To connect the XTRI to the DPU Programmer/Tester, insert the plug from the DPU cable provided with 
the Programmer/Tester into the opening on the front of the XTRI shown in Figure 2. The plug has no 
polarity and can be inserted into the holes at either direction. 

CAUTION:

 To prevent potential damage to the DPU, DO NOT connect an XTRI to the DPU until all 

connectors of the same polarity are removed from the device line of the XTRI. 

Follow the instructions in the DPU Manual (P/N 315-033260) to program the XTRI to the desired 
address. Record the device address on the address label, which comes with the product, and place it 
on the module or on the XTRI front panel. The XTRI can now be installed and wired to the system. 

 

THERE IS NO 
DIRECTIVITY 
DESIGN FOR DPU
CONNECTION. IT
IS ALLOWED TO 
INSERT THE PLUG
AT EITHER DIRECTION

PLUG FROM 
THE DPU
PROGRAMMER/
TESTER

PROGRAMMING HOLES

SLOT FOR
LOCATING
TAB

 

 

Figure 2 
Connecting the DPU Plug 

 

 

WIRING SWITCHES AND EOL 

 
CAUTION:

 Deactivate P2 circuit by either or both of the following: Using the PMI, bypass the circuit 

being modified, and/or physically disconnect the circuit from the P2 source. 

 

NORMALLY OPEN PROGRAMMABLE SWITCHES

(SEE NOTES 1 AND 2)

NORMALLY CLOSED PROGRAMMABLE SWITCHES

(SEE NOTES 1, 3, AND 4)

END OF LINE
RESISTOR
470 OHMS,
1% 1/2W

END OF LINE
RESISTOR
470 OHMS,
1% 1/2W

 

 

NOTES: 

1. 

There can be any number of normally closed or normally open switches. 

2. 

The end of line resistor must be located at the last switch. 

3. 

Do not wire a normally closed switch across the end of line resistor. 

4. 

Only for use with status applications. 

 

Figure 3 
Wiring Switches 

firealarmresources.com

Содержание XTRI-S

Страница 1: ...to Figures 8 through 13 During the isolator mode the built in dual isolators will work at both sides of the module to isolate the line short in front or behind the module The XTRI modules are available in three models The XTRI S P N S54370 B3 A1 and XTRI R P N S54370 B1 A1 can monitor a normally open or closed dry contact The XTRI S can only monitor and report the status of the contact while the X...

Страница 2: ... wired to the system THERE IS NO DIRECTIVITY DESIGN FOR DPU CONNECTION IT IS ALLOWED TO INSERT THE PLUG AT EITHER DIRECTION PLUG FROM THE DPU PROGRAMMER TESTER PROGRAMMING HOLES SLOT FOR LOCATING TAB Figure 2 Connecting the DPU Plug WIRING SWITCHES AND EOL CAUTION Deactivate P2 circuit by either or both of the following Using the PMI bypass the circuit being modified and or physically disconnect t...

Страница 3: ...ed wire size 18 AWG minimum 14 AWG maximum Wire larger than 14 AWG can damage the connector POWER LIMITED WIRING In compliance with NEC Article 760 all power limited fire protective signaling conductors must be separated a minimum of inch from all of the following items located within an outlet box Electric light Power Class 1 or non power limited fire protective signaling conductors To meet the a...

Страница 4: ... separately from terminals 6 7 and 8 NOTE Minimize the length of wire entering the outlet box WIRING AT THE TERMINAL BLOCKS Power Limited Wiring Refer to Figure 7 Wiring to positions 1 2 3 4 and 5 is power limited Non Power Limited Wiring Wiring to positions 6 7 and 8 is considered non power limited CAUTION Ground shield of device line ONLY at the specified location on the Control Panel Non shield...

Страница 5: ...dition 6 In the device line up to 30 of any compatible devices in polarity insensitive mode with 20 ohms max line resistance can be isolated between two modules in isolator mode in a Class A Style 6 wiring 7 In the device line up to 30 of any compatible devices in polarity insensitive mode with 20 ohms max line resistance can be isolated behind one module in isolator mode in a Class B Style 4 wiri...

Страница 6: ...om control panel or previous addressable device Line Line Line Not used To monitored switches refer to Fig 3 and 4 Figure 11 XTRI D Isolator Mode Wiring 1 5 4 3 2 6 7 8 To monitored switches refer to Fig 3 and 4 Line 1 Line 2 Line 1 Line 2 To next addressable device From control panel or previous addressable device Figure 12 XTRI S Polarity Insensitive Mode Wiring 1 5 4 3 2 6 7 8 To monitored swit...

Страница 7: ...witch position and or an internal relay transfer NOTE Be sure to program the XTRI before fastening the switchplate to the unit Figure 14 Mounting the XTRI S R D ELECTRICAL RATINGS Operating Voltage 13 32 Vdc Max Average Current RMS XTRI S 650µA XTRI D 950µA XTRI R 750µA MODULE STATUS LED Flash Color Condition Flash Intervals Seconds Green Normal Supervisory operation 10 Amber Device is in trouble ...

Страница 8: ...on building technology security and our offerings contact your Siemens sales or project department We strongly recommend customers to follow our security advisories which provide information on the latest security threats patches and other mitigation measures http www siemens com cert en cert security advisories htm FCC Statement WARNING Installation and usage of equipment not in accordance with i...

Отзывы: