DISASSEMBLY OF MXL SYSTEM

Remove all system power, first battery and then AC.

1.

Remove and discard the outer door and the hardware used to secure it in
place.

2.

Disconnect and remove the modules from the inner door.

3.

Remove all modules from the backbox, making sure to mark all wires.

4.

Remove the MPS power supply and batteries from the backbox. Save the
mounting hardware for later use.

ASSEMBLY OF XLS/DESIGO FIRE SAFETY MODULAR/CERBERUS PRO MODULAR SYSTEM

The three parts of the XLS-MLE6-ADPT are installed separately. The adapter plate is
installed first, followed by the inner door and then the outer door.

Adapter Plate

The XLS-MLE6-ADPT adapter plate has 18 holes in it that fit over the studs in the
MLE-6 backbox in only one way.

1.

Place the XLS-MLE6-ADPT over the studs in the backbox and secure it in
place with the six #1-4 x 20 hex flange locknuts supplied in the locations
marked “A” shown in Figure 1.

MLE-6

BACKBOX

XLS-MLE6(R)-ADPT

ADAPTER PLATE

“A”

“A”

GROUND LUG

(THIS LUG IS FOR

GROUNDING THE

AC INPUT)

REMOVE GROUND

LUG BEFORE

MOUNTING THE PTB.

AFTER INSTALLING

THE PTB, BE SURE

TO REINSTALL THE

GROUND LUG.

“A”

“A”

“A”

“A”

“B”

“B”

“B”

“B”

“B”

“B”

“B”

“B”

“B”

“B”

“B”

“B”

“C”

“C”

“D”

BATTERY BATTERY

Figure 1

Installing the XLS-MLE6-ADPT Adapter Plate in the MLE-6 Backbox

Содержание XLS-MLE6(R)-ADPT

Страница 1: ...panel is secured to the door with 10 32 nuts The removable panels may be clear OD LP blank OD BP R or vented OD GP R depending on the application The OD BP R and OD GP R panels are red The outer door is attached to the backbox by hinge pins and secured to the backbox by a keyed latch The inner door has three openings in it for the installation of an operator interface and other modules There are e...

Страница 2: ...S MLE6 ADPT are installed separately The adapter plate is installed first followed by the inner door and then the outer door Adapter Plate The XLS MLE6 ADPT adapter plate has 18 holes in it that fit over the studs in the MLE 6 backbox in only one way 1 Place the XLS MLE6 ADPT over the studs in the backbox and secure it in place with the six 1 4 x 20 hex flange locknuts supplied in the locations ma...

Страница 3: ... The stud marked D is a lug for grounding the AC input Remove the ground lug before mounting the PTB After installing the PTB be sure to reinstall the ground lug 5 There is room in the bottom of the enclosure for a battery set of up to 33 AH 6 System cards can be installed in the CC 5 CC 2 cardcage s as required Install the Inner Door Install the inner door by following the steps listed below 1 Pl...

Страница 4: ... as needed for system operation 8 Insert blank plates as needed in unused spaces on door and secure with 10 32 nuts Refer toTable 1 and Figure 3 1 E L B A T S E T A L P R O O D R E N N I L E D O M N O I T P I R C S E D G N I T N U O M P M D I 6 M C F r o f t e k c a r b e t a l p g n i t n u o M M C B d n a 8 M C S 8 M C L d e r u c e S r o o d n i s d u t s n o s t n u o M s t u n 2 3 0 1 o w t h...

Страница 5: ... P N A5Q00075194 on the inside of the outer door 2 E L B A T S E T A L P R O O D R E T U O L E D O M N O I T P I R C S E D G N I T N U O M P L D O e s u r o f e t a l P s n e L r a e l C f o n o i t a c i d n i l a u s i v n e h w d e r i u q e r s i n o i t a r e p o m e t s y s r o o d n i s d u t s n o s t n u o M s t u n 2 3 0 1 t h g i e h t i w d e r u c e S R P B D O n e h w e s u r o f e t...

Страница 6: ... R Figure 4 Outer Door and Plates 4 A ground wire comes installed on the inside of the outer door Refer to Figure 5 Bring the free end of the ground wire through the opening at the top left hand side of the inner door and secure it in place on an unused stud in the backbox with a 10 32 hex nut user supplied ...

Страница 7: ...or and secure with the key latch WIRING In compliance with NEC Article 760 all power limited fire protective signaling conductors must be separated a minimum of inch from all of the following wiring located within a control panel electric light power Class 1 or non power limited fire protective signaling conductors To meet these requirements the following guidelines must be observed when installin...

Страница 8: ...er limited wiring Wiring must be in the shortest route and must not overlap any other wiring Power Limited Wiring Wiring entering the enclosure from the top and the left side of the backbox is considered power limited Wiring must be in the shortest route and must not overlap any other wiring Use the existing lances in the backbox to dress the wires as needed to maintain separation of power limited...

Страница 9: ...needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...

Страница 10: ...Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada Document ID A6V10328630_en _b ...

Отзывы: