Before You Begin Installing
151142
2-7
*
Use a separate worksheet for each 5895XL.
**
If you are using door holders, you do not need to consider door holder current for alarm/battery standby, because
power is removed during that time. However, during normal operation, door holders draw current and must be
included in the 6.0 A total current that can be drawn from the panel.
***
Use next size battery with capacity greater than required.
2.7
Wiring Specifications
2.7.1
Length Limitations
This section contains information on calculating SBUS wire distances and the types
of wiring configurations (Class A and B).
2.7.2
Calculating Wiring distance for SBUS modules
The following instructions will guide you in determining the type of wire and the
maximum wiring distance that can be used with SBUS accessory modules.
To calculate the wire gauge that must be used to connect SBUS modules to the
panel, it is necessary to calculate the total worst case current draw for all modules on
a single 4-conductor bus. The total worst case current draw is calculated by adding
the individual worst case currents for each module. The individual worst case values
are shown in the table below.
Note: Total worst case current draw on a single SBUS cannot exceed 1 amp. If a large number of
accessory modules are required, and the worst case current draw will exceed the 1 amp limit,
then the current draw must be distributed using 5895XL Power Expanders. Each 5895XL Power
Expander provides an additional SBUS, with an additional 1 amp of SBUS current. Wiring
distance calculations are done separately for each 5895XL, and separately for the panel itself.
After calculating the total worst case current draw, Table 2-5 specifies the maximum
distance the modules can be located from the panel on a single wire run. The table
insures 6.0 volts of line drop maximum. In general, the wire length is limited by
resistance, but for heavier wire gauges, capacitance is the limiting factor.
Model Number
Worst Case Current Draw
5860 Fire Annunciator
.100 amps
5824 Parallel/Serial Interface
.040 amps
5880 LED IO Expander
.250 amps
5865 LED Fire Annunciator
.200 amps
5895XL Intelligent Power Supply
.010 amps
5496 Intelligent Power Module
.010 amps