background image

9 of 16

SigNET PRO Range Instructions

Approved Document No. DAU0000105 Rev 2

PHASED ARRAY HEARING LOOP SYSTEMS (MODEL DEPENDENT) 

 
Increasingly to ensure uniformity of the magnetic field, especially in larger installations where 
large amounts of metal are present and to limit overspill, phased array loop systems are being 
specified. A phased array system works by producing two AFILS signals 90° out of phase with 
each other. These signals are connected to two identical hearing loops laid in a special 
overlapping pattern. The resultant magnetic field is evenly spread within the covered area but 
falls off quickly outside the loop. 

Note:

 The smallest practical room width for a phased array loop is 5m. 

 
The SigNET PRO Range amplifiers offer: 
 
1. A true ‘all-in-one’ professional phased-array AFILS solution. 
2. An onboard overspill reduction phase shifter and metal compensation control. 
3. An internal PSU. 
 
See diagram below for a typical dual loop design. Note the sizes shown are examples only as 
each system must be uniquely designed. For further advice on phase shifted loop design please 
contact SigNET technical department.

2m

3.2m

1.6m offset

Green Loop
(Array 1)

Red Loop

(Array 2)

2m

3.2m

Baseline

PRO Dual

Loop Amplier

Note 1:

 If high metal content is present, the amplifier’s area of coverage will be reduced, and 

further reduced, as the 

Metal Comp

 control is increased. 

 

Note 2:

 If the 

Peak

 indicator lights strongly, reduce the 

Line

 

Input

 level and then adjust the 

Metal Comp

  control  buttons. You may have to adjust both these controls several times to 

achieve the most favourable operation. 

 

Note 3:

 Metal compensation tests must be carried out to comply with the requirements of 

BS EN 60118-4.

Loop Drive 1 & Loop Drive 2 Drive (Model Dependent) 

These menu displays are used to adjust the strength of the magnetic field generated by 
induction loops 1 & 2 by increasing the output current being driven into the loops. To comply 
with BS EN 60118-4, Output (field strength) should be set up using a FPROK1 test kit. 

 
Select either 

Loop 1 Drive

 or 

Loop 2 Drive

 display and press the 

Up

 

4

 and 

Down

 

 control 

buttons to adjust the current out for each loop. 
 
The 

Peak

 indicator, when illuminated (shown below), indicates that the amplifier is delivering 

its maximum design current. Intermittent Peak indications are acceptable, but if the Peak 
indicator is mostly on, consider installing a more powerful Pro Range amplifier.

VU

Loop 1 Drive

Metal Comp

Loop 2 Drive

Down

Up

min

max

Phantom Phase

Limit

Fault 1 2

HOT!

Peak

VU

Loop 2 Drive

Loop 1 Drive

Phase Shift

Down

Up

min

max

Phantom Phase

Limit

Fault 1 2

HOT!

Peak

Brightness 

This function will increase or decrease the brightness of the menu display. It is recommended 
that brightness level is not set to its maximum setting for a long period of time.

8 of 16

SigNET PRO Range Instructions

Approved Document No. DAU0000105 Rev 2

Phase Shift (Model Dependent) 

This menu display is used to apply optional phase shift between the two hearing loops. 
By default, the amplifier will have phase shift turned off. 
 
Select the 

Phase Shift

 display and press the 

On

 

4

 and 

Off

 

 control buttons to toggle phase 

shift on and off between loop 1 and loop 2, as shown below.

VU

Phase Shift

Loop 2 Drive

Brightness

Off

On

min

max

Phantom Phase

Limit Peak

Fault 1 2

HOT!

VU

Phase Shift

Loop 2 Drive

Brightness

Off

On

min

max

Phantom Phase

Limit Peak

Fault 1 2

HOT!

Содержание Pro Series

Страница 1: ...tal receiver Up to 24 bit 96kHz sampling OUTPUTS Loop 1 Loop 2 model dependent Type True current mode Loop output voltage 14V Single Loop drive current 1 ohm 4 75A PRO5 SD PRO5 SW 7 5A PRO7 SD PRO7 SW 11A PRO11 SD PRO11 SW Dual Loop drive current 1 ohm 2 x 3 25A PRO5 DD PRO5 DW 2 x 5A PRO7 DD PRO7 DW 2 x 7 5A PRO11 DD PRO11 DW Line Out 775mV output Fault Relay Single pole double throw SPDT NC Comm...

Страница 2: ...rom being walked on or pinched particularly at plugs convenience receptacles and the point where they exit from the apparatus 10 Only use attachments accessories specified by the manufacturer 11 Unplug this apparatus during lightning storms or when unused for long periods of time 12 Refer all servicing to qualified service personnel Servicing is required when the apparatus has been damaged in any ...

Страница 3: ...rt numbers listed above 1 x Accessory pack containing instructions this document two ferrite beads for the loop cables pluggable connectors for the outreach line out relay line in microphone terminals hearing loop fitted sticker 230V 50Hz Power max 200W Fuse T 5A H 250V No user controls or user serviceable parts inside LOOP 2 OPTICAL OPTIONAL RELAY NO COM NC LINE OUT 0V A A OUTREACH 0V A A V 1 2 3...

Страница 4: ...2 for alternative wall mount model connections 1 IMPORTANT DO NOT power up the system before completing Step 3 below The amplifier MUST NOT be operated without a loop connected to it Install Loop 1 Cable and Loop 2 Cable model dependent See Phased array hearing loop systems page 9 for example dual loop layouts BEFORE connecting the loops to the amplifier use a multimeter to check the loops are not...

Страница 5: ... metal base securely onto a vertical wall 2m mounting height Assess the condition and construction of the wall and use suitable screw fixings for the in service weight of the product The mounting holes are suitable for use with ø4 5mm countersunk screws Any dust or swarf created during the mounting process must be kept out of the enclosure and due care must be taken not to damage any wiring or com...

Страница 6: ... 2 CONNECTIONS NOT SHOWN Ensure the ferrite bead supplied is fitted at the terminal block A LOOP 1 A Loop Connectors Wall Mount Model Only Microphone Connector Wall Mount Model Only Line In Connector Wall Mount Model Only Menu Displays Use the Left and4 Right buttons to scroll through the amplifier s menu displays listed right 1 Line Input 2 Microphone 3 Phantom 4 Outreach 5 Digital model dependen...

Страница 7: ... the outreach plate audio input extension system This system allows the connection of multiple microphones or line level inputs via a range of specially designed wall ceiling or desk mountable single gang plates Up to ten outreach plates any mix can be daisychained to the amplifier s outreach connector with cable lengths up to 100m total network length easily achievable using standard two pair aud...

Страница 8: ...ation Note 3 Metal compensation tests must be carried out to comply with the requirements of BS EN 60118 4 Loop Drive 1 Loop Drive 2 Drive Model Dependent These menu displays are used to adjust the strength of the magnetic field generated by induction loops 1 2 by increasing the output current being driven into the loops To comply with BS EN 60118 4 Output field strength should be set up using a F...

Отзывы: