The boiler is supplied with an electric cable.
Should this require replacement, it must be
purchased exclusively from SIME.
The electric power supply to the boiler must
be 230V - 50Hz single-phase through a
fused main switch, with at least 3 mm spa-
cing between contacts. Respect the L and N
polarities and the earth connection.
NOTE: SIME declines all responsibility for
injury or damage to persons, animals or
things, resulting from the failure to provi-
de for proper earthing of the appliance.
2.11.1
Electrical panel
(fig. 14)
Before performing any kind of operation,
disconnect the unit from the power supply
using the bipolar switch of the plant.
Placing the boiler selector in position “OFF”
does not disconnect the electric board
from the power supply.
Remove the three
screws (9) that secure the control panel
and pull the panel forward to tilt down. To
access switchboard components, remove
the four screws that secure the cover (6).
2.11.2
Room stat connection
(fig. 14)
Electrically connect the time thermostat to
thermals 15-16 of the
“CN1”
connector
af t er having r emoved t he br idge.
The
recommended time thermostat for best
room and comfor t regulation must be
class II in accordance with regulation EN
60760.1 (clean electrical contact).
2.11.3 Wiring diagram
77
IT
ES
PT
GB
8
1
2 5
4
6
7
9
Fig. 14
Fig. 13
1) Terminals below a practicable bal-
cony must be located in such a way
that the total path of the smoke
from its outlet point from the termi-
nal to its outlet point from the exter-
nal perimeter of the balcony, inclu-
ding the height of possible railings,
is not less than 2000 mm.
2) W h e n s i t i n g t e r m i n a l s , w h e r e
materials that may be subject to
the action of the combustion pro-
ducts are present in the vicinity,
e.g., eaves, gutt er s and down-
spouts painted or made of plastic
material, projecting timberwork,
etc., distances of not less than
1500 mm must be adopted, unless
adequate shielding is provided to
guard these materials.
WARNING: After removing the
three screws (9) pull the panel
forward to tilt down.
TABLE 2
Siting of terminal
Appliances from 7 to 35 kW
(distances in mm)
A - below openable window
600
B - below ventilation opening
600
C - below eaves
300
D - below balcony (1)
300
E - from adjacent window
400
F - from adjacent ventilation opening
600
G - from horizontal or vertical soil or drain pipes (2)
300
H - from corner of building
300
I - from recess in building
300
L - from ground level or other treadable surface
2500
M - between two terminals set vertically
1500
N - between two terminals set horizontally
1000
O - from a surface facing without
openings or terminals
2000
P - as above but with openings and terminals
3000
KEY
1
Thermohydrometer
2
Time programmer seat
4
Main PCB
5
Earth faston
6
Control panel protection
7
Cover
8
Connector CN1
9
Fixing screw
IMPORTANT
Before performing any kind of operation, disconnect the unit
from the power supply using the bipolar switch of the plant.
Placing the boiler selector in position “OFF” does not disconnect
the electric board from the power supply.