K-Factor

 (W): 

Data type: 32 bit floating point (LSB – MSB) 
Description: K-factor which can be used to adjust the flow reading 
 

User Full Scale

 (W): 

Data type: 32 bit floating point (LSB – MSB)) 
Description: The user full scale value allows you to re-range the instrument. Any value between 
 
50% and 100% of the factory full scale is allowed. The new value will also redefine the analog  
outputs of the instrument (when used). The 20mA/5 VDC will represent the new full scale value. 

 

Syscon Software 

Sycon is a tool for the configuration of a Fieldbus network using a Hilscher CIF50-PB master. You 
may be using different configuration software and hardware Master. However you will need to 
accomplish the same functions. No specific slave DTMs of the equipment are available, which are 
generated from the device description files, called generic slave DTMs.  
 
Online diagnostic indicators and auto-scan function for the reading of network participants assist in the 
commissioning of the network. 
 
This guide will explain step by step how to configure the system to support various fieldbus slaves on 
a Hilscher CIF50-PB master. 
 
Before starting make sure that the necessary device description files (GSD & bit maps) are available in 
your device catalog. These are available on our web site. 
 

Import Device Description Files 

 
In order to use a fieldbus device its properties need to be added to the server. This is done by 
importing the device description files into Sycon.  
 

 

Start Sycon and create a new document (File -> New) 

 
A dialog window appears asking to select a fieldbus. For this example select Profibus: 
 

 

 
The main window is loaded. Go to the file menu and select “Copy GSD”: 
 

Содержание Profibus DP 600 Series

Страница 1: ...600 700 Series Profibus DP Instruction Manual Profibus DP Device Specification for Models 640S 760S 780S and 780S UHP Thermal Mass Flow Meters Part Number IM600 700 ProfibusDP Rev V1 May 2013...

Страница 2: ...flow meters for oxygengas You are responsible for determining if this mass flow meter is appropriate for your oxygen application You are responsible for cleaning the mass flow meter tothe degree requ...

Страница 3: ...ing Always remove main power before disassembling any part of the mass flow meter Caution Before making adjustments to the device verify the flow meter is not actively monitoring or reporting to any m...

Страница 4: ...Service Technical Assistance If you encounter a problem with your flow meter review the configuration information for each step of the installation operation andsetup procedures Verify that your sett...

Страница 5: ...witch 10 Server Assigned Address 11 Set Address 126 11 Chapter 3 Configuration 12 GSD File 12 Cyclic Data Overview 12 Cyclic Data Explained 13 Syscon Software 14 Import Device Description Files 14 Con...

Страница 6: ...ailable in the flow meter Set Up Quick Step Plan To successfully add the flow meter to a Profibus DP network you need the following Profibus network with a DP master GSD file Bitmap files Connection c...

Страница 7: ...e following pin configuration Front view The Profibus DP network can be connected with a special terminal block connection This must be requested at the time of ordering The down side of this is the P...

Страница 8: ...can be found online at http verwertraining com wp content uploads InstallationGuideV9_2 pdf The cable must conform to the following specifications Impedance 150 Ohm nominal at frequencies from 3 to 20...

Страница 9: ...Status Leds The interface has two multi color LED s mounted inside the enclosure to indicate the status To access the LED s remove the front cap The left LED shows the status of the interface the righ...

Страница 10: ...anization to be free for installing new devices to the bus Changing the station address is done in two ways either through a dip switch or through the master Dip Switch The dip switches are located in...

Страница 11: ...the server Perform the following steps to change the address 1 Assign a new address from the server 2 Set the dip switch to 128 pin 8 on or higher The assigned address will be used each time that the...

Страница 12: ...ers Hardware characteristics o VPC3 C dependable properties Software characteristics o Supported features of Profibus Freeze Sync auto baud rate detection Maximum bus data lengths Size of used data bu...

Страница 13: ...g outputs of the instrument when used The 20mA 5 VDC will represent the new full scale value Factory Full Scale R Data type 32 bit floating point LSB MSB Description Factory full scale value of the in...

Страница 14: ...s of the equipment are available which are generated from the device description files called generic slave DTMs Online diagnostic indicators and auto scan function for the reading of network particip...

Страница 15: ...estart it to make it available Configure A Slave Create A New Document And Insert A Master Place the master at the top of the line A dialog window appears where a master needs to be selected from a li...

Страница 16: ...Press Yes to use the hardware Note The board ID number changes when extra PCI cards are added to the PC Older configurations must be checked before trying to run them Auto Addressing The master needs...

Страница 17: ...menu Insert Slave Place it below the master Set the slave filter to Sierra Instruments Inc Select the desired GSD file press the Add button set the slave address and description to match the slave an...

Страница 18: ...the added slave in the main window The slave configuration window appears Select the desired modules by double clicking on the module name Press the OK button When done save the new configuration to...

Страница 19: ...19 A pop up may appear warning you that the communication may stop Press Yes to continue The data is downloaded to the master The system is ready to be used...

Страница 20: ...e sure things are working start the debug mode If everything is working correctly then the line between the master and the slave will be green and the bit map shows a green check Double click on the s...

Страница 21: ...utton and leave the debug mode Online Stop Debug Mode Should the line be red error then double click the slave to find out what the problem is The diagnostic window gives an indication of a problem wr...

Страница 22: ...ation is incorrect adjust it and download the configuration Kepserverex 4 0 You may be using different server software or a PLC This example shows how to use the KepserverEx 4 0 free demo software on...

Страница 23: ...23 Choose a Master we are using a Hilscher CIF50 master Click Next The defaults will work click Next Chose the board and type click next...

Страница 24: ...import the setup pb file that we created earlier in Syscon You may browse to the location where you saved it Click on the Browse button Browse the 640S flowmeter pb you just created in Sycon Once high...

Страница 25: ...25 You should see this warning You can review the summary of the new channel you just created You may now add your first slave device Click on Click to add a device...

Страница 26: ...26 Give your new device a name Set the device ID ID 0 was already used for the master so chose 1...

Страница 27: ...27 The next 2 screens will be fine as default click next Choose the device type Click next Review the new device summary click next...

Страница 28: ...eated a new device for your network You will now need create a Tag to access each piece of Cyclic data as specified in chapter 3 2 Click on Click to add a static tag and fill in the boxes as above The...

Страница 29: ...to add the last Address of the previous device to the starting address of the new device Add a tag name Address 0 with the data type in this case IO D 0 S 32 bit float byte swapped Add a description...

Страница 30: ...2 ASCII 7 Flow unit 5 ASCII 8 Totalizer unit 3 ASCII 9 Status 2 INT Incoming Cyclic data master to slave Instance ID Description Size bytes Format 10 Reset totalizer 4 REAL 11 User full scale 4 REAL 1...

Страница 31: ...reeze_Mode_supp 1 Sync_Mode_supp 1 Auto_Baud_supp 1 Set_Slave_Add_supp 1 Min_Slave_Intervall 1 Modular_Station 0 Fail_Safe 0 Slave_Family 0 General Max_Diag_Data_Len 6 DPV1_Slave 1 C1_Read_Write_supp...

Страница 32: ...32 GSD File Cert...