Ordering
information
Gas valves and actuators are ordered separately. For additional SKPxx.xxxUx actuator
information, see the following technical instructions:
SKP15.xxxUx 155-751P25
SKP25.xxxUx 155-752P25
SKP55.xxxUx 155-753P25
SKP75.xxxUx 155-754P25
NOTE:
The SKPxx.xxxUx actuators have an operating temperature range of 14 °F to
140 °F (-10 °C to 60 °C)!
Table 2. Product numbers
Product number
Size
NPT
Maximum
operating
pressure
psi
Close-off
pressure
psi
Capacity CFH
Natural gas at
P = 1
"
W.C.
Number of test
points, 1/4
"
NPT
Valve body
material
Inlet
Outlet
VGG10.154U
½"
20
75
327 / 242*
2
2
Aluminum
VGG10.204U
¾"
20
75
614 / 442*
2
2
Aluminum
VGG10.254U
1" 20 75 914
/
686* 2 2 Aluminum
VGG10.404U
1 ½"
20
75
2,047 / 1,643*
2
2
Aluminum
VGG10.504U
2" 20 75
3,511
2 2 Aluminum
VGG10.654U
2
½"
10
25 5,085 1
1
Cast
iron
VGG10.804U
3" 10 25
6,158
1 1 Cast
iron
* VGG10.xxxU valves, ½-through 1 ½-inch have reduced flow when used with AGA66 (NEMA 4 kit).
Capacities shown are with/without NEMA 4 kit
Accessories
Part Number
Description
AGA61
Manual adjusting throttle attachment AGA61 permits VGG10.xxxU series valves to be used as
adjustable limiting orifice valves. Once adjusted, the AGA61 has a provision to be sealed from
tampering.
AGA66
Sealing gasket to provide NEMA 3, NEMA 3R, and NEMA 4 protection.
- Gasket kit
to mount between actuator SKPxx.xxxUx and valve VGG10.xxxU
- Degree of protection increased from IP54 to IP65
- Refer to Mounting Instruction M7643.2 (74 319 0421 0)