vessel is required, ensure that the total capacity of
both vessels is adequate. Further details are available in the
current issues of BS5449 and BS6798.

NOTE: If the pressure gauge indicates 2.65 bar or greater
when  the  appliance  is  at  maximum  temperature  with  all
radiators  in  circulation  an  extra  expansion  vessel  is
required.

2.9.3

Pressure gauge

A pressure gauge is mounted on the appliance facia panel.

2.9.4

Safety valve

A safety valve set at 3 bar (43.5 psi) is fitted to the appliance

and a discharge pipe is routed to outside of the appliance. This
discharge  pipe  should  be  extended  to  terminate  safely  away
from  the  appliance  and  where  a  discharge  would  not  cause
damage  to  persons  or  property  but  would  be  detected.  The
pipe should be able to withstand boiling water, be a minimum
of 15 mm in diameter, and installed with a continuous fall.

2.10

D.H.W. SYSTEMS

– Check  that  the  mains  supply  pressure  is  within  the  pre-

scribed limits (

Table 4).

If necessary, a pressure reducing valve should be fitted to
the mains supply before the D.H.W. inlet connection.

– A  maximum  D.H.W.  flow  rate  of:  10.3  l/m  (2.3  gpm)  for

“FORMAT 80 C”

, 13 l/m (2.9 gpm) for 

“FORMAT 100 C”

and  14  l/m  (3.1  gpm)  for 

“FORMAT  110  C” 

is  recom-

mended. Higher flow rates will not damage the appliance
but  may  lower  the  water  temperature  below  an  accept-
able level.

– If  the  appliance  is  installed  in  an  area  where  the  tempo-

rary  hardness  of  the  water  supply  is  high,  say  over  150
ppm,  the  fitting  of  an  in  line  scale  inhibitor  may  be  an
advantage.  Consult  the  Local  Water  Undertaking  if  in
doubt.

– Devices capable of preventing the flow of expansion water:

e.g.  non  return  valves  and/or  loose-jumpered  stop  cocks
should  not  be  fitted  unless  separate  arrangements  are
made for expansion water.

– For  specific  information  relating  to  fittings  (eg.  Showers,

washing  machines  etc.)  suitable  for  connection  in  the
D.H.W. circuit, consult the Local Water Undertaking, how-
ever the following information is given for guidance.

2.10.1 Domestic hot/cold water supply 

taps and mixing taps

All  equipment  designed  for  use  at  mains  water  pressure  is
suitable.

2.10.2 Showers

If a shower control is supplied from the appliance it should be
of the thermostatic or pressure balanced type. Thermostatic
type  shower  valves  provide  the  best  comfort  and  guard
against water at too high temperature. Existing controls may
not be suitable, refer to the shower valve manufacturer.

2.10.3 Bidets

Providing that the appliance is of the over-rim flushing type, the
outlets are shrouded and it is impossible to attach a temporary
hand held spray, no anti syphonage device is necessary.

Vessel  charge  and  initial  system

pressure

Total  water  content  of  system

using 8 l (1.76 gal) capacity expan-

sion  vessel  supplied  with  appliance

For systems having a larger capaci-

ty multiply the total system capacity

in litres (gal) by the factor to obtain

the total minimum expansion vessel

capacity required litres (gal)

bar

psi

l

gal

0.5

7.3

96

21.1

.0833

1.5

21.8

51

11.2

.156

1.0

14.5

74

16.2

.109

TABLE 6

Содержание Format 100 C

Страница 1: ...Supplied By www heating spares co Tel 0161 620 6677 Format C Installation and servicing instructions GB PLEASE LEAVE THIS INSTRUCTION WITH THE USER ...

Страница 2: ...system been flushed in accordance with the guidelines given in BS7593 Treatment of water in domes tic hot water central heating systems Is the system and boiler full of water and the correct pressure showing on the pressure gauge Is the Auto Air Vent open Has the pump been rotated manually Is the gas supply working pressure correct Is the boiler wired correctly See installation manual Has the D H ...

Страница 3: ...8 3 INSTALLING THE BOILER 3 1 FIXING THE WALL MOUNTING BRACKET 9 3 2 HANGING THE BOILER 3 3 FLUE DUCTS PREPARATION 3 4 FLUE AND TERMINAL INSTALLATION 10 3 5 SEPARATE DUCTS 12 3 6 WATER CONNECTIONS 13 3 7 GAS CONNECTIONS 3 8 SAFETY VALVE CONNECTION 3 9 WIRING INSTRUCTIONS 4 COMMISSIONING AND TESTING 4 1 FILLING THE WATER SYSTEM 15 4 2 COMMISSIONING THE BOILER 4 3 SETTING THE C H INPUT 4 4 SETTING T...

