Wiring Diagrams & Instructions

Crystal

Edge- lit LED

Sign System

Series CAE

Accessible Exit

REV 01.12.02

-4-

POWER MODULE

R

E

D

B

R

O

W
N

OUTPUT 2.4-5 VDC

E M E R G E N C Y  S I G N S

A C  F I X T U R E S

BATTERY

FIXTURE HOUSING

BLK

R

E

D

R E D

V

I

O

L

E

T

V I O L E T

B

R

O

W
N

B R O W N

Y

E

L

L

O

W

G

R

E

E

N

P

I

N

K

O

R

A

N

G

E

B

L

A

C

K

OUTPUT 2.4-5 VDC

RED

LAMP CIRCUIT BOARD

LAMP CIRCUIT BOARD

FIXTURE

GROUND

NEUTRAL

120-277 VAC 

W H I T E

B L A C K

B L A C K

W H I T E

G R E E N

GROUND

NEUTRAL

120-277 VAC 

B L A C K

B L A C K

B L A C K

W H I T E

G R E E N

POLARIZED

CONNECTOR

TEST PANEL

DIAGNOSTICS INDICATOR

CHARGE LIGHT

TEST SWITCH

8-PIN POLARIZED

2-PIN POLARIZED

CONNECTOR

CONNECTOR

Wiring

1. This equipment to be connected to an unswitched circuit
    only.

2. For exits with Master- Remote or Self- Diagnostics, refer 
    to supplementary data sheet for wiring diagrams and
    additional instructions.

3. CAUTION: Damage to battery will occur if battery connec-
    tor is connected to charger board for prolonged period of
    time without continuous AC power provided.

Inspection and Maintenance

Important Note: Emergency lighting systems should be
    tested as often as local codes require, or at least monthly, to
    acertain that all components are operational. Allow battery to
    charge 8 hours before initial testing, and 24 hours to fully
    charge battery.

1. Normal Operation: When unit is functioning properly, with AC 
    power supplied, the "Ready" light and exit lamp will be on.

2. To Test: Press manual test switch. Status light will turn off
    and exit lamp will remain on in DC mode.

Note: Turn off AC power and disconnect battery before
    servicing unit.

Battery Replacement

Remove fixture from J-Box. Locate battery wiring and
disconnect 2- pin polarized battery plug. Pry battery
out of cavity to release hook and loop fastener. Replace
battery, reconnect battery plug and replace fixture.

Power Module Replacement

Remove fixture from J-Box. Remove two #8-32 screws
to J-Box and remove Power Module Assembly from J-Box.
Disconnect wire nuts or push nut connectors to AC line
inputs. To replace with new Power Module, reverse this
sequence.

4" SQ x 2 1/8" 

DEEP

 J-BOX

WITH 1 " EXTENSION RING

220   VFW Avenue, Grasonville, MD 21638

TEL: (410) 827-8300     Fax:(410)827- 8866

[email protected]    www.signtexinc.com

Signtex  Inc

LIGHTING

REV 07.07.2