‡ SIGNET
2540 High Performance Flow Sensor
Page 1 of 8
1/2 in. NPT conduit port
• Use 2-conductor shielded cable for cable extensions up to 300m (1000 ft.)
• Maintain cable shield through splice.
Black (5 to 24 VDC)
Silver (DC return)
+GF+ SIGNET Instruments
Other Brands
Input
Gnd.
10 k
Ω
+
5 to 24
VDC
-
black
silver
red
• pull-up resistor required (10 k
Ω
recommended).
• Use 2-conductor shielded cable for cable extensions up to 300m (1000 ft.)
• Maintain cable shield through splice.
Other
instrument
Blk, sensor
power
Red, freq.
input
Shld,
Gnd
instrument
Red (signal out)
3. Sensor Wiring
+GF+ SIGNET 2540 High Performance Flow Sensor
(English)
SAFETY INSTRUCTIONS
1. Do not remove from pressurized lines.
2. Do not exceed maximum temperature/pressure specifications.
3. Do not install/service without following installation instructions (see sensor manual).
4. Wear safety goggles and faceshield during installation/service.
5. Do not alter product construction.
6. Failure to follow safety instructions could result in severe personal injury!
10x I.D.
5x I.D.
Inlet
Outlet
Flange
15x I.D.
5x I.D.
Reducer
20x I.D.
5x I.D.
90° Elbow
50x I.D.
5x I.D.
40x I.D.
5x I.D.
25x I.D.
5x I.D.
2 x90° Elbow
2 x 90° Elbow
3 dimensions
Valve/Gate
2. Sensor Mounting Position
Vertical mounting is recommended for best overall performance. Mount
at a maximum of 45
°
when air bubbles are present.
DO NOT
mount
on the bottom of the pipe when sediments are present.
+45
°
0
°
Process Pipe
-
45
°
1. Location of Fitting
Recommended sensor upstream/downstream
mounting requirements.
•
Pipe fittings
MUST
be installed by a certified welder only. +GF+ SIGNET will not assume liability of any kind for improper
fitting installations.
•
The 2540 Hot-Tap system's overall specifications and limitations depend on the lowest maximum rating of the components
associated with the system. In other words, the Hot-Tap system is only as strong as its weakest link. For example, a ball
valve, a component of the system, is rated at a maximum 100 psi @ 175
°
F, limiting the entire system's maximum pressure/
temperature rating to 100 psi @ 175
°
F. All higher maximum specifications
MUST
yield to the component with the lowest
maximum specification.
Maximum Operating Pressure/Temperature:
• 17 bar (250 psi) @ 82
°
C (180
°
F) with standard Viton® sensor fitting O-rings.
• 17 bar (250 psi) @ 100
°
C ( 212
°
F) with optional EPR sensor fitting O-rings.
3-2540.090-1
G-7/02 English