Страница 4: ... 8 2 COMBUSTION CHAMBER INSULATION 8 3 FAN ASSEMBLY 8 4 MAIN BURNER 8 5 IGNITION DETECTION ELECTRODE 8 6 GAS VALVE 8 7 AIR PRESSURE SWITCH 24 8 8 OVERHEAT THERMOSTAT 8 9 THERMISTOR 8 10 DRIVER PCB 8 11 PUMP MOTOR 8 12 D H W HEAT EXCHANGER 25 8 13 DIVERTOR VALVE COMPLETE 8 14 DIVERTOR VALVE MICROSWITCH ASSEMBLY 8 15 C H EXPANSION VESSEL 8 16 PRESSURE TEMPERATURE GAUGE 8 17 SAFETY VALVE 8 18 AUTOMAT...

Страница 5: ...e boilers can also be fitted with a separate flues kit see section 3 for details The boiler is designed for use with sealed primary water sys tems and is supplied fully assembled and equipped with com plete valve packs The boiler can be used with a 24V room thermostat class II according to EN 60730 1 This booklet provides instructions for the boiler models FORMAT 80 C FORMAT 100 C FORMAT 110 C wit...

Страница 6: ...7 7 60 000 22 5 77 000 5 6 2 3 12 2 14 9 4 9 6 0 X G20 G31 19 8 68 000 25 0 86 000 6 8 2 7 14 9 18 0 6 0 7 2 X G30 22 0 75 000 27 6 94 000 8 2 3 3 17 9 21 3 7 2 8 6 24 2 83 000 30 1 103 000 9 6 3 8 21 2 24 8 8 5 10 0 26 5 90 000 32 6 111 000 11 1 4 5 24 7 28 5 9 9 11 4 28 8 98 000 35 1 120 000 12 7 5 1 28 5 36 5 11 4 14 7 DOMESTIC HOT WATER Max 28 8 98 000 35 1 120 000 12 7 5 1 28 5 36 5 11 4 14 7...

Страница 7: ...in 2 0 5 2 0 5 2 0 5 D H W flow rate at a temperature rise of 30 C l min gal min 11 2 2 5 13 8 3 0 15 1 3 3 35 C l min gal min 9 6 2 1 11 9 2 6 12 9 2 8 Static head Minimum bar psi 0 5 7 3 0 5 7 3 0 5 7 3 Maximum bar psi 3 0 43 5 3 0 43 5 3 0 43 5 D H W pressure Minimum bar psi 1 0 14 6 1 0 14 6 1 0 14 6 Maximum bar psi 6 0 87 6 0 87 6 0 87 Weight Empty kg lb 38 84 40 88 40 88 Total full kg lb 41 ...

Страница 8: ...er and the fan will run at full speed once the air pressure switch has been proved the burner will light The burner output then automatically adjusts to suit the system demand as the temperature of the heating water in the boiler approaches that set by the adjustable central heating control knob the burner output is reduced When this set tem perature is reached the burner extinguishes and the fan ...

Страница 9: ...or compartment may be used provid ed it is modified accordingly Where installation will be in an unusual location special procedures may be necessary BS6798 gives detailed guidance on this aspect 2 3 FLUE TERMINAL POSITION Detailed recommendations for flue installation are given in BS5440 1 The following notes are for general guidance The boiler MUST be installed so that the terminal is exposed to...

Страница 10: ...re mains pressure exceed 6 bar a pressure reducing valve must be fitted in the D H W inlet 2 8 1 Treatment of Water Circulating Systems All recirculatory systems will be subject to corrosion unless an appropriate water treatment is applied This means that the efficiency of the system will deteriorate as corrosion sludge accumulates within the system risking damage to pump and valves boiler noise a...

Страница 11: ...ing spares co Tel 0161 620 6677 7 TYPICAL SYSTEM DESIGN ALTERNATIVE METHODS OF FILLING A SEALED SYSTEM NOTE A drain cock should be installed at the lowest point of the heating circuit and beneath the appliance Fig 6 Fig 7 ...

Страница 12: ...hin the pre scribed limits Table 4 If necessary a pressure reducing valve should be fitted to the mains supply before the D H W inlet connection A maximum D H W flow rate of 10 3 l m 2 3 gpm for FORMAT 80 C 13 l m 2 9 gpm for FORMAT 100 C and 14 l m 3 1 gpm for FORMAT 110 C is recom mended Higher flow rates will not damage the appliance but may lower the water temperature below an accept able leve...

Страница 13: ...izontal Refer to fig 12 14 Accurately measure the wall thickness and note this dimension for later use Secure the wall mounting bracket in position using the screws provided Ensure that it is the correct way up as indicated in fig 8 3 2 HANGING THE BOILER Lift the appliance into position The upper cross member locates onto the wall mounting bracket Screw in the wall mounting bracket adjusting scre...

