GND FAULT

(Yellow)

Normally OFF. When illuminated,
indicates that the ZIC-4AC has
detected either a negative or positive
ground fault on its field wiring.

ZONE 1 (2, 3, 4) ACTIVE

(Red)

Normally OFF. When illuminated,
indicates that Zone 1 (2, 3, 4) is active.

TROUBLE

(Yellow)

Normally OFF. When illuminated,
indicates that the ZIC-4AC has
detected a trouble on Zone 1 (open
circuit or short circuit).

Three rotary dial switches

at the bottom of the front panel are used to set

the CAN network address of the ZIC-4AC.

PRE-INSTALLATION

The following components must be set prior to inserting the card to the CC-5
(refer to Figure 2):

S1: Not used

Switch position has to be off
(upper position)

S2: Not used

All four switch positions have to
be off (left position)

S3: Reset Switch

Momentarily Closed switch that
when pressed will initiate a hard
reset to the ZIC-4AC (similar to a
cold boot).

S5: Input Power Select

This switch selects the source of
voltage input to power the ZIC-
4AC.

BP Power

indicates that

the input is derived from the
backplane of the CC-2/CC-5 and

EXT Power

indicates that the

input is derived from E5/E11
terminal of the CC-2/CC-5,
normally connected to non-
power limited output of the PSC-
12/PSX-12. It is important to take
into account the source of the
voltage during power
calculations.

S4, S6, S7: Network Address Switch

Set the two-digit CAN network address for the ZIC-4AC using the three rotary
dial address switches located near the bottom of the front panel. (Refer to
Figure 1 for the location of the switches.) The address for the ZIC-4AC must
be the same as the address selected for it in the Zeus Programming Tool. To
set the address, turn the pointers on each of the three dials to the numbers
for the selected address. For example, if the address is 23, set the pointer for
the HUNDREDS dial to “0”, set the pointer for the TENS dial to “2”, and set
the pointer for the ONES dial to “3”. The range of allowable addresses is
from 001 to 099 (leading zeros must be used).

Figure 2

ZIC-4AC Switch and Jumper Location
for Strobe usage

Содержание ZIC-4AC

Страница 1: ...ith 2A current limit The ZIC 4AC then sends a message to the PMI indicating that it is unconfigured The ZIC 4AC supports one or two channel bulk amplification as well as synchronized and non synchronized strobes This selection is available in the Zeus tool under the detail properties for each ZIC 4AC circuit Synchronization across multiple ZIC 4AC cards is automatic as a part of the system operati...

Страница 2: ... as strobe sync will switch output polarity at the same time also outputs from other ZIC 4AC Same for In Outputs 2 3 and 4 Bulk amplification 1 channel Input 1is connected directly to output 1 output is ON steady Same for In Outputs 2 3 and 4 Bulk amplification 2 channel This mode provides the possibility to choose between two different signal for one speaker line Signal one A has to be connected ...

Страница 3: ...itch selects the source of voltage input to power the ZIC 4AC BP Power indicates that the input is derived from the backplane of the CC 2 CC 5 and EXT Power indicates that the input is derived from E5 E11 terminal of the CC 2 CC 5 normally connected to non power limited output of the PSC 12 PSX 12 It is important to take into account the source of the voltage during power calculations S4 S6 S7 Net...

Страница 4: ...one Usage S1 S2 Header Position Speaker Zone OFF up OFF left none NAC OFF up OFF left 1 3 and 4 6 Programming Options Each ZIC 4AC card is subdivided into four output circuits that can be programmed independently of each other In the Zeus Programming Tool highlight the selected ZIC 4AC Output Ckt in the Physical View and open the Detail View Properties to modify and or define the following ZIC 4AC...

Страница 5: ...l block by turning it clockwise The top terminals 1 through 8 and 9 through 16 are connected to the notification appliance devices such as bells horns strobes speakers etc Each zone has four terminal connections Class A Class A These terminals are power limited The bottom terminals 17 through 24 are connected to the input power source of the NAC devices Each zone has a terminal and terminal These ...

Страница 6: ...le Slide the card in until the card edge connectors contact the receptacles on the motherboard Verify that the DIN connectors of the card and the card cage aligned properly The card can only plug in one direction to the card cage if it does not align DO NOT FORCE the card Place thumbs on the front panel adjacent to the captive screws and gently apply even pressure on the card until the connectors ...

Страница 7: ...A 6mA Speaker Zone 34mA 6mA ZIC 4AC Module Current 89mA To calculate the maximum backplane current the following equation should be used ZIC 4AC Module Current Zone 1 Usage Req See Table above Class A current if Class A Zone 2 Usage Req See Table above Class A current if Class A Zone 3 Usage Req See Table above Class A current if Class A Zone 4 Usage Req See Table above Class A current if Class A ...

Страница 8: ...ed 3 Electrical Ratings Output Zone Supervisory 4mA max 24VDC Output Zone Alarm 4A max 24VDC 4 EOL resistor 24k ohms 1 watt 5 comes with module package EOL Kit S24135 D55 A1 5 Polarity shown in active state 6 Maximum line resistance is dependent upon the maximum current draw of connected notification appliances when activated The field wiring resistance cannot exceed the maximum line resistance sp...

Страница 9: ...for each zone can either be Class A or Class B 2 All output circuits are power limited 3 Electrical Ratings Output Zone Supervisory 4mA max 24VDC Output Zone Active 400 Watts max zone 4 EOL resistor 24k ohms 1 watt 5 comes with module package EOL Kit S24235 D55 A1 5 Polarity shown in active state ...

Страница 10: ...ne Active 400 Watts max zone 4 EOL resistor 24k ohms 1 watt 5 comes with module package EOL Kit S24135 D55 A1 5 Polarity shown in active state 6 For two channel speaker application the channel with higher priority EVAC must be connected to inputs 2 4 and the channel with the lower priority ALERT must be connected to inputs 1 3 to ensure proper switching operation of the ZIC 4AC 7 Verify that P1 P4...

Страница 11: ...RCUIT BREAKER TO PSX 12C OR CC 5 CC 2 TAMPER SWITCH BATTERY THERMISTOR OF F O ON Figure 8 ZIC 4AC Strobe Wiring With PSC 12C Power Supply Notes 1 All output circuits are power limited 2 Electrical Ratings Output Supervisory Current 2 mA max 24VDC Output Alarm Current 4A max 24VDC 3 Maximum line resistance Refer to table on page 7 4 Inputs can be daisy chained provided that the power supply can sus...

Страница 12: ...ns Gebäudesicherheit GmbH Co oHG D 80930 München Delivery subject to availability right of technical modifications reserved Order No A24205 A334 B836 Edition 2 P N 315 035200 2 Printed in the Federal Republic of Germany on environmental chlorine free paper For CE applications in Cerberus E100 systems refer to Installation Instruction A24205 A334 B844 English or A24205 A334 A844 German ...

Отзывы: