Views
3
7 | 14
Building Technologies
A6V10315050_e_en_--
Siemens Industry, Inc.
2016-10-27
3 Views
Figure 2: Printed circuit board view for XCI2001
Element
Des.
Function
Connector
X1
Plug for periphery board connection
X2
Service plug for programmed connection (not used)
X4
Diagnostic service plug (not used)
X5
Releasing relay outputs
Adjustment elements
S1*
Switch: Arm/Disarm releasing output 1
S2*
Switch: Arm/Disarm releasing output 2
S3
Reset key
X3
Jumper for degraded mode enable
LEDs
H1
Display: Releasing output 1 status ON/OFF
H2
Display: Releasing output 2 status ON/OFF
H3
Flashing: Releasing module is active
* For Class A wiring, both S1 and S2 must be in the same position at all times when
used to disarm or arm the circuit.
K2
K1
1
1
3
1
1
1
X3
X4
S1
X5
X1
H1
H2
H3
S3
X2
S2