Страница 14: ...ontal Push the junction collar B over the air duct until the air duct touches the inner part of the collar where the diame ter becomes smaller Push the elbow socket into the junction collar and onto the flue duct Fit the jointing clamp G over the juction collar Place the gasket F under the flange of the elbow and fit the elbow onto the flue manifold taking care to ensure that the silicon seal on t...

Страница 15: ...tres each additional 45 elbow reduces the available lenght by 0 45 metres NOTE Sime flue systems are suitable for installation with SE duct systems 11 Push flue duct and terminal into air duct from this end Fig 13 KEY A Elbow flange B Junction collar C Outer duct D Aluminium ring E Rubber sealing ring F Inner duct c w terminal G Gasket ø 95 125 x 2 H Fixing screw I Protective jointing clamp J Inne...

Страница 16: ...l 40 m for 110 C model For head losses in the fittings refer to Table 7 12 1 2 3 4 6 165 110 165 K ø 80 ø 80 100 92 Fig 17 KEY 1 Sponge rubber gasket ø 125 95 2 Fixing screw 3 Smoke outlet flange 4 Air intake diaphragm 6 Air smoke manifold with intakes 80 C 100 C 110 C K mm 180 205 Fig 18 Model FORMAT 100 C N segments Total horizontal lenght to remove inlet outlet in metres none 0 3 3 n 1 3 3 6 7 ...

Страница 17: ...NECTIONS Screw the gas cock into the internal thread in the gas inlet connection using a suitable jointing compound Connect the gas supply pipe 3 8 SAFETY VALVE CONNECTION The appliance safety valve is located towards the R H S of the boiler and the discharge pipe is supplied loose Remove the two selftapping screws and lower the control box to improve access Connect the discharge pipe to the valve...

Страница 18: ...30 1 clean contact Carry out electrical system checks through a suitable test meter earth continuity polarity resistance to earth and short circuit Re secure control box Ensure sufficient length of cable to allow access to control panel 14 4 1 2 3 5 6 7 8 9 Fig 20 KEY 1 Temperature and pressure gauge 2 Time programmer housing 3 Rotary switch 4 Main PCB 5 Earth faston 6 Control panel protection 7 C...

Страница 19: ...f modulation is suspected open all D H W taps to maximise flow and recheck burner pres sure Check also the inlet pressure with the burner alight this should be 20 mbar 1 0 mbar standing pressure the working inlet pressure limited to a loss no greater than 1 0 mbar for natural gas If it is necessary to adjust the D H W burner pressure the method is described in section 8 6 Reduce the D H W draw off...

Страница 20: ...alve may need cleaning To gain access to the filter first close the cold water isolation valve 20 figure 2 drain the D H W circuit via the low est tap make provision to collect a small discharge of water then loosen the brass swivel connection to access the filter 4 5 FINAL CHECKS Re light and test for gas soundness Re fit the casing front panel and securing brackets Set the C H and D H W potentio...

Страница 21: ...aking care not to dam age the insulation Remove the electrode by unscrewing it from the burner manifold Unscrew the burner manifold union and locking nut Lift the front of the burner to disengage manifold thread and then lift the burner clear Remove the burner manifold by disconnecting the four screws Inspect and if necessary clean the injectors electrodes and the main burner bars 5 2 FAN ASSEMBLY...

Страница 22: ...mble all the components in reverse order and replace all the gaskets fitted in the gas line Ensure that all seals are correctly fitted and that the pres sure sensing line is correctly fitted Check that the fan earth connection is correctly re fitted Note that the fan polarity Line and Neutral is immaterial Check for gas soundness before fitting the casing 5 7 RE COMMISSIONING Turn on the gas suppl...

Страница 23: ...t at appliance terminal block Test leads from L to N meter reads approx 240 V ac Test leads from L to E meter reads approx 240 V ac Test leads from N to E meter reads from 0 to 15 V ac 6 4 RESISTANCE TO EARTH CHECK Appliance must be disconnected from main supply and meter on Ω ohm x 100 scale All switches including thermostat on test leads from L to E if meter reads other than infinity there is a ...

Страница 24: ... the electrode and ignition transformer Does it spark now Turn the clock to the right position Close room thermostat contact Replace the fan Is there voltage available to the pump Replace the clock Check pump connection Is pump shaft free to rotate Replace the pump Make it free to rotate Has the PCB ignition locked out after 10 seconds without flame at the burner Has the PCB ignition locked out af...

