4.5 Electrical installation
Destruction of parts of equipment and loss of regulation control
`
All lines for connecting the electronic display must be shielded.
`
Never wire or disconnect electrical connections while they are live.
`
Perform wiring work in the de-energized state only.
`
Use strands with suitable ferrules.
`
Check all lines and plug connections before switching on the device.
`
Switch on operating voltage together with downstream electronic unit
(e. g., control unit).
Basically, all connections are protected against external interference.
Choose a place of operation that excludes inductive or capacitive inter-
ference influences on the magnetic sensor or its connection lines. When
mounting the system keep a maximum possible distance from lines loaded
with interference. If necessary, provide additional installations including
screening shields or metallized housings.
No modification of the sensor connection, e. g. by cable extension, is per-
mitted.
Connection of power supply
Signal
Color
+UB
red
GND
black
Fig. 8: Design EG
1
Sensor L or F
2
Cable for power supply