2
1
P1
P2
Immersion
depth > 50 %,
< 99 %
4
3
right
wrong
a
b
EN
Siemens Building Technologies
A6V10816676_----_d 97
Installing temperature sensors
Installation set temperature sensor directly immersed
There is an installation set included for meters with 5.2 × 45 mm temperature
sensors This can be used to t the sensor directl immersed in the ball valve
Carry out steps 1–4 with the position P1 shown for the
temperature sensor (TF) in the half-shell
scre tting
(1) Insert the temperature sensor in the
hal shell scre tting enclosed
it the second hal o the scre tting
in such a way that the locking pin of the
one hal ts into the recesses o the other
half.
(3) Position the O-ring at the instal-
lation point in the ball valve.
Use the genuine O-ring
from the kit enclosed.
(4) Push in the TF and use a tightening
torque of approx. 3 Nm (hand-tight) to
tighten the scre tting
Check for correct TF installation:
a Collars o the hal shell scre tting are
ush to the ball valve
b Shells o the scre tting are ush to
one another
If TF installation has not been successful,
the TF must be removed from the ball valve
again.
Then carry out steps 1-4 with the position P2 shown for the temperature
sensor T in the hal shell scre tting
The temperature sensor
must not touch the base
of the ball valve.