Signature Hardware VALLONA Скачать руководство пользователя страница 2

VALLONA RANGE HOOD INSTALLATION

LOCATION REQUIREMENTS

GENERAL REQUIREMENTS

- Range hood must be ventilated to the outdoors, except for 

non-vented (recirculating) installations.
- Do not use 4” (10.2cm) laundry-type wall caps.

- Length of the range hood and the number of elbows should 
be kept to a minumum to provide maximum performance. 

FOR THE MOST EFFICIENT AND QUIET 
OPERATION

- Use no more than three (3) 90-degree elbows.
- Ensure that there is a minimum of 24” (61cm) of straight 

duct between the elbows if more than one is used.
- Do not join two elbows together.
- Use clamps and tape to seal all joints in the vent system.
- The vent system must have a damper. If the roof or wall cap 
has a damper, do not use the damper supplied with the range 
hood.
- Use caulking to seal exterior walls or roof openings around 
the cap.
- The size of the vents should be uniform.

COLD WEATHER INSTALLATIONS

An additional back draft damper should be installed to 

minimize backward cold air flow. A thermal break should be 

installed to minimize conduction of outside temperatures as 
part of the vent system. The damper should be on the cold air 
side of the thermal break. The break should be as close as 
possible to where the vent system enters the heated portion 
of the home. 

MAKEUP AIR

Local building codes may require the use of makeup air 
systems, when using ventilation systems greater than 

specified CFM of air movement. The specified CFM varies 

from state to state. Consult your HVAC professional for 

specific local requirements. 

VENTING METHOD

To vent through a wall, a 90-degree elbow is needed. If 
exhaust ducting with a diameter less than 5.91” (150mm) or if 
flat ducting is used, the noise level of the range hood could 
increase and extraction will be less efficient. 

IMPORTANT:

 Observe all governing codes and ordinances. It 

is the installer’s responsibility to comply with installation 
clearances specified on the model/serial rating plate. Range 
hood’s location should be away from strong draft areas, such 

as windows, doors, and strong heating vents. Cabinet 
opening dimensions that are shown must be used. Given 
dimensions provide minimum clearance.

ELECTRICAL REQUIREMENTS

120 volt, 60 Hz, AC only, 15-amp

If the home contains aluminum wiring, follow the procedure 
below:
- Connect a section of solid copper wire to the pigtail leads.
- Connect the aluminum wiring to the copper wire using 
special connectors and\or tools designed and UL listed for 

joining copper to aluminum. Follow the manufacturer’s 

recommended procedure for the electrical connector. 

Aluminum/copper connection must conform to local codes 

and industry accepted wiring practice.

Wire sizes and connections must conform to the rating of 

the appliance as specified on the model/serial rating plate. 
The model/serial plate is located behind the filter on the rear 

wall of the range hood.

Wire sizes must conform to the requirements of the Nation-

al Electrical Code, ANSI/NFPA 70 (latest edition), or CSA 
Standards C22. 1-94, Canadian Electrical Code, Part 1 and 
C22.2 No. 0-M91 (latest edition) and all local codes and 

ordinances.

2

Vallona Range Hood Installation Instructions

VENTILATION REQUIREMENTS

Содержание VALLONA

Страница 1: ... vapors CAUTION To reduce the risk of fire and to properly exhaust air be sure to duct air outside DO NOT vent exhaust air into attics crawl spaces garages or within walls or ceilings 1 Vallona Range Hood Installation Instructions TO REDUCE THE RISK OF A STOVETOP GREASE FIRE PLEASE READ THE FOLLOWING Never leave surface units unattended at high settings Boil over can cause smoke and grease to spill...

Страница 2: ...ional for specific local requirements VENTING METHOD To vent through a wall a 90 degree elbow is needed If exhaust ducting with a diameter less than 5 91 150mm or if flat ducting is used the noise level of the range hood could increase and extraction will be less efficient IMPORTANT Observe all governing codes and ordinances It is the installer s responsibility to comply with installation clearances s...

Страница 3: ... a carbon filter at the motor Fumes and vapors are recycled through the top grille DO NOT block the chimney holes CALCULATING VENT SYSTEM LENGTH To calculate the length of the system you need add the equivalent feet meters for all vent pieces used in the system 3 Vallona Range Hood Installation Instructions VENTILATION REQUIREMENTS cont d Wood Screws TOOLS AND MATERIALS Pencil Level Utility Knife D...

Страница 4: ...2 to the outside vent using 6 diameter ducting If the existing outside vent contains a 5 opening a reduction fitting can be used Thread the upper chimney E to the inside of the lower chimney F Insert them vertically on of the range hood body fig 7 Affix the bracket Z fig 8 to the wall via the drill holes C Slide the upper chimney E towards the top locking it in with the appropriate screws in the drill ...

Страница 5: ...E HOOD INSTALLATION 5 Vallona Range Hood Installation Instructions Fig 4 Ⓩ Ⓔ Ⓕ Ⓛ optional recirculating mode only Ⓨ Ⓜ Fig 2 A C B 8 21 32 10 5 64 10 29 32 7 7 8 11 13 16 23 5 8_27 9 16_35 7 16 Fig 3 1 3 2 3 4 Fig 1 ...

Страница 6: ...VALLONA RANGE HOOD INSTALLATION 6 Vallona Range Hood Installation Instructions Fig 5 Fig 8 25 19 32 21 21 32 Fig 10 Fig 6 Fig 7 Fig 9 Ⓕ Ⓔ Ⓔ Ⓩ ...

Страница 7: ...Make sure filters are completely dry before putting back into the range hood Reinstall the filter by making sure the spring release handles are toward the front Insert filter into upper track Push the spring release handle Push up on filter and release handle to latch into place CARE AND MAINTENENCE OPERATING INSTRUCTIONS Use the high suction speed in cases of heavy stove top cooking It is recommended...

Отзывы: