background image

Model 3100 Series Flame Detector (11/04)

Page:  3

 Instruction Manual

2.2 Field-of-View (See Figure 2-1)

Optical Flame Detectors must be able to “see” the
fire to declare an alarm. Any obstruction between
the detector and the threat area will impair the de-
tectors ability to cover the threat area.  An obstruc-
tion is anything that is not transparent to the sensor
elements of the detector.  UV sensors and some
types of IR sensors cannot see through glass or plas-
tics.  The 3100 series of Flame Detectors has a
120° Field of View.

When covering a large area the detectors should be
located to provide overlapping fields of view to in-
sure complete coverage.

2.3 Range

The size of fire and type of materials which consti-
tute the threat will affect the detector’s range.  Dif-
ferent materials produce different amounts of the
radiant energy used by the detector to “see” the
fire.   Also, the range of the detector is a function of
the fire size.  Using the square of the distance rule,
if the device will detect a one sq. ft. fire at 60 feet,
to detect a 1/4 size fire (aprox. 6 sq. in.) the devices
must be within 30 feet.  The Model 3100 Detector
is optimized to a 1 sq. ft. Kerosene fire at 80 feet
with the sensitivity settings set to maximum sensi-
tivity.

2.4 Environment

All optical flame detectors sense radiant energy at
some frequency or frequencies within their Field-
of-View.  Any source which radiates energy at the
same frequency or frequencies used by the detector

to sense a fire may impact the detector’s ability to
“see” the fire.  Care should be taken to minimize
radiant energy sources within the detectors Field-
of-View.  Because of the variety of environments
and conditions, a factory trained technician or quali-
fied P.E. should be consulted before deciding on
the location of devices.  The Model 3100 Detector
uses an Ultraviolet sensor (180 - 260 nanometers),
an Infrared sensor (.715 - 3.5 microns), and a Vis-
ible sensor (480 - 560 nanometers).

2.5 Configuration (See Figure 2-2)

All of the 3100 Series models have field adjustable
configuration switches located on the front face of
the detector.  The factory settings are shown in 

italic

text.  The enhanced models  have additional con-
figuration options for the Verified Fire.

2.5.1 Sensitivity

All versions have several sensitivity settings
available.  The sensitivity settings are 20, 40,
60, and 

80

 feet.  Each setting is optimized to

alarm on a 1 sq. ft. Kerosene fire within 5
seconds.  Switches 1 and 2 control the sensi-
tivity.  

The factory default is 80 feet. (SW1

and SW2 are off.)

Note: Different fuels emit energy at different
rates. For example; a fire involving fuel oil
does not emit energy at the same rate as gaso-
line. Consequently, the Model 3100 will be
able to respond to a gasoline fire at a little
greater distance than it will to a fuel oil fire.
Similary, a fire involving acetone will be seen
at a greater distance than one involving gaso-
line.

SW1
SW2
SW3
SW4
SW5

SW9
SW8
SW7
SW6

SW1 Shown in off position

SW2 Shown in on position

Figure 2-2:  Configuration Switches

Содержание 3100-01

Страница 1: ...MODEL 3100 XX FLAME DETECTOR ...

Страница 2: ...owing Sierra Monitor products Model Description 3100 01 Flame Detector Standard 3100 02 Flame Detector Enhanced Relay 3100 03 Flame Detector Enhanced Relay 3100 04 Flame Detector Enhanced Relay 3100 05 Flame Detector Enhanced Relay 3100 06 Flame Detector Flame Detector 4 20mA The instructions are effective for the above models as of March 1 1997 Instruction Manual Part Number T15007 Rev C2 Applica...

Страница 3: ...ral Precautions 7 3 2 Housing and Conduit 7 3 3 Connection 7 3 4 Testing 8 4 MAINTENANCE 8 4 1 Lens Cleaning 8 5 TROUBLESHOOTING 9 6 SPECIFICATIONS 11 7 WARRANTY 11 APPENDICES A FIGURES A 1 Exploded View 12 A 2 Housing Dimensions 12 A 3 Common Wiring Configurations 13 A 4 Enhanced Series Wiring Connections 14 B TABLES 15 B 1 Dip Switch Settings 15 B 2 Connectors 16 B 3 Verify Aux Relay Configurati...

Страница 4: ...y which may be connected as normally open or normally closed contacts Models 3100 02 03 04 and 05 have in addition to the Fire and Faults relays a Fire Verify system and an Auxiliary Fault system The Fire Verify system adds a field ad justable level of certainty to the declaration of a verified fire The Auxiliary Fault system will acti vate the Aux Relay for the Lens Test fault This allows a separ...

Страница 5: ...tinuously monitoring the internal systems When a fault is detected the Fault Relay is de energized In Fault Mode the LEDs will flash a code indicating the type of fault Afault indication may mean the device is unable to detect a fire or that a device has become unreliable i e a Voltage Low fault For most faults the detector will return to Normal Mode when the fault condi tion is corrected The Mode...

Страница 6: ...e same frequency or frequencies used by the detector to sense a fire may impact the detector s ability to see the fire Care should be taken to minimize radiant energy sources within the detectors Field of View Because of the variety of environments and conditions a factory trained technician or quali fied P E should be consulted before deciding on the location of devices The Model 3100 Detector us...

Страница 7: ...t de energize when a flame is not present for a short period of time For the detector to be set to Non latching both Fire Output and Verify Output must be set to Non latching If either the fire out put or the verify output is set to Latching then the detector will be set to Latching When the detector is set to Latching the LED s will indicate an alarm until the device is reset regardless of the fi...

Страница 8: ...t indication The de tector is disabled if a fault 2 or 3 is indicated 2 7 Relay operation See Figure 2 4 The Model 3100 01 has two relays the enhanced Models 3100 02 03 04 and 05 have four relays The function of the Fire and Fault Relays is the same on all models The Verify Relay and Aux Relay is only available on the enhanced models All relay connections are made at the connectors lo cated on the...

Страница 9: ...fy In and Verify Out provides connections for nor mallyopencontactsonthe3100 02and3100 04 or normally closed contacts on the 3100 03 and 3100 05 The configuration of Nor mally Open or Normally Closed contacts is fixed and can only be changed by the fac tory 2 7 4 Auxiliary Fault The Aux Relay is energized whenever the detector fails the Lens Check test This fault indicates the detectors inability ...

Страница 10: ... to various systems All connections are made on the back of the Model 3100 Flame Detector Module Remove the housing cover from the housing base Loosen the two slot ted head captive screws located on the top of the PC board Lift the Detector Module out of the housing base Strip and connect the wires to the connectors located on the back of the Detector Module 3 3 1 Power Power for the 3100 01 02 03...

Страница 11: ... must be observed 4 0 MAINTENANCE The self test functions eliminate the need for most regular maintenance procedures If a detector indi cates a fault use the troubleshooting section of this document to correct the fault Contact the local authority having jurisdiction or consult the local codes for any maintenance they may require for the type of system installed 4 1 Lens Cleaning The most common f...

Страница 12: ...libration Fault Calibration constants have been corrupted Factory service is required 5 2 4 Fault Type 4 Voltage Low Fault The input voltage is below 15 VDC Re move the Detector Module from the hous ing With the detector connected to power measure the voltage between Pin 1 and Pin 4 on the Power connector J5 The volt age should be between 15 32 VDC If the voltage is out of range check external wir...

Страница 13: ...me on the detector is operating normally Check external alarm initiating cir cuit wiring 2 If the relay closes and the LEDs remain off or the relay remains open and the LEDs come on the detector needs factory service 3 If the relay remains open and the LEDs re main off contact the factory for further diag nostic information ...

Страница 14: ...d hereunder including all implied warranties of merchant abilityandfitnessandtheexpresswarrantiesstatedherein are in lieu of all obligations or liabilities on the part of SMC for damages including but not limited to conse quential damages arising out of or in connection with the use or performance of the product Sensitivity 1 ft sq Pan fire on axis 80 feet within 5 seconds using standard fuel Swit...

Страница 15: ...Instruction Manual Page 12 Model 3100 Series Flame Detector 11 04 Figure A 2 Model 3100 Series Dimensions Figure A 1 Model 3100 Series Exploded View APPENDIXA ...

Страница 16: ...Model 3100 Series Flame Detector 11 04 Page 13 Instruction Manual Figure A 3 Model 3100 Series Common Wiring Connections ...

Страница 17: ...Instruction Manual Page 14 Model 3100 Series Flame Detector 11 04 Figure A 4 Model 3100 Series Enhanced Wiring Connections Factory jumpers are used to set NC or NO connections ...

Страница 18: ...F OFF ON Level 5 Min Verify shorter ON OFF ON Level 6 Max Verify longer OFF ON ON Level 7 Verify Disabled ON ON ON B 1 3 Fire Output Latching Control Fire Output Description SW6 Latching Alarm until Power down Reset OFF Following Alarm until no fire 5 to 10 sec ON B 1 4 Verify Relay Latching Control 3100 02 03 04 and 05 Models only VerifyRelay Description SW7 Latching Alarm until Power down Reset ...

Страница 19: ...f Relay Pin 6 Right Most Aux Fault Relay NO or NC Side of Relay B 2 3 Fault Connector J4 Fault Relay Description Normally Energized State Pin 1 Left Most Normally Closed Side of Relay Pin 2 Middle Common Side of Relay Pin 3 Right Most Normally Open Side of Relay B 2 4 Power Communications Connector J5 Power Comm Description Pin 1 Left Most Pin 5 Power DC Pin 2 Pin 6 Communication RS 485 Pin 3 Pin ...

Страница 20: ...s the detectors ability to tolerate both modulated and unmodulated false alarm stimuli FalseAlarms Source Distance Unmodulated Modulated Resistive Electric Heater 1320 Watt 6 Feet No Response No Response Fluorescent Lights 2 40 Watt Bulbs 6 Feet No Response No Response Halogen Light 500 Watt 10 Feet No Response No Response Incandescent Light 100 Watt 6 Feet No Response No Response Arc Welder 50 Wa...

Страница 21: ...11 04 B 7 Detector Response to Fuels Table Fuel Distance Fire Size Response Time Heptane 80 Feet 1 Square Foot Less than 3 sec Silane 50 Feet 18 inch jet Less than 3 sec Hydrogen 15 Feet 18 inch jet Less than 5 sec Kerosene 75 Feet 1 Square Foot Less than 5 sec ...

Страница 22: ...Model 3100 Series Flame Detector 11 04 Page 19 Instruction Manual APPENDIX C WIRING CONNECTIONS ...

Страница 23: ...1 2 4 6 7 16 Testing 8 Verify 1 Fire Following 2 4 6 Fire Probability 2 H Housing 1 7 I Infrared 3 L Latching 2 4 6 15 LEDs 2 4 5 20 Lens 8 Lens Test 1 2 M Mode Alarm 2 4 5 Fault 5 Fire Following 2 Latching 2 Normal 2 4 Verified Fire 4 N Normal Mode 2 4 5 Normally Closed 2 6 7 Normally Open 2 6 7 P Power 4 7 16 19 R Range 3 Relay 5 Aux 2 5 6 7 17 Auxiliary 1 Control 4 Fault 1 2 6 7 Fire 1 2 4 6 7 ...

Страница 24: ...del 3100 Series Flame Detector 11 04 Page 21 Instruction Manual T Testing 8 U Ultraviolet 3 V Verified Fire 2 4 5 6 Verify Control 4 Relay 2 4 5 6 7 15 Verify Control 6 15 Versions 2 Visible 3 W Wiring 7 ...

Отзывы: