THIS GUIDE IS FOR EXPERIENCED INSTALLERS ONLY

and summarises key information provided in the full manual (Document No. DAU0000081). Page numbers, e.g.

refer to the main manual.

Networked systems are not included in this guide.

SigTEL (1-16 Line) EVCS - Quick Start Installation Guide

FUSE

8 x

outstation lines

EVC302F

THS1-E/MK4

ECU-8

EVC302S

3A fused spur

ECU-8S

(optional)

8 lines of 2-core (1.5mm

2

)

and

earth/CPC cable, enhanced 
fire-rated, up to 1km in length.

Master/Slave interconnection via 
supplied looms and short length of 
steel conduit (25mm OD, max. length 
60mm). Mount slave directly adjacent 
to the master.

Fixed wiring, 2-core and earth/cpc 
cable (0.75mm

2

to 2.5mm

2

) fed from 

switched spur, fused at 3 amps.

additional

outstations

1 of 2

Approved Document No. DAU0302001 Rev 1

SigTEL

Emergency Voice
Communication System

SigTEL EVCS Wiring Overview

Install the EVCS

Location

Site all equipment indoors in well-lit areas, free from obstruction. If background noise exceeds 40 dB, use
an acoustic hood. Site control unit(s) in the control room or lobby, 1.4 metre above final floor level (FFL).
Fit Type A (fire telephone) outstations in fire fighting lobbies and fire access points, 1.3 to 1.4 metres
above FFL. Fit type B (disabled refuge) outstations in disabled refuges, 0.9 to 1.0 metre above FFL.

Mounting

Remove base PCBs before first fix installation

to protect them and expose the base mounting holes.

Wall mount the control units, either surface or semi-flush. Fix the base securely onto a wall using No. 8
round-head, or countersunk screws. If an optional ECU-8S is fitted make the interconnections to the
ECU-8 using supplied looms and short length of steel conduit (25 mm OD, max. length 60 mm).

After mounting, remove any dust/swarf and re-install base PCBs. Ensure all connecting looms are refitted
correctly; ECU-8 internal connections are B to B, C to C. ECU-8 to ECU-8S (optional) is A to A, D to B.

Pg11

Pg11

Wiring and Cable Entry

See Fig 1 above for cable types. Install all wiring in accordance with the current edition of the IEE Wiring Regs (BS 7671), or relevant national
standards. Use enhanced fire-rated cables between outstations and control equipment.

Test Outstation Lines

Test all lines for faults before terminating outstation lines to the ECU-8/ECU-8S. In addition, test outstation lines using a FITT telephone line
tester (see component list above).

CAUTION: DO NOT use an Insulation Resistance Tester (Megger) with any devices connected as they will be destroyed.

Fit Outstations

See Fig 1 above for cable type. Maximum recommended cable distance is 1 km, beyond which audio quality may degrade. For wiring and
connection details refer to Type A outstation instructions (Doc. No. DAU0000001) and Type B outstation instructions (Doc. No. DAU0302000).

Connect Outstation Lines to the Control Equipment

Do not connect outstation lines to the ECU-8, or optional ECU-8S, until they have been tested, fault-free and suitable cable glands fitted.
Connect outstation lines directly to the Exchange PCB (see Fig 2 left). Connect screens to the earth terminal in the back of the enclosure.

8 x Lines from Type A or Type B Outstations

 

L1    L2

 

+ - + -

L3    L4

 

+ - + -

L5    L6

 

+ - + -

L7    L8

 

+ - + -

I/P A   I/P B   I/P C 

N/O C N/C 0V +24 OP3 OP2 OP1 

+ - + - + -

All screens connect

to Earth terminal

ECU-8 or ECU-8S

Exchange PCB

A

C D

B

Fig 2

Pg12

Pg7

Pg18

Pg19

Part No.

Description

ECU-8

8-line Master EVC Control Unit c/w line cards, handset and LCD

ECU-8S

8-line Slave EVC Expansion Unit (expands ECU-8 to 16 lines)

EVC302F

Disabled Refuge (Type B) Outstation, handsfree, duplex, flush mounted

EVC302S

Disabled Refuge (Type B) Outstation, handsfree, duplex, surface mounted

THS1-E/MK4

Fire Telephone (Type A) Outstation c/w red steel case, handset & key

THS1-ET/MK4

Fire Telephone (Type A) Outstation c/w red steel case, handset & T-Bar

BF359/1

Weatherproof enclosure for EVC302F

BF359/2

Anti-tamper enclosure for ECU-8 or ECU-8S

FITT

EVC Telephone Line Tester

BC286/2

24 V, 7 Ah battery used with ECU-8

AFP385

Grey flush bezel for ECU-8 or ECU-8S

T-BEZ

Red flush bezel for THS1-E/MK4 and THS1-ET/MK4

SigTEL EVCS Components

Pg19