INSTALLATION INSTRUCTIONS AND OWNER'S MANUAL
1. Disconnect AC power before servicing.
2. Refer to wiring diagram for proper connections.
3. All servicing should be performed by qualified personnel.
4. Consult your local building code for approved wiring and installation.
5. Do not use this equipment for other than intended use.
6. Do not let power cords touch hot surfaces.
7. Mount and secure the fixture at a location and height to avoid ready access
and tampering by unauthorized persons.
8. The use of accessory equipment is not recommended by the manufacturer
and may cause an unsafe condition.
9. Suitable for wet locations. See product label for temperature limitations.
IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
5”
8 1/2”
7 3/8”
BACK BOX
OUTPUT LOW VOLTAGE
TO FIXTURE
2 CONDUCTORS*
(SEE TABLE 1 FOR WIRE SIZE)
(DAC OPTION)
EMERGENCY INPUT
120/ 277 VAC
PRIMARY INPUT
UTILITY 120/ 277 VAC
N
N
BLACK/ ORANGE
BLACK/ ORANGE
WHITE
BLUE
BROWN
WHITE
RED
BLACK
L
L
INPUT
120/ 277
VAC
(4) #6-32 X 1/2
SCREWS
0UTPUT 5 VDC
3 3/4”
3 1/2”
Remote Power Supply (RPS)
1. Use framing or brackets to install Masonry Box housing as shown, in a location convenient for access
to battery and power supply. Align top edge flange flush with finished panel surface. See Table 1 to
estimate wire size required based on maximum wiring length for low voltage output wiring from RPS to
the fixture.
2. INPUT WIRING: Connect 120/277 AC input wiring to building supply with wire nuts, and connect
GROUND to Housing with Screw mount.
3. OUTPUT LOW VOLTAGE WIRING: Connect output wiring to fixture. See Table 1 for minimum wire
sizebased on distance to fixture.
4. Turn AC power ON after fixture is connected and check lamp operation.
5. (DAC OPTION): Turn Primary Supply OFF and activate Emergency Supply to check operation.
STANDARD MASONRY BOX
3 3/4" X 3 1/2" X 7 3/8"
TYPICAL STOCK MODELS:
CROUSE HINDS #TP693
RACO # 698
SEE TABLE 1 FOR
MAX WIRING LENGTH
INPUT
120/277 VAC
OUTPUT 5 VDC
RPS
DAC
(OPTION)
LED DRIVER
120/277 VAC
TABLE 1
MAXIMUM WIRING LENGTH
FROM RPS TO EXIT FIXTURE
MAX (4) EXIT SIGNS
WIRING
SIZE AWG
#20
300
400
#18
LENGTH (FT)
CRR,CRS,RPR
Remote Power Supply
For CRS AC Mullion Mount Signs
10.15.00
Series CRSAC-MM