SAFETY AND INSTALLATION MANUAL FOR 

PHOTOVOLTAIC MODULES 

5a/5b), and achieve the 5.4  kPa load 

rating. 

 

 

In horizontal configuration, fixing the 

modules by blocking them at the 4 

mounting  holes will guarantee the 

characteristics regarding the static loads as 

certified. 

 

When clamping the modules in horizontal 

configuration on a support structure, the 

following rules have to be applied in order 

to maintain the resistance against  static 

loads as certified: 

 

o

 

If the bars or rails are in vertical 

direction, they have to be placed 

nearby the corner holes or in any case 

a spacing of 800-941 mm between the 

bars has to be maintained  in order to 

achieve the 5.4 kPa load rating  (Fig. 

5a/5b). 

 

o

 

If the bars or rails are in horizontal 

direction, they have to be placed with 

a spacing of 500-750 mm  in order to 

achieve the UL specified 2.4 kPa load 

rating (Fig. 5a/5b). 

 

 

The modules can also be fixed by placing 

them  with their  frame on a structure that 

is supporting the two sides of the  frame 

over  their whole length. In this case, the 

position of the mounting clamps must be in 

accordance with the above mentioned 

spacings (800-941  mm and 500-750 mm 

respectively) – refer also to Fig. 5a/5b. 

 

 

Fig. 3a: Mechanical drawing of an SLA module showing 

the mounting holes, the drainage holes,  and the 

ground connection holes 

 

Fig. 3b: Mechanical drawing of an SLG module showing 

the mounting holes, the drainage holes, and the 

ground connection holes 

Содержание SLAXXXM3A/SLAXXXM

Страница 1: ...Document Number MAN SFO 02 Revision Date April 2 2013 SILFAB ONTARIO INC SAFETY and INSTALLATION MANUAL Photovoltaic Modules SLAXXXM3A SLAXXXM SLAXXXP3A SLAXXXP SLGXXXM3G SLGXXXM SLGXXXP3G SLGXXXP...

Страница 2: ...tly follow the instructions Failure to follow these instructions may result in death injury or property damage and possible void of warranty Warning All instructions should be read and understood befo...

Страница 3: ...pshots which enable you to monitor the operation of the modules and determine possible although rare anomalies The electrical output parameters for SLA SLG modules of technical importance during the o...

Страница 4: ...r expense resulting from improper installation handling or use 3 Underwriters Laboratories UL Listing Information This product meets or exceeds the requirements set forth by UL 1703 for PV Modules Thi...

Страница 5: ...ing periods of high winds Do not use oil based lubricants on any part of the junction box as this can cause long term damage to the plastics Ensure that wire cable connections are routed in accordance...

Страница 6: ...LES intensity greater than 400 W m2 Opaque material can be supplied by Silfab upon request o Making the connections during hours of low intensity of solar irradiance such as early morning or late afte...

Страница 7: ...isphere Mounting Methods Mounting using mounting holes Each module must be securely fastened at a minimum of 4 points Use the 4 mounting holes slots see Fig 3a 3b on the PV module frame to bolt the mo...

Страница 8: ...ny case a spacing of 800 941 mm between the bars has to be maintained in order to achieve the 5 4 kPa load rating Fig 5a 5b o If the bars or rails are in horizontal direction they have to be placed wi...

Страница 9: ...used for attaching the modules to support structure Fig 4b modules attached to supporting structure rail item 01 using a clamp item 02 fixed with a bolt item 03 and nut item 04 view between two module...

Страница 10: ...risk of electric shock and prevent damage to the module During the wiring and installation of the modules use caution Do not trample on or scratch the modules Do not drop sharp or heavy objects on ei...

Страница 11: ...nce losses Bypass diodes are not over current protection devices In the event of a known or suspected diode failure installers or maintenance providers should contact Silfab Never attempt to open the...

Страница 12: ...UL listed grounding lug o Schletter Rapid Clamps are acceptable when using the proper size to match Silfab s 38 mm frame o WEEB clips compatible with the chosen racking mounting clip are also acceptab...

Страница 13: ...erform direct measurements on individual modules using conventional instrumentation the following action should be taken To measure the open circuit voltage Voc Note even in the presence of an insolat...

Страница 14: ...ons and for corrosion as well as the mechanical connection is recommended Under normal conditions sufficient rainfall cleaning of the module is not required In extreme climatic conditions the electric...

Страница 15: ...nage the Packaging Each package has been designed to allow the shipment and storage of modules in order to maintain their integrity unchanged over time provided that the information and indications su...

Страница 16: ...materials used to construct them Although the modules are stiffened by an aluminium frame any direct impact to the glass or on the corners of the modules should be avoided Avoid flexing the laminates...

Страница 17: ...a visible position and containing some pertinent information such as serial number of each module part number of each module and pallet number All Numbers are readable with a standard bar code reader...

Страница 18: ...00M SLG305M SLG310M SLG315M SLG320M SLG325M SLG330M SLG335M Pmax 300 305 310 315 320 325 340 345 Vmp 36 5 36 7 36 9 37 1 37 3 37 5 37 8 38 1 Imp 8 26 8 35 8 44 8 53 8 62 8 7 8 75 8 8 Voc 44 9 45 1 45...

Страница 19: ...maintenance To download a copy of this installation manual scan the QR Code on the back of a Silfab module or go to www silfab ca media center download area html Silfab Ontario 240 Courtneypark Drive...

Отзывы: