VNT Mounting

Refer to Figure 2.
The VNT mounts at the top of the VNT mounting plate with the four hex nuts provided.

1.

Place the VNT over the four studs on the VNT-MP.

2.

Place the four hex nuts supplied over the studs and tighten them to secure
the VNT to the VNT-MP.

VNT

STUDS (4) FOR

MOUNTING VNT

VNT-MP

FIBER SWITCH

MOUNTING RAIL

XND BRACKET

Figure 2

Mounting the VNT to the VNT-MP

WIRING

Wiring for the VNT-Building Configuration is shown in Figure 3. Wiring for the VNT-Fire
Command Center is shown in Figure 4.

All connections are supervised and power limited unless otherwise stated.

ELECTRICAL RATINGS

For power, the VNT may only be connected to the VNT-PS (P/N 500-450491).

Input Voltage:   Regulated 24VDC
Input Current:  1.7A @ 24VDC max.

Содержание VNT

Страница 1: ...system 100BaseTTCP IP connection to a local Fiber Ring Switch This connection transports the network signals HNET and XNET audio supervision and monitoring data streams One or more independent HNET RS485 interfaces to the module network of an XLS Desigo Fire Safety Modular Cerberus PRO Modular or its components An XNET RS485 interface to the XLS Desigo Fire Safety Modular Cerberus PRO Modular node...

Страница 2: ...hem to secure the VNT to the VNT MP VNT STUDS 4 FOR MOUNTING VNT VNT MP FIBER SWITCH MOUNTING RAIL XND BRACKET Figure 2 Mounting the VNT to the VNT MP WIRING Wiring for the VNT Building Configuration is shown in Figure 3 Wiring for the VNT Fire Command Center is shown in Figure 4 All connections are supervised and power limited unless otherwise stated ELECTRICAL RATINGS For power the VNT may only ...

Страница 3: ...ologies Division P N 315 050490 3 3 FIRE SYSTEM TO P5 1 1 19 1 1 _ _ _ 2 2 H N GND 6 24 12 18 7 13 1 2 3 4 TB1 TB2 BATTERY P9 P12 TB3 TB4 P4 OFF O ON P10 HNET CAN 1 2 3 4 5 1 2 3 4 5 P3 1 2 E5 Figure 3 Connection Diagram for VNT Building ...

Страница 4: ... 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 LCM 8 OR SCM 8 LCM 8 OR SCM 8 LCM 8 OR SCM 8 LCM 8 OR SCM 8 LCM 8 OR SCM 8 LCM 8 OR SCM 8 LCM 8 OR SCM 8 LCM 8 OR SCM 8 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 Buzzer 12345678 12345678 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 ...

Страница 5: ...eeds Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional in...

Страница 6: ...Siemens Industry Inc Building Technologies Division P N 315 050490 3 6 THIS PAGE HAS BEEN LEFT INTENTIONALLY BLANK ...

Страница 7: ...Siemens Industry Inc Building Technologies Division P N 315 050490 3 7 THIS PAGE HAS BEEN LEFT INTENTIONALLY BLANK ...

Страница 8: ...Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada P N 315 050490 3 Document ID A6V10316286 ...

Отзывы: