HZS 772 

TOUCH OPERATING PANEL 

 

 

Page 26  

15.07.2020 

15 

STOP BRKPT

 

The  CPU  was  stopped  by  a  breakpoint 
in the program. 

Info 

16 

CPU STOP

 

The  CPU  was  stopped  by  the  program-
ming software. 

Info 

17 

INT ERROR

 

The  CPU  has  triggered  a  false  interrupt 
and  stopped  the  user  program  or  has 
encountered  an  unknown  instruction 
while running the program. 

Cause: 

A non-existent operating system 
was used.  

Stack error (uneven number of 
PUSH and POP instructions).  

The user program was interrupt-
ed through a software error.  

 

Solution: 

Correct program error 

18 

SINGLE STEP

 

The  CPU  is  in  single  step  mode  and  is 
waiting for further instructions. 

Info 

19 

READY

 

A  module  or  project  was  sent  to  CPU 
and it is now ready to run the program. 

Info 

20 

LOAD

 

The program is stopped and the CPU  is 
currently  receiving  a  new  module  or 
project. 

Info 

21 

UNZUL.

 

MODULE

 

The  CPU  has  received  a  module  that 
does not belong to the project. 

Solution: 

Recompile and download the 
entire project 

22 

MEMORY FULL

 

The  operating  system  memory  /heap)  is 
too small. No memory could be reserved 
while  calling  an  internal  or  interface 
function from the application. 

Cause: 

Memory is only allocated bun not 
released.  

 

Solution  

Clear memory 

23 

NOT LINKED

 

When  starting  the  CPU,  a  missing 
module  or  a  module  that  does  not 
belong to the project was detected. 

Solution: 

Recompile and download the 
entire project 

24 

DIV BY 0

 

A division error has occurred. 

Possible Causes: 

Division by 0.  

The result of a division does not 
fit in the result register.  

 

Solution: 

Correct program error 

25 

DIAS ERROR

 

While  accessing  a  DIAS  module,  an 
error has occurred. 

Hardware problem 

26 

WAIT

 

The CPU is busy. 

Info 

Содержание 05-895-772

Страница 1: ...HZS 772 Touch Operating Panel Operating Manual Date of creation 26 03 2014 Version date 15 07 2020 Article number 06 895 772 E...

Страница 2: ...t of this work may be reproduced edited using an electronic system duplicated or dis tributed in any form print photocopy microfilm or in any other process without the express permission We reserve th...

Страница 3: ...implified using this terminal A resistive touch screen serves as the input medium for process data and parameters The output is shown on a 7 WVGA TFT color display With the LSE mask editor graphics ca...

Страница 4: ...ditions 5 1 5 7 WVGA Display incl Touch 6 1 6 Miscellaneous 6 2 Mechanical Dimensions 7 3 Connector Layout 8 3 1 Front 8 3 1 1 Status LED 9 3 2 Backside 10 3 2 1 Applicable Connectors 13 4 Cooling 14...

Страница 5: ...terface Connections 19 7 5 RS485 20 8 CAN Bus Setup 21 8 1 CAN Bus Station Number 21 8 2 Number of CAN Bus Participants 21 8 3 CAN Bus Data Transfer Rate 21 9 CAN Bus Termination 22 10 Process Diagram...

Страница 6: ...rd Internal I O no Interfaces 1x USB 2 0 Type A front 1x USB device 1 1 Type Mini B back 1x Ethernet 10 100 RJ45 1x CAN bus 6 pin Weidm ller 1x RS485 Modbus 6 pin Weidm ller 1x RS232 9 pin D Sub 1x M...

Страница 7: ...current maximum 16 9 A for 50 s 1 3 Terminal Dimensions 180 x 135 x 50 mm W x H x D Material front plate until HW 5 x 3 mm plastic RAL 9006 since HW 6 00 3 mm aluminum unadulterated Weight until HW 5...

Страница 8: ...e 0 1926 x 0 1790 mm Number of pixels 800 3 RGB x 480 Active surface 154 08 x 85 92 mm Backlighting LED Contrast 500 1 Brightness typically 280 cd m Visible field left right below 70 above 50 1 If the...

Страница 9: ...TOUCH OPERATING PANEL HZS 772 15 07 2020 Page 7 2 Mechanical Dimensions...

Страница 10: ...t many of the USB devices on the market do not comply with USB specifications this can lead to device malfunctions It is also possible that these devices will not be detected at the USB port or functi...

Страница 11: ...nning except when controlled through application differently BLINKS in the CLI while processing the autoexec lsl until the application is running OFF when error occurs or reset can be set from the app...

Страница 12: ...devices Ethernet packets could be sent to the control with such a high frequency i e broadcasts that the high interrupt load could cause a real time runtime error or runtime error By configuring the p...

Страница 13: ...ction for an error voltage The termination is made by an internal 120 resistor on the X5 connector between RS485 Modbus A and RS485 Modbus B Pin Function RS232 1 DCD 2 Rx 3 Tx 4 DTR 5 GND 6 DSR 7 RTS...

Страница 14: ...meant to be used as a removable media and thus only should be removed from the card holder for maintenance purposes Il est recommand de n utiliser que les supports de stockage approuv s par SIGMATEK c...

Страница 15: ...uded with delivery X2 8 pin RJ45 not included in delivery X3 9 pin D Sub not included in delivery X4 X5 6 pin Weidm ller plug B2L3 5 6 included in delivery X6 USB 1 1 Mini B not included in delivery X...

Страница 16: ...power loss can reach up to 8 5 Watts To ensure the necessary air circula tion for cooling the following mounting instructions must be followed 5 Mounting Instructions The following distance from the h...

Страница 17: ...TOUCH OPERATING PANEL HZS 772 15 07 2020 Page 15 A mounting position of 60 to 120 is also required...

Страница 18: ...ATTENTION If the device is not supplied for 2 years the battery is empty Battery order number 01 690 055 MANUFACTURER DATA Lithium battery RENATA 3 0 V 235 mAh Use batteries from RENATA with the label...

Страница 19: ...river loosen and remove the battery cover When exchanging the battery caution must be taken to avoid a short circuit Other wise a defect can be caused in the terminal 3 Using the strap remove the batt...

Страница 20: ...is not previously saved the settings in the heat controller are lost 2 Disconnect the HZS 773 supply 3 Using the correct torx screw driver loosen and remove the battery cover 4 Using the strap remove...

Страница 21: ...connector Noise signals can therefore be prevented from reaching the electronics and affecting the function 7 3 ESD Protection Typically USB devices keyboard mouse are not equipped with shielded cabl...

Страница 22: ...requires a defined quiescent point a pull up and pull down resistor is required in addition to the termination resistor These resistors are already integrated into the device The terminating resistors...

Страница 23: ...nts on the CAN bus depends on the cable length termi nation resistance data transfer rate and the drivers used in the participants With a termination resistance of 120 at least 100 participants are po...

Страница 24: ...20 9 CAN Bus Termination In a CAN bus system both end modules must be terminated This is necessary to avoid transmission errors caused by reflections in the line The termination is made by an internal...

Страница 25: ...TOUCH OPERATING PANEL HZS 772 15 07 2020 Page 23 10 Process Diagram...

Страница 26: ...e time can be configured using two system varia bles Runtime time remaining SWRuntime pre selected value for the runtime counter Solution Optimize the application s cyclic task Use higher capacity CPU...

Страница 27: ...emory module Cause The program memory module is defect The user program is too large The program memory module is missing Solution Exchange the program memory module 08 RESET The CPU has received the...

Страница 28: ...Info 20 LOAD The program is stopped and the CPU is currently receiving a new module or project Info 21 UNZUL MODULE The CPU has received a module that does not belong to the project Solution Recompile...

Страница 29: ...the correct operating system version 35 MAX IO Reserved 36 MODULE LOAD ERROR The LASAL Module or project cannot be loaded Solution Recompile and download the entire project 37 BOOTIMAGE FAILURE A gene...

Страница 30: ...red during a floating point operation 60 DIAS RISC ERROR Error from the Intelligent DIASMaster Restart report error to SIGMATEK 64 INTERNAL ERROR An internal error has occurred all appli cations are s...

Страница 31: ...SRam data Possible Causes SRam configured incorrectly Battery fort he internal program memory supply is empty Solution Analyze log file Event00 log Event19 log Check configuration Change internal prog...

Страница 32: ...s made to open an un known table 114 C_OUTOF_NEAR Memory allocation error 115 C_OUT OF_FAR Memory allocation error 116 C_INCOMAPTIBLE An object with the same name already exists but has a different cl...

Страница 33: ...TOUCH OPERATING PANEL HZS 772 15 07 2020 Page 31 243 LSL LOAD 252 CONTINUE 253 PRERUN The application is started 254 PRERESET The application is ended 255 CONNECTION BREAK...

Страница 34: ...effect fades after the screen has been turned off for some time or when dynamic content is displayed damage from the permanent effect is irreversible This effect can have the following causes Operatio...

Страница 35: ...ed onto the cloth and not directly on the terminal The cleaning solution should not be allowed to reach the terminal electron ics for example through the ventilation slots No erosive cleaning solution...

Страница 36: ...Note added 28 10 2015 15 6 Buffer battery 6 1 Exchanging the battery 6 2 Exchanging the battery Description adapted to actual hardware 19 04 2016 4 1 1 Performance Data Table updated 05 09 2016 7 12...

Отзывы: