Signet 8450-3 Pressure Transmitter 

Delta Pressure (Differential Mode)

If two sensors are connected to the transmitter, the DELTA 
(Sensor 1 - Sensor 2) can be assigned to output. To enable 
differential mode, the selected output's "Source" selection must 
be set to "DP". 

For pressure and temperature transmitters ensure Sensor 1 is 
equal to ID 1:
Sensor 1 - Sensor 2
Difference = 60

Example: 4-20 mA
Loop1 Source: DP
Loop1 Range: 0-120
Loop1: = 12.00 mA

Example: Output
Output1 Source: DP
Output1 Mode: Low
Output1 Setpoint: 70
Output1 = ON

ENTER

Sensor 1 (80)

Sensor 2 (20)

Pres1:  4.5 

psi

Pres2:  2.3 

psi

ENTER

Signet Pressure

Transmitter

3.3  Open Collector Output

The Open Collector output can be used as a switch that responds 
when the process variable moves above or below a setpoint.

 Low:

Output triggers when process variable is less than the setpoint. 
The output will relax when the process variable moves above the 
setpoint plus the hysteresis value.

• 

High:

Output triggers when process variable is greater than the 
setpoint. The output will relax when the process variable moves 
below the setpoint plus the hysteresis value.

Hysteresis

Time

Low Setpoint

Process

Output energized

Output de-energized

Hysteresis

Time

High Setpoint

Process

VIEW menu

•  During normal operation, the ProcessPro displays the VIEW menu.
•  When using the CALIBRATE or OPTIONS menus, the ProcessPro will return to the VIEW menu if no 

activity occurs for 10 minutes.

•  To select the item you want displayed, press the UP or DOWN arrow keys. The items will scroll in a 

continuous loop.

•  Changing the display selection does not interrupt system operations.
•  No keycode is necessary to change display selection.
•  Output settings cannot be edited from the VIEW menu.

View Menu

Display

Description

Press1: 7.89 psi

Press2: 4.56 psi

Monitor Pressure 1 and Pressure 2 simultaneously.
This is the permanent view display.

Delta Pressure:

3.33 psi

Monitor the delta pressure (Channel 1 rate - channel 2 rate = Delta Pressure)
This is a permanent display.

The displays below are temporary. After 10 minutes the display returns to the permanent display.

Loop 1 Output:

12.00 mA

Monitor the 4 to 20 mA output for Loop 1 and 2.

Loop 2 Output:

 7.65 mA

Last CAL:

02-10-09

Monitor date for scheduled maintenance or date of last calibration.
(See description in Calibrate Menu.)

Содержание 8450-3

Страница 1: ...al panel cutout an adhesive template is provided as an installation guide Recommended clearance on all sides between instruments is 1 inch 2 Place gasket on instrument and install in panel 3 Slide mounting bracket over back of instrument until quick clips snap into latches on side of instrument 4 To remove secure instrument temporarily with tape from front or grip from rear of instrument DO NOT RE...

Страница 2: ...es two sensors the total length of cable connected to the transmitter is limited to 400 ft The 3 conductors from a dual sensor system can be tied together and then a single set of wires continued on to the transmitter For best performance ground the sensor SHIELD wire to a local earth ground at a point near the sensor Experiment with connecting the sensor shield wire to different local ground poin...

Страница 3: ...r supply Internal PLC Connection Connection to a PLC Recorder separate supply PLC or Recorder Loop 2 Loop 2 System Power Loop 1 System Power Loop 1 AUX Power AUX Power Transmitter Terminals Loop 2 Loop 2 System Power Loop 1 System Power Loop 1 AUX Power AUX Power Transmitter Terminals Loop 2 Loop 2 System Power Loop 1 System Power Loop 1 AUX Power AUX Power Power Supply 12 24 VDC PLC Terminals Cha...

Страница 4: ... variable moves below the setpoint plus the hysteresis value Hysteresis Time Low Setpoint Process Output energized Output de energized Hysteresis Time High Setpoint Process VIEW menu During normal operation the ProcessPro displays the VIEW menu When using the CALIBRATE or OPTIONS menus the ProcessPro will return to the VIEW menu if no activity occurs for 10 minutes To select the item you want disp...

Страница 5: ...diting Procedure Step 1 Press and hold ENTER key 2 seconds to select the CALIBRATE menu 5 seconds to select the OPTIONS menu Step 2 The Key Code is UP UP UP DOWN keys in sequence After entering the Key Code the display will show the first item in the selected menu Step 3 Scroll menu with UP or DOWN arrow keys Step 4 Press RIGHT ARROW key to select menu item to be edited The first display element w...

Страница 6: ... 20 mA output Pressure 1 Pressure 2 or Delta Pressure Pressure1 Pressure2 Loop 1 Range psi 0 0 100 0 Check the 2450 Sensor instructions for the range capability of your sensor Be sure to modify this setting if you change the Pressure Units Output 1 Source Pressure1 Select the INPUT SIGNAL represented by this Open Collector Output Pressure 1 Pressure 2 or the Delta Pressure Pressure1 Pressure2 Outp...

Страница 7: ...le display and output response Select LOW HIGH or OFF Output1 Active Low Active HIGH This setting is used to turn a device pump valve ON at the setpoint Active LOW This setting is used to turn a device OFF at the setpoint Output2 Active Low Loop1 Adjust 4 00 mA Adjust the minimum and maximum current output Use this setting to match the system output to any external device The display value represe...

Страница 8: ...641 Heavy duty wall mount bracket 3 5000 598 198 840 225 Surface Mount Bracket 3 9000 392 159 000 368 Liquid tight connector kit for rear cover includes 3 connectors 3 9000 392 1 159 000 839 Liquid tight connector kit NPT 1 piece 3 9000 392 2 159 000 841 Liquid tight connector kit PG13 5 1 piece Display Condition Possible Causes Suggested Solutions Check Sensor Sensor not wired properly Sensor con...

Отзывы: