Siemens Industry, Inc.
Building Technologies  Division

P/N 315-048670-11

7

Care must be taken when installing the zone input and zone output field wiring to

prevent possible cross wiring. This can cause severe damage to the system when

powered up or when zone is activated.

 The screw terminals can accommodate one 12-18 AWG or two 16-18 AWG.

If the total output of all 8 zones exceeds 12 amps, a single PSC-12 cannot be used to

supply the ZIC-8B. Refer to the PSC-12 Installation Instructions, P/N 315-033060 for

information when the total system load exceeds 12 amps.

INSTALLATION

The ZIC-8B plugs perpendicularly into one slot in the CC-5/CC-2 card-cage via two 96-
pin DIN connectors and can occupy any slot in the card cage. (Refer to Figure 4.)

Insert the ZIC-8B card into the card guides right side up (lettering on the front panel
is legible)

Slide the card in until the card edge connectors contact
the receptacles on the motherboard.

Verify that the DIN connectors of the card and the card-
cage aligned properly. The card can only plug in one
direction to the card cage, if it does not align, DO NOT
FORCE the card.

Place thumbs on the front panel adjacent to the captive
screws and gently apply even pressure on the card
until the connectors seat in the receptacles on the
motherboard.

Secure with the captive screws.

Power up the system and verify that the ZIC-8B power
LED turns ON.

ELECTRICAL RATINGS

Figure 4

Installing The  ZIC-8B

24V Back Plane or

External Power Current

See NOTE below

Screw Terminal 24V Current

Total Device Current

6.2V Back Plane Current

0

24V Standby Current

105mA

NOTE:  

The 24V current is dependent on the usage and wiring

type of each ZICCkt of the ZIC-8B. Listed below are the required

current draws for each zone usage and wiring type.

ZIC-8B Current Requirement

Per Output Zone

Zone Usage

Output Current

Requirement

Not Used

0

NAC

17mA

Strobe - Sync.

17mA

Strobe - Unsync.

17mA

Speaker Zone - 2 Ch.

34mA

Speaker Zone - 1 Ch.

17mA

NAC - Coded

17mA

ZIC-8B Supervisory State Standby Current =91mA

Содержание ZIC-8B

Страница 1: ... supports synchronized and non synchronized strobes This selection is available in the Zeus tool under the detail properties for each ZIC 8B circuit Synchronization across multiple ZIC 8B cards is automatic as a part of the FireFinder XLS Desigo Fire Safety Modular Cerberus PRO Modular operating characteristics Refer to document P N 315 096363 for a list of strobes that support synchronization Fea...

Страница 2: ...he zone output is supervised for open and short circuit condi tions while the zone is inactive and allows different combinations of output configura tions standard NAC speakers etc per card Each ZIC 8B card occupies any one card slot in the CC 5 CC 2 cardcage The ZIC 8B also has the capability to detect ground fault on its zone output as indicated by a diagnostic LED See Note above Controls and In...

Страница 3: ... ZIC 8B has detected a trouble on Zone 3 open circuit or short circuit or Zone 3 is disarmed ZONE 4 ACTIVE Red Normally OFF When illuminated indi cates that Zone 4 is active TROUBLE Yellow Normally OFF When illuminated indi cates that the ZIC 8B has detected a trouble on Zone 4 open circuit or short circuit or Zone 4 is disarmed ZONE 5 ACTIVE Red Normally OFF When illuminated indi cates that Zone ...

Страница 4: ... the Zeus ProgrammingTool The ZIC 8B card and its Out Ckt properties must be set prior to normal operation In the Zeus ProgrammingTool highlight the selected ZIC 8B card in the Physical View and open the Detail View Properties to modify and or define the following ZIC 8B card properties HNET Address This address must match the address set in ZIC 8B hardware Base Language Custom Message The message...

Страница 5: ...ion PRE INSTALLATION The following components must be set prior to inserting the card into the CC 5 CC 2 refer to Figure 2 S2 Reset Switch Momentarily Closed switch that when pressed will initiate a hard reset to the ZIC 8B similar to a cold boot S3 S4 S5 Network Address Switch Set the three digit HNET network address for the ZIC 8B using the three rotary dial address switches located near the bot...

Страница 6: ...B by lining up the connector on the ZIC 2C to the receptacle on the ZIC 8B Gently insert the connector into the receptacle being careful not to bend the connector Refer to Figure 2 for positioning the ZIC 2C on the ZIC 8B WIRING Remove all system power before installation first battery then AC To power up connect the AC first then the battery All field wiring to the ZIC 8B is connected to the term...

Страница 7: ...eceptacles on the motherboard Verify that the DIN connectors of the card and the card cage aligned properly The card can only plug in one direction to the card cage if it does not align DO NOT FORCE the card Place thumbs on the front panel adjacent to the captive screws and gently apply even pressure on the card until the connectors seat in the receptacles on the motherboard Secure with the captiv...

Страница 8: ... If a ZIC 8BA has the following ZICCkt setting ZICCkt 1 Speaker Zone 2 Ch ZICCkt 2 Speaker Zone 2 Ch ZICCkt 3 Speaker Zone 2 Ch ZICCkt 4 Speaker Zone 2 Ch ZICCkt 5 Speaker Zone 2 Ch ZICCkt 6 Speaker Zone 2 Ch ZICCkt 7 Speaker Zone 2 Ch ZICCkt 8 Speaker Zone 2 Ch By applying the equation above the maximum current requirement for this card will be determined Max Current 105 34 34 34 34 34 34 34 34 3...

Страница 9: ... max 24VDC 4 EOL resistor 24k ohms 1W 5 P N 140 033771 5 Polarity shown in active state 6 Maximum line resistance is dependent upon the maximum current draw of connected notifica tion appliances when activated The field wiring resistance cannot exceed the maximum line resistance specified for any given NAC current draw SeeTable 7 For a list of Compatible Notification Appliances refer to P N 315 09...

Страница 10: ...must be in accordance with Article 760 of NEC or local building codes Wiring for each zone must be Class B 2 All output circuits are power limited to NFPA 70 per NEC 760 3 Electrical Ratings Output Zone Supervisory 8mA max 24VDC Output Zone Active 25V 25 watts max zone 70V 30 watts max zone 4 EOL resistor 24k ohms 1 watt 5 P N 140 033771 5 Polarity shown in active state 6 For a list of Compatible ...

Страница 11: ...must be in accordance with Article 760 of NEC or local building codes Wiring for each zone must be Class B 2 All output circuits are power limited to NFPA 70 per NEC 760 3 Electrical Ratings Output Zone Supervisory 8mA max 24VDC Output Zone Active 25V 25 watts max zone 70V 30 watts max zone 4 EOL resistor 24k ohms 1 watt 5 P N 140 033771 5 Polarity shown in active state 6 For a list of Compatible ...

Страница 12: ...ecurity concept that is customized to individual security needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components use...

Отзывы: