Service Bypass Switch
7.2.3
Isolating one UPS for service/maintenance
In a redundant system one UPS can be isolated for service/maintenance without
affecting the other parallel UPS(s).
1.
Check that the remaining UPS(s) will be able to carry the load when one UPS is
isolated.
2.
Switch off the system to be isolated for maintenance by pushing both the green
“ON” and the red “OFF” key simultaneously.
3.
Disconnect battery, mains, and output by opening battery MCCB/fuse and
turning input switch (Q001) and output switch (Q002) to position “0”.
When Q002 is in position “0” the UPS can be operated and tested as a single
system without affecting the other parallel UPS(s).
Switching back the UPS to normal parallel/redundant operation
1.
Turn the input switch (Q001) and the output switch (Q002) to position “1”.
2.
Charge capacitors, connect battery and start up the UPS as described in chapter
5.0.
The UPS will automatically switch to normal operation and start load sharing
with the other parallelled UPS(s).
Warning!
The system will discharge built-
in capacitors. However, before
working on the system check
with a multimeter that there is
no dangerous voltage on the
terminals .