4/21
Building Technologies Division
CC1N7696en
20.04.2016
Life cycle
LDU11... has a designed lifetime* of 250,000 burner startup cycles which, under normal
operating conditions in heating mode, correspond to approx. 10 years of usage (starting
from the production date given on the type field). This lifetime is based on the endurance
tests specified in standard EN298 and the table containing the relevant test documenta-
tion as published by the European Association of Component Manufacturers (Afecor)
(www.afecor.org).
The designed lifetime is based on use of the LDU11... according to the manufacturer’s
Data Sheet. After reaching the designed lifetime in terms of the number of burner startup
cycles, or the respective time of usage, the LDU11... is to be replaced by authorized
personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery
Disposal notes
The unit contains electric and electronic components and must not be disposed of to-
gether with domestic waste. Local and currently valid legislation must be complied with.