![SIGMATEK SAI 041 Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/sigmatek/sai-041/sai-041_operating-manual_1268144016.webp)
SAI 041
SAFETY ANALOG INPUT CURRENT MODULE
Page 14
18.05.2022
3.4
Miscellaneous
Article number
20-897-041
Hardware version
2.x
Approvals
CE, TÜV EG type tested
3.5
Environmental Conditions
Storage temperature
-40 ... +85°C
Environmental temperature
0 ... +60 °C
1)
Humidity
0-95 %, non-condensing
Installation altitude above sea
level
0-2000 m without derating
>2000 m up to a maximum of 5000 m with derating of the maximum
environmental temperature by 0.5 °C per 100 m
Operating conditions
pollution degree 2
EMC resistance
EN 61000-6-7 (noise immunity requirements for devices
with functional safety)
EN 61000-6-2 (industrial area)
EMC noise generation
EN 61000-6-4 (industrial area)
Vibration resistance
EN 60068-2-6
3.5 mm from 5-8.4 Hz
1 g from 8.4-150 Hz
Shock resistance
EN 60068-2-27
15 g (147.15 m/s
2
)
Protection type
EN 60529
IP20
1)
Starting at an ambient temperature of +55 °C, the safety parameter from chapter 2.3.1 must be used.