35
TABLE OF ACTIVATED ALARMS/FAULTS
Type
No.
Description
PAR
A0
Last activated alarm/fault
PAR
A1
Last but one activated alarm/fault
PAR
A2
Third from last activated alarm/fault
PAR
A3
Previous activated alarm/fault
PAR
A4
Previous activated alarm/fault
PAR
A5
Previous activated alarm/fault
PAR
A6
Previous activated alarm/fault
PAR
A7
Previous activated alarm/fault
PAR
A8
Previous activated alarm/fault
PAR
A9
Previous activated alarm/fault
9.7
Checks after commissioning
9.7.1
Chimney sweeper function
The chimney sweeper function is used by the qualified
maintenance technician to check the mains gas pressure, detect
the combustion parameters and to measure the combustion
efficiency required by legislation in force.
This function lasts 15 minutes and is activated by proceeding
as follows:
– disassemble the smoke outlet duct of the
Brava Slim HE 20 R e
and
Brava Slim HE 40 R e
, if not already removed
– if the panel (2) has not already been removed, remove the
two screws (1), pull the front panel (2) forwards and release it
from the top by lifting it
2
1
Fig. 42
– remove the screws (3) securing the control panel (4)
– move the panel (4) upwards (a) but keeping it in the side
guides (5) to the end of travel
– bring it forwards and down (b) until it is horizontal
3
a
b
5
4
Fig. 43
– close the gas valve
– loosen the screw of the "mains pressure" point (6) and connect
a pressure gauge
6
Fig. 44
– open the gas valve
– power the boiler by setting the main switch to "ON"
ON
Fig. 45
– press the button
y
for at least 1 second until "SUMMER"
mode
l
has been selected
– press and hold down the buttons
<
and
>
at the same time
for approximately 10 seconds until the message “Hi” appears
on the display together with the flashing symbols
l
and
n
– press the button
>
to make the boiler operate at maximum
power "Hi" and check that the mains gas pressure value on the
pressure gauge is correct. Take a reading of the combustion
data and measure the combustion efficiency.
– press the button
<
to make the boiler operate at minimum
power "Lo". The message
“Lo”
will appear on the display
together with the flashing symbols
l
and
n
Содержание Brava Slim HE 20 R i
Страница 4: ...4 ...
Страница 42: ...42 12 EXPLODED VIEWS Brava Slim HE 20 R i Brava Slim HE 40 R i ...
Страница 43: ...43 Brava Slim HE 20 R e Brava Slim HE 40 R e ...
Страница 44: ...44 Brava Slim HE 20 R i Brava Slim HE 20 R e Brava Slim HE 40 R i Brava Slim HE 40 R e ...
Страница 45: ...45 Brava Slim HE 20 R i Brava Slim HE 20 R e Brava Slim HE 40 R i Brava Slim HE 40 R e ...
Страница 46: ...46 Brava Slim HE 20 R i Brava Slim HE 20 R e Brava Slim HE 40 R i Brava Slim HE 40 R e ...
Страница 55: ...55 ...