Building Technologies 

Network Node WTT16…, WTX16… 

CE1N2874en 

HVAC Products 

 

14.07.2005 

The display of the WT…16… facilitates commissioning work and troubleshooting. In 
addition to the standard display that shows the operating mode of the WTT16, there are 
5 different display levels from “A“ to “E“ that can be selected by the user. 

Display level 

 

 

Current operating mode 

 

 

WT…16 number (primary address) and network 
number alternate 

 

Number of WT…16 on the network 

 

Number of consumption meters on the network 

 

Remaining capacity of the WTT16’s main battery 
in % 

 

Error code (3 groups) 

 
There is a total of 6 operating modes some of which can be selected by pressing the 
button on the network node, some are selected automatically, or from a connected PC 
via the ACT26 commissioning software. The selected operating mode appears on the 
display: 

Operating mode 

Display 

Explanation 

Standard mode 

 

This is the normal operating mode of the data 
collectors: Telegrams from the metering de-
vices are received, stored and further handled 
by the network 

Extended  
standard mode

1)

 

M

 

The receiver is always active to ensure fast 
communication. This mode is automatically 
activated in the case of mains-powered opera-
tion (WTX16…). It can also be started manually 
with the ACT26 service tool 

Installation mo-
de

2)

 

 

In installation mode, the radio network will be 
configured automatically. Metering devices that 
transmit installation telegrams in this operating 
mode are registered on the network 

Extended instal-
lation mode

2)

 

M

 

Same as installation mode, except that in addi-
tion to installation telegrams, data telegrams 
are accepted also. This mode is practical when 
the network is installed at a later stage 

Search mode 

 

Metering devices that have been lost are syn-
chronized again (this mode is activated  
automatically) 

Extended search 
mode

2)

 

M

 

Same as resynchronization mode. It must be 
started manually with the ACT26 service tool 
and searches for lost or manually entered me-
tering devices 

1) 

In battery powered network nodes this mode is terminated automatically after eight hours. 

2) 

This mode is terminated automatically after eight hours.

 

Display 

Operating modes 

Содержание WTT16 Series

Страница 1: ...nent of the Siemeca system It has been designed for use in buildings to create a radio network for receiving and storing the data transmitted by the consumption meters installed in the building Communication between several network nodes is via radio also so that no wiring is required All meas ured values acquired by the consumption meters are continuously exchanged within the network which means ...

Страница 2: ... system must not be ex ceeded The network nodes with gateway and integrated M Bus master WTX16 GSM and WTX16 IP are able to read M Bus meters according to EN1434 3 Technical design The network node consists of the following subassemblies transceiver for Siemeca network memory for 500 meters M Bus Slave RS232 optional backup battery power supply mains supply WTX16 battery WTT16 Receiver and transmi...

Страница 3: ...ton for switching the display blue 8 Reset button recessed 9 Display 10 Connector not for the user 11 Firmware memory covered up The wall mounted section of the network nodes WTT16 contains only the main battery The wall mounted section of the network nodes WTX16 and WTX16 232 contains the power pack and possibly an additional RS232 interface GND n c RTS CTS Rx Tx 4 2 7 3 5 6 1 1 Mains connection ...

Страница 4: ...ing de vices are received stored and further handled by the network Extended standard mode1 M The receiver is always active to ensure fast communication This mode is automatically activated in the case of mains powered opera tion WTX16 It can also be started manually with the ACT26 service tool Installation mo de2 In installation mode the radio network will be configured automatically Metering dev...

Страница 5: ...onal interface s CAUTION connect the mains cable to the power supply unit only 1 2 3 1 Mains connection L and N 2 Preinstalled mains cable no flexible power cable 3 Extra insulation shrink sleeve Connect the AC 230 V power supply line to the power pack of the WTX16 in the following order Remove the upper housing section of the WTX16 from the base For that purpose remove the 2 cable connections pow...

Страница 6: ...aintained Staff dealing with the product must be familiar with all potential hazards and mainte nance measures in accordance with the instructions given in this document Non observance of these warning notes can lead to personal injury or damage to property Ensure that the local regulations for radio transmission installations and electrical instal lations are complied with Pursuant to the Verordn...

Страница 7: ...similar behavior in other modes too The main battery used by the WTT16 requires careful treatment Do not short circuit or damage the battery Do not expose the battery to excessive heat Return exhausted batteries to the supplier Read the enclosed safety instructions carefully M Bus connection Any network node can be connected to the M Bus temporarily service connector or continuously screw terminal...

Страница 8: ...ions in mm WTX16 WTT16 The information provided in this Data Sheet only gives general descriptions and general technical features which in the case of specific applications may not necessarily apply or which may change due to further development of the product Technical features are binding only when expressly agreed upon at the time a contract is concluded 2002 Siemens Building Technologies AG Su...

Отзывы: