background image

Troubleshooting

Georg Fischer Signet LLC, 3401 Aerojet Avenue, El Monte, CA  91731-2882  U.S.A.  •  Tel. (626) 571-2770  •  Fax (626) 573-2057
For Worldwide Sales and Service, visit our website:  www.gfsignet.com  •  Or call (in the U.S.):  (800) 854-4090
For the most up-to-date information, please refer to our website at www.gfsignet.com

3-8350.090-1   Rev. H  01/12  English 

 © Georg Fischer Signet LLC 2012

Ordering Information

Mfr. Part No. 

Code 

 

Description

3-8350-1 

159 000 192 

Temperature transmitter Field mount

3-8350-1P 

159 000 193 

Temperature transmitter Panel mount

3-8350-2 

159 000 194 

Temperature transmitter Field mount with relays

3-8350-2P 

159 000 195 

Temperature transmitter Panel mount with relays

3-8350-3 

159 000 196 

Temperature transmitter Field mount with dual input/output

3-8350-3P 

159 000 197 

Temperature transmitter Panel mount with dual input/output

Accessories

Mfr. Part No. 

Code 

 

Description

3-8050   

159 000 184 

Universal mounting kit

3-8052   

159 000 188 

3/4” Integral mounting kit

3-8052-1 

159 000 755 

3/4" NPT mount junction box

3-8050.395 

159 000 186 

Splashproof rear cover

3-8050.396 

159 000 617 

RC Filter kit (for relay use)

3-0000.596 

159 000 641 

Heavy duty wall mount bracket

3-5000.598 

198 840 225 

Surface Mount Bracket

3-9000.392 

159 000 368 

Liquid tight connector kit for rear cover (includes 3 connectors)

3-9000.392-1 

159 000 839 

Liquid tight connector kit, NPT (1 piece)

3-9000.392-2 

159 000 841 

Liquid tight connector kit, PG13.5 (1 piece)

3-9900.396 

159 001 701 

Angle Adjustment Adapter Kit

Display Condition

Possible Causes

Suggested Solutions

Check Sensor?

•  Sensor not wired properly.
•  Sensor connected to 8350 while power 

is on.

• Defective sensor.

•  Correct sensor wiring.
•  Recycle power with all sensors connected.
•  Replace defective sensor.

Too much error

CHECK SENSOR

The value entered in Set Temperature 

fi

 eld is greater than 20 °C (36 °F) 

deviation from sensor input. (The 8350 
allows a maximum of 20 °C offset.).

• Con

fi

 rm calibration values.

•  Replace defective sensor.

Reset to Factory

Calibration

Value in SET TEMPERATURE 

fi

 eld

is -999.

Entering "-999" in this 

fi

 eld will remove all user 

calibration input and restore the factory values.

Open Collector is always

 

activated

•  Hysteresis value too large.
• Defective transmitter.

•  Change the hysteresis value
• Replace transmitter

Value must be

400 or less

Value entered in Output PlsRate 

fi

 eld is 

greater than 400.

Select a maximum pulse rate of 400 pulses per 
minute or less.

Содержание 8350-1

Страница 1: ...evels Electrical Power 12 to 24 VDC 10 regulated 21 mA max current Current output 4 to 20 mA isolated fully adjustable and reversible Max loop impedance 50 Ω max 12V 325 Ω max 18V 600 Ω max 24V Update rate 200 ms Output accuracy 0 03 mA Open collector output Optically isolated 50 mA max sink 30 VDC maximum pull up voltage Programmable for High Low with adjustable hysteresis Pulse operation maximum...

Страница 2: ...d remove Outp ut Outp ut Syst em Pwr Loop Syst em Pwr Loop 2 1 4 3 Sens r Gnd SHI ELD Sens r IN RED Sens r V BLA CK 7 6 5 quick clips gasket panel terminals mounting bracket latch Panel Mount Installation Detail 3 Electrical Connections Caution Failure to fully open terminal jaws before removing wire may permanently damage instrument Wiring Procedure 1 Remove 0 5 0 625 in 13 16 mm of insulation fr...

Страница 3: ... 12 24 VDC PLC or Recorder PLC Terminals Power Supply 12 24 VDC Power Supply 12 24 VDC Stand alone application no current loop used Connection to a PLC with built in power supply Connection to a PLC Recorder separate supply Example Two transmitters connected to PLC Recorder with separate power supply Transmitter Terminals Transmitter 1 Terminals Transmitter 2 Terminals Transmitter Terminals 7 6 5 ...

Страница 4: ...resis Time High Setpoint Process 10 5 O p e n C o l l e c t o r O u t p u t R a t e 0 t o 1 0 0 P u l s e s m i n endpoint Pulse rate 0 pulses 100 pulses Starting point View Menu 3 3 Open Collector Output The Open Collector output can be used as a switch that responds when the process value moves above or below a setpoint or it can be used to generate a pulsing signal with a rate proportional to t...

Страница 5: ... VIEW menu ProcessPro Editing Procedure Step 1 Press and hold ENTER 2 seconds to select the CALIBRATE menu 5 seconds to select the OPTIONS menu Step 2 The Key Code is keys in sequence After entering the Key Code the display will show the first item in the selected menu Step 3 Scroll menu with or arrow keys Step 4 Press to select menu item to be edited The first display element will begin flashing ...

Страница 6: ... Off if not used Output Setpnt 25 0 C In Low or High Mode the Open Collector output will be activated when the temperature reaches this value Be sure to modify this setting if you change the Temperature Units Output Hys C The Open Collector output will be de energized at Setpoint Hysteresis depending on High or Low Setpoint selection Output Range 25 0 45 0 If the output is in PULSE mode set the st...

Страница 7: ...Low Active HIGH This setting is used to turn a device pump valve ON at the setpoint Active LOW This setting is used to turn a device OFF at the setpoint Loop Adjust 4 00 mA Adjust the minimum and maximum current output Use this setting to match the system output to any external device The display value represents the precise current output Adjustment limits 3 80 mA 4 00 mA 5 00 mA 19 00 mA 20 00 m...

Страница 8: ...er kit for relay use 3 0000 596 159 000 641 Heavy duty wall mount bracket 3 5000 598 198 840 225 Surface Mount Bracket 3 9000 392 159 000 368 Liquid tight connector kit for rear cover includes 3 connectors 3 9000 392 1 159 000 839 Liquid tight connector kit NPT 1 piece 3 9000 392 2 159 000 841 Liquid tight connector kit PG13 5 1 piece 3 9900 396 159 001 701 Angle Adjustment Adapter Kit Display Con...

Отзывы: