ASSEMBLY OF XLS/DESIGO FIRE SAFETY MODULAR/CERBERUS PRO SYSTEM

The three parts of the XLS-MSE3-ADPT are installed separately. The adapter plate is
installed first, followed by the inner door and then the outer door.

Adapter Plate

The XLS-MSE3-ADPT adapter plate has holes in it that fit over the studs in the MSE-3
backbox in only one way.

1.

Place the XLS-MSE3-ADPT over the studs in the backbox and secure it in
place with the hardware provided as shown in Figure 1.

MSE-3

BACKBOX

XLS-MSE3(R)-ADPT

ADAPTER PLATE

“B”

“C”

“C”

“A”

“A” = 6-32 X

“B” =10-32 X 7/16 SCREWS (QTY. 2)

“C” = 6-32 HEX NUTS (QTY. 2)

3/8 SCREWS (QTY. 5)

“A”

“A”

“B”

“D”

GROUND LUG

(THIS LUG IS FOR GROUNDING

THE AC INPUT)

REMOVE GROUND LUG BEFORE

MOUNTING THE PTB.

AFTER INSTALLING THE PTB, BE SURE

TO REINSTALL THE GROUND LUG.

Figure 1

Installing the XLS-MSE3-ADPT Adapter Plate in the MSE-3 Backbox

2.

Install the required CC-5 system cardcage, PSC-12 power supply, and PTB
power termination board after careful consideration of NEC Article 760 for
separation of power limited and non-powered limited wiring. Refer to Figure
2. Use the hardware provided with those modules to mount them to the
adapter plate. Refer to the CC-5 Installation Instructions, P/N 315-033035,
and the PSC-12 Installation Instructions.

3.

One PTB can be mounted on the XLS-MSE3-ADPT on the bottom right of
the plate using the four studs provided. Refer to the PTB Installation
Instructions, P/N 315-034877.  The stud marked “D” in Figure 1 is a lug for
grounding the AC input. Remove the ground lug before mounting the PTB.
After installing the PTB, be sure to reinstall the ground lug.

4.

A battery set of up to 18 AH capacity can be placed in the bottom of the
enclosure.

5.

System cards can be installed in the CC-5 cardcage, as required.

Содержание XLS-MSE3-ADPT

Страница 1: ...3 ADPT The adapter plate installs over the existing studs in an MSE 3 R backbox The inner door has an opening in it for the installation of a FCM2041 U2 U3 operator interface and either one ID MP mounting plate or one ID SP blank plate The inner door is permanently hinged right and is attached to the backbox by screws The XLS MSE3 R ADPT is for indoor use only in dry environments With this convers...

Страница 2: ...E TO REINSTALL THE GROUND LUG Figure 1 Installing the XLS MSE3 ADPT Adapter Plate in the MSE 3 Backbox 2 Install the required CC 5 system cardcage PSC 12 power supply and PTB power termination board after careful consideration of NEC Article 760 for separation of power limited and non powered limited wiring Refer to Figure 2 Use the hardware provided with those modules to mount them to the adapter...

Страница 3: ...e top and bottom holes on the right hand side of the backbox 2 Tighten the screws just a few turns leaving a 1 8 inch gap between the head of the screws and the backbox 3 Slide the inner door into position under the screws 4 Make certain the flange at the left hand top of the inner door is seated in the lip in the backbox Refer to Figure 3 Adjust the door as needed so that it seats securely in the...

Страница 4: ...r u c e S r o o d n i s d u t s n o s t n u o M s t u n 2 3 0 1 o w t h t i w P S D I e h t s a e z i s e m a s e h t t r e s n i k n a l B t e k c a r b e t a l p g n i t n u o m P M D I d e r u c e S r o o d n i s d u t s n o s t n u o M s t u n 2 3 0 1 o w t h t i w XLS MSE3 ADPT INNER DOOR ID SP OR ID MP MOUNTING FCM2041 U2 U3 MOUNTING Figure 4 Inner Door Modules Install the Outer Door The out...

Страница 5: ...limited field wiring the installer must comply with NEC article 760 which states The fire alarm power limited circuits are installed usingTypes FPL FPLR FPLP or permitted substitute cable provided these power limited cable conductors extending beyond the jacket are separated by a minimum of 0 25 in 6 35 mm or by a noncon ductive sleeve or nonconductive barrier from all other conductors If energy l...

Страница 6: ...wer limited wiring Use the existing lances on the adapter plate to dress the wires as needed to main tain separation of power limited and non power limited wiring Install Wiring The primary mains input must have a separate or dedicated circuit breaker Wire in accordance with local codes and Article 760 of NEC 1 Remove the knockouts in the backbox for the entry of field wiring 2 Pull all field wiri...

Страница 7: ...needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...

Страница 8: ...Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada Document ID A6V10328636_en _c P N A5Q00054384 ...

Отзывы: