3.1 

CONTROL BOX

The  boiler  is  equipped  with  FM  12  elec-

tronic  control  and  protection.  Ignition

and  flame  detection  are  controlled  by

two  electrodes  which  guarantee  maxi-

mum  safety  with  inter vention  times,

within  1  second  for  accidental  switching

off or gas failure.

3.1.1 

Operating cycle

Before igniting the boiler, use a voltmeter

to make sure that the electrical connec-

tion  t o  t he  t erminal  block  has  been

installed  properly,  with  respect  to  the

position of the live and neutral points, as

shown in the diagram. 

Then  press  the  switch  on  the  terminal

block so that the boiler begins to operate

upon  request  either  for  heating  or  for

drawing  hot  water:  a  discharge  current

is  sent  to  the  ignition  electrode  through

the  FM  12  programmer,  and  the  gas

valve opens at the same time. 

Burner  ignition  normally  takes  place

within 2 or 3 seconds from the moment

that  electric  discharge  on  the  ignition

electrode has begun. 

When  the  pilot  burner  is  turned  on  the

FM12  device  opens  the  second  electric

valve and proceeds to the ignition of the

principal  burner.  However,  it  is  possible

for  ignition  failures  to  occur,  with  conse-

quent  activation  of  the  signal  indicating

that the equipment has "locked out". Fai-

lures may be due to one of the following

causes:

- Gas failure

The control box runs through the cycle

normally sending electric power to the

ignition electrode. The electrode conti-

nues  spark  discharge  for  a  maximum

of 60 sec.

If  the  pilot  burner  does  not  ignite,  the

control box "locks out".

This  may  occur  upon  first  ignition  or

af ter  long  periods  of  boiler  lay-of f

when there is air in the pipes.

It  may  be  caused  by  the  failure  of  the

gas  valve  to  open  owing  to  a  break  in

the electric coil.

– Ignition electrode fails to spark

In the boiler, only the opening of gas to

the burner appears to occur. After 60

sec. the control box "locks out". 

This  may  be  due  t o  ther e  being  a

break  in  the  wire  of  the  electrode  or

the  wire  not  being  properly  fastened

to  the  terminal  of  the  control  box;  or

alternatively,  the  transformer  has

burnt out.

– No detection of flame

The continuous spark discharge of the

electrode is noted to continue starting

from ignition even though the pilot bur-

ner  is  lit.  After  60  seconds  have  ela-

psed,  the  sparks  cease,  the  burner

goes out, and the warning lamp indica-

ting equipment "lock-out" lights up. 

This  occurs  when  the  positions  of  live

and  neutral  have  not  been  respected

on the terminal block. There is a break

in the wire of the sensing electrode or

the  electrode  itself  is  ear thed:  the

electrode is worn out and needs repla-

cing. The control box is faulty.

When  there  is  a  sudden  voltage  failure,

the  burner  shuts  down  immediately;

when  the  power  supply  returns,  the  boi-

ler will start up again automatically.

3.2  

REGULATING THERMOSTAT

"EKO  OF"

boilers  are  equipped  with  a

regulating thermostat with a double con-

tact  having  differentiated  settings  (6  fig.

2).  This  makes  it  possible  to  obtain  a

reduction  of  heat  output  before  the  bur-

ner goes out completely, by means of the

coil  assembly  installed  on  the  gas  valve

regulator. 

This step-modulation system affords the

following advantages:

– higher overall boiler efficiency;

–  containment  within  acceptable  values

of  the  increase  in  temperature  that

takes place in the cast-iron body (heat

inertia) when the burner goes out.

3.3

SMOKE SAFETY DEVICE 

‘EKO 3/6 OF - 3/4 OF PVA’

This  is  a  safety  device  against  possible

smoke  emission  into  the  environment

due  to  inefficiency  or  partial  obstruction

of the flue.

The  safety  device  goes  into  action  by

blocking operation of the gas valve when

the return of the smoke into the environ-

ment  is  continuous  and  in  possibly  dan-

gerous quantities.

The  device’s  intervention  consists  in  the

‘locking  out’  of  the  control  box  because

the burner fails to be ignited; in this case,

press  the  release  button  and  the  boiler

will start up again automatically.

Should the boiler continue to "lock out", it

will be necessary to make a careful check

of the flue pipe, making all the necessary

modifications and amendments so that it

can work properly.

3.4 

RESIDUAL PREVALENCE IN 

THE  ‘3/4 OF PVA’ SYSTEM

In  the  diagram  fig.  8,  you  can  see  the

representation  of  the  residual  prevalen-

ce  in  function  of  the  capacity,  within  the

heating plant.

3.5 

LOSS OF LOAD 

BOILER CIRCUIT ‘3/12 OF’

The load losses are shown in the diagram

of fig. 8/a.

31

IT

GB

FR

BE

DE

FEATURES

200

150

100

50

0

100

200

Portata l/h

p mbar

250

300

0

350

400

450

300

400

500

600

800

1000

2000

2500

1500

500

550

600

3 OF PVA

4 OF PVA

Fig. 8

Flow rate l/h

Содержание EKO 3 OF

Страница 1: ...he discharge channel of the combustion waste is free Check that gate valves are open if there are any Check that the heating system has been filled with water and that air has been bled out of it Make sure that the circulator is not blocked Purge the system bleeding off the air present in the gas pipe by operating the pressure relief valve on the gas valve inlet FONDERIE SIME Co Ltd based in Garbo...

Страница 2: ...E BOILER 1 2 DIMENSIONS 1 2 1 EKO 3 6 OF 3 4 OF PVA version CONNECTIONS M Delivery to heating system R 1 UNI ISO 7 1 M1 Delivery to heating system PVA ver R 1 UNI ISO 7 1 G Gas supplier R 3 4 UNI ISO 7 1 R Return to heating system R 1 UNI ISO 7 1 S Boiler discharge pipe Rp 1 2 UNI ISO 7 1 C1 Boiler loading vers PVA Rp 1 2 UNI ISO 7 1 L P K ø D 3 0F 460 675 110 3 OF PVA 460 675 60 110 4 0F 560 675 ...

Страница 3: ...t 16 5 mbar and when downstream at 11 5 mbar 6 Intermittent pilot 7 Combustion chamber door 8 Burner manifold 9 Pressure intake 10 Pump EKO 7 OF EKO 8 12 OF KEY 1 Gas valve 2 Probe measurement sheath 3 Control Panel 4 Gas pressure switch with minimum rates of pressure in the system calibrated for G20 in ascent at 16 5 mbar and in descent at 11 5 mbar 6 Intermittent pilot 7 Combustion chamber door ...

Страница 4: ...312BP4117 1312BP4117 Category II2H3P II2H3P II2H3P II2H3P II2H3P II2H3P Type B11BS B11BS B11BS B11BS B11BS B11BS Maximum operating pressure bar 4 4 4 4 4 4 Maximum operating temperature C 85 85 85 85 85 85 Water contained in Boiler l 14 18 17 22 20 23 Boiler s cast iron elements n 3 3 4 4 5 6 Temperature regulation C 40 85 40 85 40 85 40 85 40 85 40 85 Expansion tank Capacity pressure preloading l...

Страница 5: ...8 1312BP4118 1312BP4118 1312BP4118 Category II2H3P II2H3P II2H3P II2H3P II2H3P II2H3P Type B11 B11 B11 B11 B11 B11 Maximum operating pressure bar 4 4 4 4 4 4 Maximum operating temperature C 85 85 85 85 85 85 Water contained boiler l 26 29 32 35 38 41 Boiler s cast iron elements n 7 8 9 10 11 12 Temperature regulation C 40 85 40 85 40 85 40 85 40 85 40 85 Principle Gas Nozzles Quantity of Nozzles n...

Страница 6: ...ed 20 C For this reason it is advisable to install a mixer valve CAUTION The system circulation pump or pumps must go into action at the time of boiler ignition For this reason you are recommended to use an auto matic system of precedence The gas connection must be made using seamless steel pipe Mannesmann type which is galvanized and has threaded joints provided with gaskets excluding three piece...

Страница 7: ...ust be rounded off with a radium of no less than 20 mm hydraulically equivalent sections are also permitted fitted with a chimney at the top the outlet of which must be outside the so called reflux area to prevent for mation of counter pressure preven ting the products of combustion from being freely released into the environ ment It is thus necessary to comply with the minimum heights shown in fi...

Страница 8: ...tallation of an optional control unit RVA 43 222 cod 8096303 marked with different colours black orange and brown fig 5 Connectors are polarised so that the order cannot be inverted To install the control unit connect these connectors and remove jumpers 13 14 and 15 17 marked with bold letters in the electric system of the figure 6 from the terminal board The control unit also permits the use of r...

Страница 9: ...E Type QAC31 outdoor temperature probe optional SC Type QAZ21 boiler immersion probe optional SS Type QAZ21 boiler immersion probe optional PI Heating system pump vers 3 4 OF PVA PB Boiler pump C Connectors of the control unit black orange brown F Fuse T 200 mA TI Insulation transformer only for FR BE PBY Recirculation pump TM Minimum temperature thermostat Only for vers 3 4 OF PVA NOTE During the...

Страница 10: ...lation Boiler temperature is controlled on the basis of climate permitting envi ronmental compensation There is direct heating circuit mana gement with pump for each control ler Automatic adaptation to a climatic curve on the basis of the building s thermal inertia and the presence of free heat sources with environmen tal compensation On off optimisation accelerated hea ting and early off feature ...

Страница 11: ...en though the pilot bur ner is lit After 60 seconds have ela psed the sparks cease the burner goes out and the warning lamp indica ting equipment lock out lights up This occurs when the positions of live and neutral have not been respected on the terminal block There is a break in the wire of the sensing electrode or the electrode itself is earthed the electrode is worn out and needs repla cing Th...

Страница 12: ... the working pressures have been adjusted reseal the regulators When the gas pressures are to be reset this must be done following a set order first the maximum pressure and then the minimum 4 INSTRUCTIONS FOR USE AND MAINTENANCE 9 1 4 3 7 8 2 KEY 1 Coil EV1 2 Pressure regulator 3 Coil assembly 4 Coil EV2 7 Pressure inlet upstream 8 Pressure inlet downstream 9 Gas pressure switch of minimum rate a...

Страница 13: ...n upstream at 27 mbar and when downstream at 22 mbar In the models with a gas valve VRB 25PA instead turn the knob of the mini mum rate pressure 9 fig 9 chan ging the rate from 11 5 mbar for G20 to 22 mbar for G31 In order to regulate the power heat fol low the instructions of 4 1 Once the operating pressures have been changed seal the regulators Apply the plate provided in the kit for identificat...

Страница 14: ...ich covers a rate from 40 to 85 oC The temperature that has been fixed can be controlled on the thermometer SAFETY THERMOSTAT fig 16 The safety thermostat is of the manually resetting type and turns on IGNITION AND FUNCTIONING 0 120 20 100 40 80 6 C Fig 14 Fig 15 0 120 20 100 40 80 6 C USER S INSTRUCTIONS WARNINGS In case of fault and or incorrect equipment operation deactivate the boiler without ...

Страница 15: ...y Should the boiler continue to lock out it will be necessary to make a careful check of the flue pipe making all the necessary modifications and amendments so that it can work properly LOCK OUT RESET OF THE CONTROL BOX fig 18 If the burner fails to ignite the red led on the reset button will turn on Press the button to restart the boiler automatically fig 18 Should the boiler lock out again you m...

Страница 16: ...emperature Increase or reduce the temperature of the room with the regulating knob In the case of reduced temperature NOTE After each regulation wait at least two hours for the new temperature to expand through the room TO CHANGE THE HEATING PERIODS With reference to the day chosen set the changes as following NOTE The heating periods automatically repeat on a weekly basis To this end select the a...

Отзывы: