Modbus
Address Parameter Units FIX
EGU
40080:0
Sensor 7: Sensor Disconnected
(Trouble Bits)
40080:2
Sensor 7: Voltage Regulator Failure
40080:3
Sensor 7: Sensor Bad
40080:4
Sensor 7: Duplicate Sensor
40080:5
Sensor 7: Timer Failure
40080:6
Sensor 7: Sensor Bridge Failure (Combustibles)
40080:7
Sensor 7: Type Error
40081:0
Sensor 7: Enabled
40081:1
Sensor 7: Auto Calibration Enabled
40081:2
Sensor 7: Low Alarm Latch
40081:3
Sensor 7: Calibrated
40081:4
Sensor 7: Zone Option Enabled
40081:5
Sensor 7: Calibration Table Initialized
40081:6
Sensor 7: H
2
S Sensor Resistance too high
40081:7
Sensor 7: Operate Mode (as opposed to Warm Up Mode)
40082:0
Sensor 7: High Alarm Latch
40082:1
Sensor 7: Low Sensitivity
40082:2
Sensor 7: Sensor not Valid
40084:0
Sensor 7: Concentration % / PPM 0 - 6553.5
40090:0
Sensor 8: Sensor Disconnected
(Trouble Bits)
40090:2
Sensor 8: Voltage Regulator Failure
40090:3
Sensor 8: Sensor Bad
40090:4
Sensor 8: Duplicate Sensor
40090:5
Sensor 8: Timer Failure
40090:6
Sensor 8: Sensor Bridge Failure (Combustibles)
40090:7
Sensor 8: Type Error
40091:0
Sensor 8: Enabled
40091:1
Sensor 8: Auto Calibration Enabled
40091:2
Sensor 8: Low Alarm Latch
40091:3
Sensor 8: Calibrated
40091:4
Sensor 8: Zone Option Enabled
40091:5
Sensor 8: Calibration Table Initialized
40091:6
Sensor 8: H
2
S Sensor Resistance too high
40091:7
Sensor 8: Operate Mode (as opposed to Warm Up Mode)
40092:0
Sensor 8: High Alarm Latch
40092:1
Sensor 8: Low Sensitivity
40092:2
Sensor 8: Sensor not Valid
40094:0
Sensor 8: Concentration
% / PPM
0 - 6553.5