Operation
i
ndu
Q
®
- Series VMM
- 38 -
© SIKA
•
Ba_VMM_us
•
09/2018
One of the following settings can be chosen
(
"Selection window / make a selection",
p. 23):
Setting
Function
not used no alarm function
>22 mA
rise of current in case of alarm
<3,8 mA reduction of current in case of
alarm
7.1.9
Simulation
The functional class SIMULATION includes
the functions for simulating output signals or
output states.
If simulation mode is activated, all output
signals will be generated depending on the
selected items. This function enables testing
of peripherals connected to the device with-
out water flow.
Simulation on / off:
The function
Simulation on/off
is in-
tended for activating or deactivating simula-
tion mode
For selecting the desired function within the
class please use the keys
and
.
After selecting the function
simulation
on/off,
press the ENTER key to display the
current setting:
Example:
For changing the parameter please refer to
the description in Section "Selection window
/ make a selection".
Notice
Simulation will be deactivated auto-
matically after restarting the device or
without a keystroke for at least 10
minutes.
Simulation preset value Q / direct:
This function is intended for defining whether
a volume flow rate is preset or the outputs
will be set directly.
For selecting the desired function within the
class please use the keys
and
.
Press ENTER key to display the current se-
lection for the type of simulation:
Example:
Simulation
[off]
Preset of
[direct]