Troubleshooting Guide 

 

Complaint 

Cause 

Solution 

Compressor 
will not run 

1.

 

No voltage at wall receptacle  

2.

 

Service cord pulled out of wall 
receptacle  

3.

 

Low voltage causing 
compressor to cycle on 
overload  

4.

 

Power switch is in “Off” 
position  

5.

 

Inoperative control 

6.

 

Compressor stuck  

7.

 

Compressor windings open  

8.

 

Compressor overload stuck 
open  

9.

 

Relay lead loose 

10.

 

Relay loose or inoperative 

11.

 

Power cord disconnected from 
dispenser 

12.

 

Faulty cabinet wiring  

1.

 

Check circuit breaker or fuse 

2.

 

Replace 

3.

 

Contact power company and 
confirm that voltage 
fluctuation does not exceed 
10% plus or minus from the 
nominal rating 

4.

 

Turn switch on 

5.

 

Call service technician 

6.

 

Call service technician 

7.

 

Call service technician 

8.

 

Call service technician 

9.

 

Call service technician 

10.

 

Call service technician 

11.

 

Call service technician 

12.

 

Call service technician 

Compressor 
runs but no 
refrigeration 

1.

 

System out of refrigerant   

2.

 

Compressor not pumping  

3.

 

Restricted filter drier   

4.

 

Restricted capillary tube   

5.

 

Moisture in system   

1.

 

Call service technician 

2.

 

Call service technician 

3.

 

Call service technician 

4.

 

Call service technician 

5.

 

Call service technician 

Compressor 
short cycles 

1.

 

Erratic control thermostat  

2.

 

Faulty relay  

3.

 

Low voltage   

4.

 

Compressor draws excessive 
wattage  

1.

 

Call service technician 

2.

 

Call service technician 

3.

 

Contact power company and 
confirm that voltage 
fluctuation does not exceed 
10% plus or minus from the 
nominal rating 

4.

 

Call service technician 

Compressor 
runs too much 
or constantly 

1.

 

Temperature to low 

2.

 

Erratic control 

3.

 

Abnormally high room 
temperature 

4.

 

Door or lid gaskets not sealing 

5.

 

System undercharged due to 
leaks  

6.

 

System undercharged from 
factory 

7.

 

System overcharged  

8.

 

System not clean  

9.

 

Restricted filter drier 

10.

 

Restricted capillary tube  

1.

 

Adjust temperature control 

2.

 

Call service technician 

3.

 

Reduce room temperature or 
relocate dispenser 

4.

 

Adjust or call service 
technician 

5.

 

Call service technician 

6.

 

Call service technician 

7.

 

Call service technician 

8.

 

Call service technician 

9.

 

Call service technician 

10.

 

Call service technician 

Содержание SKBD110P

Страница 1: ...1 Technical Manual and ReplacementPartsList BeverageDispenser Specifications Subject to Change Without Notice 1600 Xenium Lane North Minneapolis MN 55441 3787 Phone 763 923 2441 MODEL SKBD110P ...

Страница 2: ...lowing factors must be observed When placing the unit on a counter the counter must be able to support a minimum of 100 pounds When placed on a counter the unit must be on the feet supplied If the feet are removed the unit will not operate properly and the warranty will be void There must be at least two inches of clear space above on the sides and behind the unit and open in front Correct serving...

Страница 3: ...by removing the Valve Insert first then removing or installing the Cream Container The end of the tube may need to be cleaned daily with a clean cloth to prevent buildup which could affect the dispensing of product After loading the creamer press and hold the REFILL button for 3 seconds until the indicator flashes 00 Defrost The Silver King cream dispenser is a manual defrost unit The unit should ...

Страница 4: ...3 ...

Страница 5: ...4 ...

Страница 6: ...5 REPLACEMENT PARTS LIST MODEL SKBD110P WHEN ORDERING REPLACEMENT PARTS PLEASE PROVIDE MODEL AND SERIAL NUMBERS ...

Страница 7: ...e valve insert by pulling it straight up Cleaning Once removed the valve can be cleaned with a brush and warm soapy water or in a dishwasher The valve area in the dispenser should also be cleaned with a brush and warm soapy water Insert New Bag into Container Insert a new beverage bag into the container as shown Lock the tube into place at the bottom of the container ...

Страница 8: ...centered to avoid kinking which could result in reduced product flow or leaking Install Valve Insert Push and hold valve slide while inserting the valve insert from above Cut Tube Cut the tube one inch below the valve Press REFILL Button Press and hold the REFILL button for 3 seconds display 00 to alert the dispenser that a new beverage bag has been installed ...

Страница 9: ...ing 3 Restricted filter drier 4 Restricted capillary tube 5 Moisture in system 1 Call service technician 2 Call service technician 3 Call service technician 4 Call service technician 5 Call service technician Compressor short cycles 1 Erratic control thermostat 2 Faulty relay 3 Low voltage 4 Compressor draws excessive wattage 1 Call service technician 2 Call service technician 3 Contact power comp...

Страница 10: ...an Beverage leaking or not flowing 1 Tube kinked 2 Valve stuck 1 Remove valve and pull tube straight through valve area 2 Clean valve and valve area or call for service Ordering Parts Service Contact Silver King Refrigeration at 800 328 3329 for technical assistance Model__________________ Serial No ___________________ Date Installed__________________ 33547 REVISION C ...