XCI2001-U1Releasing module
MountingInstallation
A6V10315050_e_en_--
Building Technologies
2016-10-27
Siemens Industry, Inc.
Страница 1: ...XCI2001 U1 Releasing module Mounting Installation A6V10315050_e_en_ Building Technologies 2016 10 27 Siemens Industry Inc ...
Страница 2: ...on of its contents and communication thereof to others without express authorization are prohibited Offenders will be held liable for payment of damages All rights created by patent grant or registration of a utility model or design patent are reserved Issued by Siemens Industry Inc Building Technologies Division 8 Fernwood Road Florham Park NJ 07932 Tel 1 973 593 2600 www sbt siemens com FIS Edit...
Страница 3: ...Inc 2016 10 27 Table of contents 1 Description 5 2 Mounting 6 3 Views 7 4 Pin assignments for releasing module 8 4 1 X5 plug connection for releasing relay output 8 5 Indicators 10 6 Adjusting elements for releasing module 11 7 Technical data 12 8 FCC Statement 13 ...
Страница 4: ...Building Technologies A6V10315050_e_en_ Siemens Industry Inc 2016 10 27 4 14 ...
Страница 5: ...ing valves in releasing and sprinkler systems Activation can be event controlled or performed manually The releasing module is mounted on the periphery board Properties Automatic or manual activation Dual channel control Supervision of releasing circuit wiring as class A or class B circuit Supports several valve systems Suited to indoor applications not wet rooms ...
Страница 6: ...he releasing module on the periphery board 1 Periphery board 250p or periphery board 500p 2 Threaded standoffs on back box 3 Releasing module XCI2001 4 2x fixing screw X901 Slot in periphery board X5 Connection terminal on releasing module 1 Plug the releasing module 3 into slot X901 on the periphery board 2 Fasten the releasing module to the threaded standoffs 2 in the back box using the two fixi...
Страница 7: ...plug not used X5 Releasing relay outputs Adjustment elements S1 Switch Arm Disarm releasing output 1 S2 Switch Arm Disarm releasing output 2 S3 Reset key X3 Jumper for degraded mode enable LEDs H1 Display Releasing output 1 status ON OFF H2 Display Releasing output 2 status ON OFF H3 Flashing Releasing module is active For Class A wiring both S1 and S2 must be in the same position at all times whe...
Страница 8: ...ut Pin Designation Description 4 REL_CIR1 Relay output for releasing 1 3 REL_CIR1 Relay output for releasing 1 2 REL_CIR2 Relay output for releasing 2 1 REL_CIR2 Relay output for releasing 2 Admissible cable cross section 12 18 AWG unshielded XCI2001 U1 supports two Class B circuits or one Class A circuit as shown below Class B wiring Figure 3 Class B wiring X5 4 3 2 1 REL_CIR1 REL_CIR1 REL_CIR2 R...
Страница 9: ...Class A wiring Note 1 Loop wires must be terminated directly onto the SOLENOID Note 2 Loop wires must be terminated directly onto the SOLENOID REL EOL Terminating resistor 24 kΩ and diode Siemens part number 500 696359 The maximum length of line of the relay connections is limited to a resistance of 3 5 Ω X5 4 3 2 1 REL_CIR1 REL_CIR1 REL_CIR2 REL_CIR2 REL EOL SOLENOID x x Note 1 Note 2 ...
Страница 10: ... Status of releasing circuit 1 Off Releasing circuit 1 inactive On Releasing circuit 1 activated H2 Green Status of releasing circuit 2 Off Releasing circuit 2 inactive On Releasing circuit 2 activated H3 Green Status of processor Off steady Processor is not running Flashing Processor is running On steady Processor is not running Not applicable for Class A wiring ...
Страница 11: ...2 armed normal S1 and S2 control output The outputs are disarmed in the OFF position The relays are disarmed but are still supervised The outputs are armed in the ON position For Class A wiring both S1 and S2 must be in the same position at all times when used to disarm or arm the circuit S3 reset key for releasing module Button Function Position Meaning S3 RESET Pressed The module is reset Jumper...
Страница 12: ...tage DC 24 V Special Application Output current 2 0 A per output channel Connection terminals Design Screw terminals Admissible cable cross section 12AWG 18AWG not shielded Relay outputs Maximum line resistance 3 5 Ω Preaction deluge Maximum line resistance 2 5 Ω Minimum voltage at the coil DC 20 4 V Mechanical data Dimensions W x H 3 25 x 4 75 8 25 x 12 05 cm Weight Approx 3 2 oz 90 g ...
Страница 13: ...can radiate radio frequency energy and if not installed and used in accordance with the instructions manual may cause interference to radio communications It has been tested and found to comply with the limits for a Class A computing device pursuant to Part 15 of FCC Rules which are designed to provide reasonable protection against such interference when operated in a commercial environment Operat...