10 Recommended Shielding for VARAN
The VARAN real-time Ethernet bus system exhibits a very robust quality in harsh industrial
environments. Using IEEE 802.3 standard Ethernet physics, the potentials between an
Ethernet line and sending/receiving components are separated. In the event of an error, the
VARAN Manager resends messages to a bus participant immediately. The shielding
described below is mainly recommended.
For applications in which the bus is operated outside the control cabinet, the correct shielding
is required. This is especially important, if due to physical requirements, the bus cables must
be placed next to sources of strong electromagnetic noise. It is recommended to avoid placing
VARAN bus lines parallel to power cables whenever possible.
SIGMATEK recommends the use of CAT5e industrial Ethernet bus cables.
An S-FTP cable should be used for the shielding.
An S-FTP bus is a symmetric, multi-wire cable with unshielded pairs. For the entire shielding,
a combination of foil and braiding is used. A non-laminated variant is recommended.
The VARAN cable must be secured at a maximum distance of 20 cm from
the connector to protect against vibration!
Содержание VARAN SV 142 S-DIAS
Страница 13: ...S DIAS SPLITTER VARAN SV 142 02 08 2019 Page 11 5 Mechanical Dimensions...
Страница 15: ...S DIAS SPLITTER VARAN SV 142 02 08 2019 Page 13 7 Connector Layout 7 1 Front View...
Страница 18: ...SV 142 S DIAS SPLITTER VARAN Page 16 02 08 2019 7 2 Top View...
Страница 35: ...S DIAS SPLITTER VARAN SV 142 02 08 2019 Page 33 Documentation Changes Change date Affected page s Chapter Note...
Страница 36: ...SV 142 S DIAS SPLITTER VARAN Page 34 02 08 2019...