50
007-6399-002
4: Rack Information
See “System-level Specifications” in Appendix A for a more complete listing of SGI ICE XA
system operating specifications and environmental requirements.
SGI ICE XA E-Cell Rack Assemblies
SGI ICE XA system configurations require the use of enhanced “closed-loop” cooling and the
compute rack assemblies are generally referred to as an “E-Cell”. A complete E-Cell assembly
consists of two compute racks and an air-to-water heat exchanger (the cooling tower) for cooling
the compute racks, see Figure 4-3 for an example. The racks are connected together to create a
sealed unit to support closed-loop cooling. The E-Cell rack system does not exhaust heated air into
the surrounding environment; this means an E-Cell does not add to the heat load of the computer
room. Multiple E-Cells can be interconnected and configured to create very large systems. Many
E-Cell configurations also require the use of a separate cooling distribution rack unit (CDU rack)
(not shown in Figure 4-4 on page 54).
Figure 4-3
E-Cell Rack Configuration Example
The smallest E-Cell assembly consists of two compute racks with a cooling rack in between.
E-Cell systems use liquid-cooled compute/graphics/InfiniBand boards and also require the use of
Содержание ICE XA
Страница 1: ...SGI ICE XA System Hardware User Guide Document Number 007 6399 002 ...
Страница 4: ......
Страница 12: ......
Страница 25: ...Powering the System On and Off 007 6399 002 7 Figure 1 4 Three Phase PDU Example ...
Страница 32: ......
Страница 65: ...SGI ICE XA Series D Rack 42U 007 6399 002 47 Figure 4 1 D Rack Front Lock Example ...
Страница 66: ...48 007 6399 002 4 Rack Information Figure 4 2 Optional Water Chilled Door Panels on Rear of ICE XA D Rack ...
Страница 72: ...54 007 6399 002 4 Rack Information Figure 4 4 E Cell Rack Assembly Example CDU on Left ...
Страница 82: ......