background image

-2-

Series MHE-RE

Moonlite LED™
High Output Emergency Light

02.17.02

Fig. 2. SURFACE MOUNT WITH END BRACKETS

Fig. 3. SURFACE MOUNT TO J-BOX

WIRING SHOWN FOR EM OPERATION ONLY

WIRING SHOWN FOR EM & NORMAL ON OPERATION 

END BRACKET

(2) SUPPLIED

PIGTAIL & LAMP 

CONNECTOR (SUPPLIED)

24 VDC

IN/ OUT

24 VDC

IN/ OUT

BL

BL

Y
B
R

BL

Y
B
R

YB R

CEILING

POLARIZED LAMP

CONNECTOR

LAMP 

HOUSING

MOUNT 

SCREWS

(2) REQ'D

LAMP

ASSBY

COVER

SCREW

ANCHOR

BRACKET

SCREW

(4) SUPPLIED

LAMP

ASSBY

COVER

15 1/2”

CEILING

J- BOX
4" Octagon

24 VDC

IN/ OUT

24 VDC

IN/ OUT

B Y R BL

SURFACE MOUNT WITH END BRACKETS

1. See Fig 2. Install (2) screw anchors at 15 ½” centers. 
2. Insert flat blade screwdriver under notch at end of cover, twist gently to release cover plate. Unscrew (4) #8 lamp assembly screws, lift lamp 
    assembly from Housing and disconnect lamp plug. 
3. Attach end brackets with (4) #8 screws and nuts as shown, mount housing assembly to ceiling and route 24VDC IN/OUT wiring from CBS 
    branch circuit into housing. 
4. Proceed as for STANDARD SURFACE MOUNT steps 4 - 5

SURFACE MOUNT TO J-BOX

1. See Fig 3. Install standard 4” Octagon J-box centrally above installation point as shown and secure to ceiling using appropriate screw 
anchors.  2. 
    Route 24VDC IN/OUT wiring from CBS branch circuit into j-box.  

KEY
B= BLACK:COMMON: 12/24 VDC NEG -
Y= YELLOW: EXITS/CVRE: 12/24 VDC POS +
R= RED: EMERGENCY: 24VDC POS +
BL= BLUE: NORMAL ON LIGHTING (NOL): 24 VDC POS +

Отзывы: