![Sierra INNOVA-SWITCH 215 Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/sierra/innova-switch-215/innova-switch-215_instruction-manual_1266486022.webp)
IM-215 Rev-A.1 Series Innova-Switch™ Page 22 of 42
4.0
OPERATION AND CALIBRATION OF THE Innova-Switch
™
FS4200 SWITCH FOR
FLOW APPLICATIONS
4.1
Pre-Operational Check
With the switch installed and process conditions at no-flow, the following procedure
can be used to verify preliminary operation.
4.1.1
Remove the instrument enclosure cover by turning counter clockwise (ccw) to expose
the Innova-Switch™ Switch electronics.
4.1.2
Turn on power at its source.
4.1.3
Observe that either the red or green LED comes on.
4.1.4
If neither lamp illuminates refer to the trouble shooting Section, 6.2.
4.2
L.E.D. and Relay Status Logic (Fail-safe)
4.2.1
The L.E.D.s (Red; Green) are an indication of the sensors status (ie. flow below the
setpoint or flow above the set point) and are not affected by the position of the failsafe
jumper J-2. The failsafe jumper J-2 changes the relay activation status allowing the
user to select the failsafe power off condition most appropriate to the application.
Refer to the tables below that show the logic conditions between the sensors, L.E.D.
lights, relay coil and contacts for each position of the failsafe jumper J-2.
4.2.2
Normal Operation (as set at factory)
The switch comes configured from the factory with the following operation with the J-2
jumper in the B(2-3) position. (Refer to Figure 8.0.)
RELAY
RED GREEN RELAY
CONTACT
SENSOR STATUS
LED
LED COIL STATUS
STATUS
o NC
No Flow or Flow Below Set Point
ON
OFF
Activated
o NO
o NC
Flow or Flow Above Set Point
OFF
ON
Deactivated
o NO
Содержание INNOVA-SWITCH 215
Страница 36: ...IM 215 Rev A 1 Series Innova Switch Page 36 of 42 9 2 FLOW CONVERSION CHART...
Страница 37: ...IM 215 Rev A 1 Series Innova Switch Page 37 of 42 9 3 FLOW OF WATER THROUGH SCHEDULE 40 STEEL PIPE...
Страница 38: ...IM 215 Rev A 1 Series Innova Switch Page 38 of 42 10 0 OPTIONS 10 1 LIVETAP LT...
Страница 39: ...IM 215 Rev A 1 Series Innova Switch Page 39 of 42 10 2 VARIABLE INSERTION VI...
Страница 40: ...IM 215 Rev A 1 Series Innova Switch Page 40 of 42 10 3 THERMOCOUPLE OUTPUT TO and 10 4 RTD OUTPUT RT...
Страница 41: ...IM 215 Rev A 1 Series Innova Switch Page 41 of 42...