Страница 25: ...g Check pump connection Is there 230V ac available at the fan terminals Replace the PCB Replace the pump Replace the divertor valve Replace the fan Check filter at inlet of hydraulic group Has the PCB ignition locked out after 10 seconds without flame at the burner Has the PCB ignition locked out after 10 seconds with flame at the burner before lock Is the gas available Open the gas cock Is the sa...

Страница 26: ... AND FEATURE SUPPLY POSITION CLOSED OPEN J7 METANO GPL Ready to function with LPG Ready to function with natural gas Open J8 ANN RIT Ignition delay cancelled Ignition delay operating Open In the heating phase the electronic board is programmed to include a burner technical delay interval of approx 3 minutes which occurs both at system cold starting and at subsequent re ignitions The aim is to over...

Страница 27: ...the fan Drop and tilt the fan forwards and remove in a down wards direction Re assemble in reverse order Ensure that the earth con nection is correctly refitted Note that the polarity Line and Neutral is immaterial 8 4 MAIN BURNER Remove the main burner by following section 5 1 Transfer the ignition electrode onto the new burner assembly Re assemble in reverse order Check the electrode gaps fig 28...

Страница 28: ...itch Re assemble in reverse order referring to the wiring dia grams section 7 if necessary Ensure that the pressure sensing lead is correctly connected to the low pressure connection on the pressure switch marked P2 8 8 OVERHEAT THERMOSTAT The overheat thermostat is situated on the flow pipe below the sealed chamber 11 fig 3 Remove the casing front panel as described in section 5 1 Disconnect the ...

Страница 29: ...essel union on the C H return pipe If a rear flue outlet is used it is necessary to disengage the flue and air duct temporarily Refer to section 3 5 Remove the adjusting screws on the wall mounting brack et thereby allowing the appliance to move slightly for wards at the top Lift the expansion vessel out of the appliance through the top Replace the expansion vessel and re assemble in reverse order...

Страница 30: ...15 48 6281502 Flow water switch spare parts 49 6013101 Automatic air vent 50 6017210 Manual air vent 1 4 51 6281500 Straight fitting 3 4 52 6281501 Straight fitting 1 2 53 6226421 O ring Dalmar R12 54 6281522 14 plate heat exchanger kit 80C 100C 54 A 6281525 16 plate heat exchanger kit 110C 55 6281504 Divertor valve 56 6168401 Locking nut for pipe Ø 15 57 6226607 Pipe fixing spring 58 6272301 Circ...

Страница 31: ... Washer MPMV 3318 4 6220601 O ring R1 MPMV 3325 5 6218500 Clip Ø 17 for diverting valve 6 6153101 Diaphragm assembly for divertor valve Position Code Description 7 6231201 Brass ring nut MPMV 3320 8 6223902 Teflon short spacer MPMV 3315 9 6222000 D H W filter MPMV 3326 10 6220602 O ring 4093 MPMV 18 11 6223903 Teflon long spacer MPMV 3316 9 2 DIVERTOR VALVE Fig 30 a ...

Страница 32: ...19 6147406 Air smoke manifold plug M14x1 5 20 6226417 O ring 3043 21 6242602 Air smoke manifold screw 22 6248803 Lip seal for Ø 60 pipe 23 6028706 Air smoke manifold gasket 24 6028707 Air intake gasket 25 6288000 Air intake 26 6257512 Air deflector for separate ducts 30 5190600 Smoke chamber assembly 80C Position Code Description Model 30 A 5190610 Smoke chamber assembly 100C 110C 31 2016020 Locke...

Страница 33: ...apping screw 73 6289800 Control panel 74 6273210 Guidelight 2 ways out 75 6217005 Temperature and pressure gauge 76 6230687 Main PCB with ignition 77 6201501 Trimmer spindle Ø 5 78 6201505 Trimmer spindle Ø 6 79 6260701 Rotary switch 80 2211610 Earth faston Position Code Description Model 82 6289900 Control panel protecting cover 83 6290300 Control panel cable cover 84 6290200 Room stat connection...

Страница 34: ...Supplied By www heating spares co Tel 0161 620 6677 ...

Страница 35: ...ersion of the boiler please stick onto the casing panel the plate showing the relevant fee ding gas which is included in the kit NOTE When reassembling components which you have removed replace gas seals test all gas con nections after assembly using soapy water or a product made specifically for the purpose being sure not to use open flame Conversion must be performed by authorised personnel only...

Страница 36: ...ting spares co Tel 0161 620 6677 Cod 6272251B Documentation Dpt Sime Ltd Unit D2 Enterprise Way Bradford Road Bradford West Yorkshire BD10 8EW Tel 0870 9911114 Fax 0870 9911115 www sime ltd uk e mail enquiries sime ltd uk ...

Отзывы: