THIS GUIDE IS FOR EXPERIENCED INSTALLERS ONLY
and summarises key information provided in the full manual (Document No. DAU0000081). Page numbers, e.g.
refer to the main manual.
Networked systems are not included in this guide.
SigTEL (1-16 Line) EVCS - Quick Start Installation Guide
FUSE
8 x
outstation lines
EVC302F
THS1-E/MK4
ECU-8
EVC302S
3A fused spur
ECU-8S
(optional)
8 lines of 2-core (1.5mm
2
)
and
earth/CPC cable, enhanced
fire-rated, up to 1km in length.
Master/Slave interconnection via
supplied looms and short length of
steel conduit (25mm OD, max. length
60mm). Mount slave directly adjacent
to the master.
Fixed wiring, 2-core and earth/cpc
cable (0.75mm
2
to 2.5mm
2
) fed from
switched spur, fused at 3 amps.
additional
outstations
1 of 2
Approved Document No. DAU0302001 Rev 1
SigTEL
Emergency Voice
Communication System
SigTEL EVCS Wiring Overview
Install the EVCS
Location
Site all equipment indoors in well-lit areas, free from obstruction. If background noise exceeds 40 dB, use
an acoustic hood. Site control unit(s) in the control room or lobby, 1.4 metre above final floor level (FFL).
Fit Type A (fire telephone) outstations in fire fighting lobbies and fire access points, 1.3 to 1.4 metres
above FFL. Fit type B (disabled refuge) outstations in disabled refuges, 0.9 to 1.0 metre above FFL.
Mounting
Remove base PCBs before first fix installation
to protect them and expose the base mounting holes.
Wall mount the control units, either surface or semi-flush. Fix the base securely onto a wall using No. 8
round-head, or countersunk screws. If an optional ECU-8S is fitted make the interconnections to the
ECU-8 using supplied looms and short length of steel conduit (25 mm OD, max. length 60 mm).
After mounting, remove any dust/swarf and re-install base PCBs. Ensure all connecting looms are refitted
correctly; ECU-8 internal connections are B to B, C to C. ECU-8 to ECU-8S (optional) is A to A, D to B.
Pg11
Pg11
Wiring and Cable Entry
See Fig 1 above for cable types. Install all wiring in accordance with the current edition of the IEE Wiring Regs (BS 7671), or relevant national
standards. Use enhanced fire-rated cables between outstations and control equipment.
Test Outstation Lines
Test all lines for faults before terminating outstation lines to the ECU-8/ECU-8S. In addition, test outstation lines using a FITT telephone line
tester (see component list above).
CAUTION: DO NOT use an Insulation Resistance Tester (Megger) with any devices connected as they will be destroyed.
Fit Outstations
See Fig 1 above for cable type. Maximum recommended cable distance is 1 km, beyond which audio quality may degrade. For wiring and
connection details refer to Type A outstation instructions (Doc. No. DAU0000001) and Type B outstation instructions (Doc. No. DAU0302000).
Connect Outstation Lines to the Control Equipment
Do not connect outstation lines to the ECU-8, or optional ECU-8S, until they have been tested, fault-free and suitable cable glands fitted.
Connect outstation lines directly to the Exchange PCB (see Fig 2 left). Connect screens to the earth terminal in the back of the enclosure.
8 x Lines from Type A or Type B Outstations
L1 L2
+ - + -
L3 L4
+ - + -
L5 L6
+ - + -
L7 L8
+ - + -
I/P A I/P B I/P C
N/O C N/C 0V +24 OP3 OP2 OP1
+ - + - + -
All screens connect
to Earth terminal
ECU-8 or ECU-8S
Exchange PCB
A
C D
B
Fig 2
Pg12
Pg7
Pg18
Pg19
Part No.
Description
ECU-8
8-line Master EVC Control Unit c/w line cards, handset and LCD
ECU-8S
8-line Slave EVC Expansion Unit (expands ECU-8 to 16 lines)
EVC302F
Disabled Refuge (Type B) Outstation, handsfree, duplex, flush mounted
EVC302S
Disabled Refuge (Type B) Outstation, handsfree, duplex, surface mounted
THS1-E/MK4
Fire Telephone (Type A) Outstation c/w red steel case, handset & key
THS1-ET/MK4
Fire Telephone (Type A) Outstation c/w red steel case, handset & T-Bar
BF359/1
Weatherproof enclosure for EVC302F
BF359/2
Anti-tamper enclosure for ECU-8 or ECU-8S
FITT
EVC Telephone Line Tester
BC286/2
24 V, 7 Ah battery used with ECU-8
AFP385
Grey flush bezel for ECU-8 or ECU-8S
T-BEZ
Red flush bezel for THS1-E/MK4 and THS1-ET/MK4
SigTEL EVCS Components
Pg19
Fig 1