PROBLEM

POSSIBLE CAUSE 

CORRECTIVE ACTION

White powder residue 

forming within burner box 

or on adjacent walls or 

furniture

1. When heated, the vapors   

    from furniture polish, wax, 

    carpet cleaners, etc., turn into 

    white powder residue

1. Turn heater off when using 

    furniture polish, wax, carpet 

    cleaner or similar

Heater produces 

unwanted odors

1. Heater is burning vapors from 

    paint, hairspray, glues, etc. 

    See IMPORTANT statement, 

    page 21

2. Gas leak (see warning statement on   

    page 24)

3. Low fuel supply

1. Ventilate room. Stop using 

    odor causing products while 

    heater is running

2. Locate and correct all leaks 

    (see “Checking Gas Connections” on 

    page 17)

3. Refill supply tank (propane/LP 

    models)

Heater shuts off in use 

(ODS operates)

1. Not enough fresh air is 

    Available

2. Low line pressure

3. ODS/pilot is partially clogged

1. Open window and/or door for 

    Ventilation

2. Contact local gas supplier 

3. Clean ODS/pilot (see “Care and    

    Maintenance” on page 23)

Gas odor exists even 

when control knob is in 

OFF position

1. Gas leak (see warning statement on   

    page 24)

2. Control valve is defective

1. Locate and correct all leaks 

    (see “Checking Gas Connections” on 

    page 17)

2. Contact customer service

Moisture/condensation 

noticed on windows

1. Not enough 

    combustion/ventilation air 

1. Refer to “Air for Combustion 

    and Ventilation” on page 7

Slight smoke or odor 

during initial operation

1. Residues from manufacturing 

    process

1. Problem will stop after a few 

    hours of operation

Heater produces a 

whistling noise when 

burner is lit

1. Turning control knob to HIGH 

    (5) position when burner is 

    Cold

2. Air in gas line

3. Air passageways on heater 

    are blocked

4. Dirty or partially clogged 

    burner orifice

1. Turn control knob to LOW (1) 

    position and let warm up for a 

    minute

2. Operate burner until air is 

    removed from line. Have gas 

    line checked by local 

    propane/LP gas company.

3. Observe minimum installation 

    Clearances (see “Installation” on   

    page 10)

4. Clean burner (see “Care and    

    Maintenance” on page 23)

Fan is not spinning 

1. There is no power to fan

2. Fan motor is bad

1. Verify fan is plugged in

2. Replace fan

Fan is making a loud 

noise

1. Fan housing or blades are 

    Dirty

2. Fan rotation is blocked 

3. Defective fan

1. Clean fan (see “Care and    

    Maintenance” on page 23)

2. Verify wiring is not in fan path

3. Replace fan

TROUBLESHOOTING

Содержание C18000CLF

Страница 1: ...oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air For Combustion and Ventilation section on page 7 of this manual INSTA...

Страница 2: ...4 500 24 500 18 000 18 000 Fuel Type Natural Gas Natural Gas Propane Propane Natural Gas Natural Gas Propane Propane Ignition Electronic Push Button Electronic Push Button Electronic Push Button Elect...

Страница 3: ...ter will remain hot for a time after shutoff Allow surfaces to cool before touching WARNING Make sure any panel safety screen or guard removed for servicing an appliance is replaced prior to operating...

Страница 4: ...in a bedroom These units are not approved for bathroom use 3 This heater needs fresh air ventilation to run properly This heater has an Oxygen Depletion Sensing ODS safety shutoff system The ODS shut...

Страница 5: ...ner on and off to maintain a desired room temperature For further information see page 19 State of Massachusetts The installation must be made by a licensed plumber or gas fitter in the Commonwealth o...

Страница 6: ...Water vapor is a by product of gas combustion An unvented room heater produces approximately one 1 ounce 30 mL of water for every 1 000 BTU 3 Kw of gas input per hour An unvented room heater is inten...

Страница 7: ...LLY TIGHT CONSTRUCTION The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation However in buildings of unusually tight construction you must provide add...

Страница 8: ...as heater ___________ BTU hr Gas heater logs ___________ BTU hr Other gas appliances ___________ BTU hr Total ___________ BTU hr Do not include direct vent gas appliances Direct vent draws combustion...

Страница 9: ...se items directly to the outdoors or spaces open to the outdoors These spaces include attics and crawl spaces Follow the National Fuel Gas Code NFPA 54 ANS Z223 1 Air for Combustion and Ventilation fo...

Страница 10: ...oining wall than required CAUTION This heater creates warm air currents These currents move heat to wall surfaces next to the heater Installing the heater next to vinyl or cloth wall coverings or oper...

Страница 11: ...cle DO NOT dispose of batteries in fire Improper disposal may cause batteries to leak or explode PREINSTALLED FAN OPTIONAL WARNING This appliance is equipped with a three prong grounding plug for your...

Страница 12: ...its wire connected to the receptacle mounting screw ACCESSING FAN 1 Turn off gas supply to appliance 2 Remove appliance from mounted position if applicable 3 Remove screws connecting rear heater cove...

Страница 13: ...13 INSTALLATION GREEN BLACK WHITE POWER CORD FAN WIRING ASSEMBLY DIAGRAM MOTOR ELECTRICAL SCHEMATIC...

Страница 14: ...r will be placed for leg installation to prevent scratching of the table and or the heater Set back of heater on table with the bottom of heater extending outside the table edge Fasten Support Legs to...

Страница 15: ...INES MAYBE IN WALL Before cutting drilling or hammering verify their location If needed contact your electrician plumber or service person WALL MOUNTING Fig 11 Insert Rawl Plugs into wall after drilli...

Страница 16: ...line pressure is higher the unit will not work and heater regulator damage could occur CAUTION Never connect the heater directly to a LP supply This heater requires an external regulator not supplied...

Страница 17: ...5 kPa Leak Testing Heater Gas Internal Connections 1 Open equipment shutoff valve see Fig 13 2 Make sure control knob of the heater is in the OFF position 3 Open gas supply tank valve LP systems 4 Che...

Страница 18: ...y to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If y...

Страница 19: ...hts The pilot is visible centered below the burner behind the front grill see Fig 16 Do not attempt to light the pilot by hand 7 Keep control knob depressed for 30 seconds after pilot lights Release c...

Страница 20: ...cool which shuts the heater off If pilot flame pattern is incorrect turn heater off see To Turn Off Gas to Appliance on page 20 see Troubleshooting pages 24 through 26 Ignitor Control Knob OFF P I L O...

Страница 21: ...me Fig 23 Incorrect Abnormal Flame Pattern with tall flames with Control Knob Set to High Flame Infrared Flame Glass 1 2 Height Glass 1 2 Height Fig 20 Correct Normal Flame Pattern with short flames w...

Страница 22: ...f the barrier becomes damaged the barrier shall be replaced with the manufacturer s barrier for this appliance OPERATION Fig 26 Viewing Glass Warning Label WARNING Never operate the appliance without...

Страница 23: ...free of dust and debris NOTE The fan motor is pre lubricated for extended bearing life and requires no further lubrication WARNING Turn off heater and let cool before servicing CAUTION You must keep t...

Страница 24: ...lectrode is positioned wrong 2 Ignitor electrode is broken 3 Ignitor electrode is not connected to ignitor cable 4 Ignitor cable is pinched or wet 5 Damaged ignitor cable 6 Bad ignitor or ignition mod...

Страница 25: ...burner s 1 Manifold pressure is too low 2 Burner orifice is clogged 1 Contact your gas supplier 2 Clean burner orifice see Care and Maintenance on page 23 or contact customer service Burner backfiring...

Страница 26: ...ontrol valve is defective 1 Locate and correct all leaks see Checking Gas Connections on page 17 2 Contact customer service Moisture condensation noticed on windows 1 Not enough combustion ventilation...

Страница 27: ...Burner Assembly Infrared 1 1 1 1 3 1 ODS LP Propane Pilot 1 1 1 1 3 2 ODS NG Natural Gas Pilot 1 1 1 1 4 Ignition Wire 1 1 1 1 1 1 1 1 5 1 Thermostatic Gas Valve 1 1 5 2 Thermostatic Gas Valve 1 1 5 3...

Страница 28: ...sponsible for any incidental indirect or consequential damages except as provided by law 6 All other warranties expressed or implied with respect to the product its components and accessories or any o...

Отзывы: