background image

Siemens Industry, Inc.
Building Technologies  Division

P/N 315-033050-15

14

Figure 9

ZIC-4A Releasing Service Wiring

NOTES
1. All wiring must be in accordance with

Article 760 of NEC or local building
codes.

2. Electrical Ratings: 24VDC

2mA max @ Supervisory
3A max @ Alarm

3. All circuits are power limited to

NFPA 72 per NEC 760.

4. EOL resistor, 24k ohms,

1 watt, 5%, P/N 140-820405.

5. Polarity shown in active state for UL

compliant wiring only.

6. N/A
7. Releasing is wired for Class B only.
8. Any circuit may be used.
9. Input voltage sources can be daisy-

chained.

10. For Compatible Solenoids, refer to

table at right.

11. Refer to Zeus Quick Start Guide (P/N

315-033875) for information about
programming of releasing service.

12. Refer to CAB1/CAB1R (P/N 315-

0330007) and CAB2-BB/CAB3-BB (P/
N 315-033009) Installation
Instructions for details on
the separation of power
limited and non-power
limited wiring.

13. Positive or negative ground

fault detected at <40K ohms
for terminals 1-16.

14. For FM approved Pre-Action/

Deluge: All initiating devices
connected to the system
must be wired CLASS A.

15. Wiring diagram shown for

24VDC solenoid.

16.  Wiring diagram shown for

12VDC solenoids (2 units in
series.)

17. Wiring diagram shown for

6VDC solenoids (4 units in
series.)

18. The ZIC-4A circuit must be

configured as “NAC Steady”.
The “Releasing Zone” usage
in Zeus is only to be used
for legacy UL releasing
applications that did not
include the REL-EOL.

19. The ZIC-4A circuit must

include a UL864 listed
Releasing Disconnect
Switch such as Siemens
Model RSM-5, P/N S54339-
F1-A1. The  switch  position
must be monitored using an
input module such as the
HTRI-M using the second
set of contacts.

RELEASING  ZONE

ZONE 3

RELEASING  ZONE

ZONE 1

RELEASING ZONE

ZONE 2

REL-EOL
MODULE

+

-

+

-

+

-

+

-

* The REL-EOL ships
   with three resistors. 
   Use the 24K resistor 
   (P/N 140-034677) 
   with the ZIC-4A.

See Note 15

See Note 14

See Note 14

See Note 16

1      

2      

3      

4      

5      

6      

7      

8

9     

10     

11     

12     

13     

14     

15     

16

+

+

+

-

+

-

+

-

17     

18     

19     

20     

21     

22     

23     

24

ZONE 1 & 2

INPUT

ZONE 3

INPUT

ZONE 4

INPUT

ONE SLOT OF CC-5

REL-EOL
MODULE

REL-EOL
MODULE

REL-EOL
MODULE

RELEASING  ZONE

ZONE 4

+

-

+

-

+

-

+

-

+

+

-

-

-

-

NC

NC

NC

NC

NC

NC

NC

NC

24K, 

1/2W

5%

*

24K, 

1/2W

5%

*

24K, 

1/2W

5%

*

24K, 

1/2W

5%

*

Disconnect

Switch

Supervising

Module

Disconnect Circuit

Disconnect 

Circuit

Disconnect 

Circuit

Disconnect 

Circuit

S

D

I

O

N

E

L

O

S

E

L

B

I

T

A

P

M

O

C

N

O

I

T

A

C

I

L

P

P

A

R

E

R

U

T

C

A

F

U

N

A

M

R

O

L

E

D

O

M

D

I

O

N

E

L

O

S

R

E

B

M

U

N

T

R

A

P

S

N

E

M

E

I

S

R

E

B

M

U

N

T

R

A

P

F

O

R

E

B

M

U

N

S

D

I

O

N

E

L

O

S

S

E

I

R

E

S

N

I

M

U

M

I

X

A

M

F

O

R

E

B

M

U

N

S

D

I

O

N

E

L

O

S

D

R

A

C

R

E

P

L

A

V

O

R

P

P

A

3

1

A

P

F

N

)

e

g

u

l

e

D

n

o

it

c

A

-

e

r

P

(

O

C

S

A

7

0

1

A

0

1

2

8

R

A

/

N

C

D

V

4

2

e

n

O

4

L

U

7

0

1

A

0

1

2

8

T

C

D

V

4

2

e

n

O

4

L

U

R

E

N

N

I

K

S

2

C

1

1

1

C

0

N

0

0

N

9

9

N

B

G

1

2

3

7

C

D

V

4

2

e

n

O

4

L

U

5

2

X

B

L

2

V

L

C

D

V

4

2

e

n

O

4

L

U

1

0

0

2

A

P

F

N

O

C

S

A

6

-

2

3

5

8

1

2

V

H

G

B

1

1

9

7

9

6

-

0

0

5

C

D

V

6

r

u

o

F

6

1

L

U

E

T

I

T

P

A

N

S

5

F

4

A

-

B

N

2

-

A

3

2

8

2

G

B

2

1

9

7

9

6

-

0

0

5

C

D

V

2

1

o

w

T

8

L

U

6

F

4

A

-

B

N

2

-

A

3

2

8

2

G

B

3

1

9

2

9

6

-

0

0

5

C

D

V

4

2

e

n

O

4

L

U

4

F

4

A

-

B

N

2

-

A

3

2

8

2

G

B

1

1

9

7

9

6

-

0

0

5

C

D

V

6

r

u

o

F

6

1

L

U

B

4

9

5

2

3

9

G

B

1

7

6

9

4

6

-

0

0

5

C

D

V

4

2

e

n

O

4

L

U

X

L

T

4

2

-

2

-

C

E

Y

P

C

/

8

2

1

0

A

P

G

B

5

2

9

7

9

6

-

0

0

5

C

D

V

4

2

e

n

O

4

L

U

4

2

-

2

-

C

E

Y

P

C

/

7

3

3

0

A

P

G

N

I

K

I

V

1

9

5

1

1

A

/

N

C

D

V

4

2

e

n

O

4

L

U

2

9

5

1

1

C

D

V

4

2

e

n

O

4

L

U

5

9

5

1

1

C

D

V

4

2

e

n

O

4

L

U

1

0

6

1

1

C

D

V

4

2

e

n

O

4

L

U

2

0

6

1

1

C

D

V

4

2

e

n

O

4

L

U

5

1

2

3

1

C

D

V

4

2

e

n

O

4

L

U

3

4

8

3

1

C

D

V

4

2

e

n

O

4

L

U

4

4

8

3

1

C

D

V

4

2

e

n

O

4

L

U

E

D

D

I

K

0

0

0

-

4

9

4

7

9

8

-

K

W

A

/

N

C

D

V

4

2

e

n

O

4

L

U

S

U

N

A

J

1

8

4

8

1

,

2

2

7

0

2

A

/

N

C

D

V

4

2

e

n

O

4

L

U

X

A

M

I

N

I

M

3

2

3

9

8

8

A

/

N

C

D

V

4

2

e

n

O

4

L

U

Initiating devices configured for supervisory signaling

are latching by default. If non-latching behavior is

required, check the self restoring supervisory checkbox

in the node properties for your Zeus configuration.

Содержание ZIC-4A

Страница 1: ...ry Industry Inc Inc Inc Inc Inc Building Building Building Building BuildingT T T T Tec ec ec ec echnologies Di hnologies Di hnologies Di hnologies Di hnologies Division vision vision vision vision P N 315 033050 15 Zone Indicating Card Installation Instructions Model ZIC 4A ...

Страница 2: ...rvised Notification Appliance Wiring 12 ZIC 4A Supervised MunicipalTie Wiring 13 ZIC 4A Leased Line Wiring 13 ZIC 4A Releasing Service Wiring 14 ZIC 4A Releasing Service Wiring With PSC 12 Power Supply 15 ZIC 4A Bell Follower Circuit Wiring 16 ZIC 4ATwo Channel Audio Wiring 17 ZIC 4A Single Channel Audio Wiring 18 ZIC 4ATwo Channel Audio and Strobe Wiring 19 ZIC 4A Single Channel Audio and Strobe ...

Страница 3: ...ized strobes This selection is available in the Zeus tool under the detail properties for each ZIC 4A circuit Synchroniza tion across multiple ZIC 4A cards is automatic as a part of the FireFinder XLS Desigo Fire Safety Modular Cerberus PRO Modular operating characteristics Refer to docu ment P N 315 096363 for a list of strobes that support synchronization Features ZIC 4A features are as follows ...

Страница 4: ...ing the reset switch re initializes the ZIC 4A operation The LEDs follow the reset switch and their functions are defined as follows POWER Green Normally ON When illuminated indi cates that power for the ZIC 4A is applied to the card CARD FAIL Yellow Normally OFF When illuminated indi cates that the card microprocessor has failed CAN FAIL Yellow Normally OFF When illuminated indicates that the CAN...

Страница 5: ...witch towards the bottom of the board if Zone 1 is configured as a Primary Bell Follower otherwise toggle it to the top of the board for normal operation as shown in Figure 2 S2 Leased Line Select Switches These switches select the zones configured for Leased Line application Toggle each switch to the ON position if the corre sponding zone is configured as Leased Line If the zone is not configured...

Страница 6: ...inal of the CC 2 CC 5 normally connected to non power limited output of the PSC 12 PSX 12 It is important to take into account the source of the voltage during battery calculations P1 P2 P3 P4 Shunt Headers NAC Input Supervision Enable These headers select the NAC input zone supervision If usage application is set for speaker func tion place the shunt jumpers of the corresponding zone between 1 2 ...

Страница 7: ... location where the ZIC 4A is inserted in the CC 5 Base Language Custom Message The message associated with the ZIC 4A card Alternate Language Custom Message The message associated with the ZIC 4A card in an alternate language ZIC Card 24V Power Source Select back plane or screw terminals Each ZIC 4A card is subdivided into four output circuits that can be programmed independently of each other In...

Страница 8: ...to certain usage selections for example MunicipalTie can only be configured as Class B wiring type that are enforced by the Zeus tool during Edit mode or Compile time Refer to the Zeus Quick Start Manual P N 315 033875 or the Zeus self help index for more information WIRING Remove all system power before installation first battery then AC To power up connect the AC first then the battery All field...

Страница 9: ...d to supply the ZIC 4A Refer to the PSC 12 Installation Instructions P N 315 033060 for information when the total system load exceeds 12 amps 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 TO PSC 12 TB4 TO PSC 12 TB4 TO PSC 12 TB4 TO PSX 12 TB4 TO PSX 12 TB4 TO PSC 12 TB4 TO PSC 12 TB4 TO PSC 12 TB4 TO PSX 12 TB4 TO PSX 12 TB4 ONE SLOT OF CC 5 ONE SLOT OF CC 5 ONE SLOT OF...

Страница 10: ... r r u C r e w o P l a n r e t x E w o l e b E T O N e e S t n e r r u C V 4 2 l a n i m r e T w e r c S t n e r r u C e c i v e D l a t o T t n e r r u C e n a l P k c a B V 2 6 0 t n e r r u C y b d n a t S V 4 2 A m 9 8 E T O N A 4 C I Z e h t f o t k C C I Z h c a e f o e p y t g n i r i w d n a e g a s u e h t n o t n e d n e p e d s i t n e r r u c V 4 2 e h T e p y t g n i r i w d n a e g a...

Страница 11: ...vice NFPA 13 and NFPA 2001 Bell Follower Single Channel and Two Channel Audio Single Channel and Two Channel Audio and Strobe Bell Follower Refer to Figure 11 When the ZIC 4A zones are configured as a bell follower it follows a signal that comes from another reverse polarity source The zones can be set as a Bell Follower Primary or Bell Follower Secondary The Bell Follower Primary receives an inpu...

Страница 12: ...ided across all four tones Sync is not provided between ZIC 4A cards 8 For a list of Compatible Notification Appliances refer to P N 315 096363 9 Refer to CAB1 CAB1R P N 315 0330007 and CAB2 BB CAB3 BB P N 315 033009 Installation Instructions for details on the separation of power limited and non power limited wiring 10 Positive or negative ground fault detected at 40K ohms for terminals 1 16 1 2 ...

Страница 13: ...nd non power limited wiring 12 Positive or negative ground fault detected at 40K ohms for terminals 1 16 Figure 8 ZIC 4A Leased Line Wiring 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 ZONE 1 2 INPUT ZONE 3 INPUT ZONE 4 INPUT ONE SLOT OF CC 5 LEASED LINE ZONE 1 LEASED LINE ZONE 3 4 3 2 1 4 3 2 1 LLM 1 NC NC NC NC NC NC NC NC TB1 TB2 4 3 2 1 4 3 2 1 LLM 1 TB1 TB2 4 3 2 1 4 3 2 1 L...

Страница 14: ...ee Note 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 ZONE 1 2 INPUT ZONE 3 INPUT ZONE 4 INPUT ONE SLOT OF CC 5 REL EOL MODULE REL EOL MODULE REL EOL MODULE RELEASING ZONE ZONE 4 NC NC NC NC NC NC NC NC 24K 1 2W 5 24K 1 2W 5 24K 1 2W 5 24K 1 2W 5 Disconnect Switch Supervising Module Disconnect Circuit Disconnect Circuit Disconnect Circuit Disconnect Circuit S D I O N E L O S E ...

Страница 15: ... meet FM Approved installation requirements Refer to PSC 12 Installation Instructions P N 315 033060 for battery calculations FOR FM APPROVED INSTALLATION ONLY Double Interlock A sprinkler system comprised of two interlocks an interlock which opens when Pre action Systems powered by a listed releasing panel and a second interlock which opens when a pressure loss is experienced in the sprinkler pip...

Страница 16: ...llower Primary Input Alarm Current 6mA max Input Voltage 24 VDC nominal No end of line resistor is used Bell Follower Secondary Input Voltage 24 VDC nominal Output Supervision Current 4mA max Output Alarm Current 3A max Output Voltage 24 VDC nominal 4 Bell Follower Primary is not supervised 5 Bell Follower Secondary is supervised for input voltage presence short and open on the output and is power...

Страница 17: ...ification Appliances refer to P N 315 096363 8 Refer to CAB1 CAB1R P N 315 0330007 and CAB2 BB CAB3 BB P N 315 033009 Installation Instructions for details on the separation of power limited and non power limited wiring 9 Verify that P1 P4 are in the proper location for speaker application 10 Positive or negative ground fault detected at 40K ohms for terminals 1 16 Figure 12 ZIC 4A Two Channel Aud...

Страница 18: ...ding codes Wiring for each zone can either be Class A or Class B 2 All output circuits are power limited to NFPA 70 per NEC 760 3 Electrical Ratings Output Zone Supervisory 4mA max Output Zone Active 96 Watts max zone 4 EOL resistor 24k ohms 1 watt 5 P N 140 033771 5 Polarity shown in active state 6 For a list of Compatible Notification Appliances refer to P N 315 096363 7 Refer to CAB1 CAB1R P N ...

Страница 19: ...ng 9 Verify that P1 P4 are in the proper location for speaker application 10 Maximum line resistance is dependent upon the maximum current draw of connected notification appliances when activated The field wiring resistance cannot exceed the maximum line resistance specified for any given NAC current draw SeeTable 11 Zone Usage pair is interchangeable Verify proper wiring 12 Positive or negative g...

Страница 20: ...ower limited wiring 9 Verify that P1 P4 are in the proper location for speaker application 10 Maximum line resistance is dependent upon the maximum current draw of connected notification appliances when activated The field wiring resistance cannot exceed the maximum line resistance specified for any given NAC current draw SeeTable 11 Zone usage pair is interchangeable Verify proper wiring 12 Posit...

Страница 21: ...1 OPTIONAL ABORT OVER RIDES MANUAL RELEASE ELIMINATE G4 CONNECT M TO M FOR DIRECT MANUAL RELEASE NOTE SELECT SELF RESTORING SUPERVISORIES AT THE NODE LEVEL IN ZEUS IF YOU WANT ABORT EVENTS TO SELF RESTORE NOTE THE USE OF ALARM VERIFICATION IS NOT ALLOWED FOR DEVICES IN A CROSS ZONED INITIATING CIRCUIT SUPERVISORY DISPLAY CAT ABORT SWITCH ALARM ALARM ST2 ST1 O O D L1 M M Q E E T T ENABLE ENABLE CAN...

Страница 22: ... needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional ...

Страница 23: ...Siemens Industry Inc Building Technologies Division P N 315 033050 15 23 This page has been left intentionally blank ...

Страница 24: ...ad East Oakville Ontario L6H 0H6 Canada P N 315 033050 15 Siemens Gebäudesicherheit GmbH Co oHG D 80930 München For CE applications in Cerberus E100 systems refer to Installation Instruction A24205 A334 B844 English or A24205 A334 A844 German This page has been left intentionally blank Document ID A6V10239104 ...

Отзывы: