5
Siemens
CE1N4213en
Smart Infrastructure
2020-02-20
Operating pressure and operating temperature
Liquids:
Operating pressure and medium temperature per IS0 7005
(Observe all local and applicable laws).
Type summary
Type
DN
k
vs
Shutoff ball valve 2-port
3-port changeover valve (L)
3-port changeover valve (T)
[m
3
/h]
–
VBI60.15-5L
-
15
5
–
–
VBI60.15-12T
12
1)
VAI60.15-15
–
–
15
–
VBI60.20-9L
–
20
9
–
–
VBI60.20-16T
16
1)
VAI60.20-22
–
–
22
–
VBI60.25-9L
–
25
9
–
–
VBI60.25-16T
16
1)
VAI60.25-22
–
–
22
–
VBI60.32-13L
–
32
13
–
–
VBI60.32-25T
25
1)
VAI60.32-35
–
–
35
–
VBI60.40-25L
–
40
25
–
–
VBI60.40-49T
49
1)
VAI60.40-68
–
–
68
–
VBI60.50-37L
–
50
37
–
–
VBI60.50-73T
73
1)
VAI60.50-96
–
–
96
1)
k
vs
Bypass B > 50 % of k
vs
A ─ AB
DN
=
Nominal size
k
vs
=
Flow nominal value for chilled water (5…30 °C) through a fully opened ball valve at a
differential pressure of 100 kPa (1 bar)