background image

instabus EIB

 

Technical Product Information 

April 2006 

Touch panel UP 588 

5WG1 588-2AB01  

Touch panel UP 588/11 

5WG1 588-2AB11 

Touch panel UP 588/21 

5WG1 588-2AB21 

Accessories: Design frame, anodised aluminium 

5WG1 588-8AB01 

Technical Manual 

UP 588, 6 pages 

Siemens AG 

 

 

Automation and Drives Group 

Update: http://www.siemens.de/gamma 

©

 Siemens AG 2006 

Electrical Installation Technology 

 

Subject to change without prior notice 

P.O.Box 10 09 53, D-93009 Regensburg 

2.3.1.4/4

 

 

 

 
B1 Flush-type 

box 

B2  Opening for power supply cable 
B3  Opening for bus cable 
B4 Touch 

panel 

B5 Fixing 

screws 

B6  Design frame  
B7 All-purpose 

cover 

 
Connecting the bus cable (Diagram 3 “A”) 

 

The bus terminal (C3) is suitable for solid conduc-
tors with 0.6 ... 0.8mm Ø. 

 

Remove approx. 3 cm of the insulation of the bus 
cables. 

 

Strip approx. 5mm of insulation from the conduc-
tors (C3.4) and place in the terminal (C3) (red = +, 
grey = -). 

 
Clipping on the bus terminal 

 

Place the bus terminal in the guide slot and press 
the terminal (C3) downwards until it reaches the 
stop. 

 

C3

 

C3.1

 

C3.3

 

C3.2

 

5 mm

 

C3

 

C3.4

 

C3

 

C3.4

 

"A"

 

C4.1

"B"

 

6....7mm

 

C4.2

C4

 

 

 

Diagram 4: Connections 

 
 
Connecting the power supply terminal (Diagram 3 “B”) 

 

Strip 6...7mm of insulation from the conductors 
(C4.1), clip on the power supply terminals (C4) and 
tighten the screws (C4.2).  

 
Terminal assignment:  
 230V 

24V 

1   

 

    Earth  

In1:     +/- DC: AC 

2  N 

 

  Neutral conductor 

not connected 

3  L    Phase 

In2:     +/- DC: AC 

 

After connecting the bus terminal and the power supply 
terminal to the cables, the terminals are inserted in the 
corresponding openings on the touch panel. Once the 
bus voltage has been applied, the learning button can 
be pressed and the physical device address can be pro-
grammed. The LED should be extinguished when the 
physical address has been programmed.  
The device is then screwed into the box using the four 
screws supplied (see Diagram 2). 
The protective foil that is attached to the surface of the 
display may now be removed. No sharp objects or tools 
should be used to do so. 
After screwing the device into position and removing 
the protective foil, the required design cover can be 
inserted in the display frame. Finally, the all-purpose 
cover is placed onto the display and latched in place, 
thereby holding the design cover in position. 
 

Caution:

 

Do not exert direct pressure on the display!  
There is a risk of the glass breaking! 

Once the installation is completed, the power supply 
voltage can be connected to the supply and the device 
can be put into operation (see the application program 
description for information about programming). 
 
 

Dismantling 

 

-

 

First disconnect the power supply voltage from the 
supply. 

-

 

The all-purpose cover must first be removed when 
dismantling the device or replacing the design 
frame. The cover can be released at the openings 
provided (D1) at the bottom using the dismantling 
tool provided or a plastic screwdriver.  

Caution:

 

When releasing the cover, only slight pres-
sure may be exerted on the display. Do not 
damage the surface of the display with the 
dismantling tool! 

 

Содержание UP 588

Страница 1: ...an alarm page with 4 alarm signals and 2 text messages as well as the execution of time controlled tasks The following accessories are required for the touch panel Design frame aluminium 5WG1 588 8AB01 Application Programs 01 07 Touch Panel vision 802103 display and operation of up to 70 EIB standard functions on 7 display pages display of an alarm page with 4 alarm signals and 2 text messages exe...

Страница 2: ...l display with graphic capability and backlighting Connections Bus line EIB bus terminal screwless 0 6 0 8mm solid insulation strip length 5mm Power supply Insulation strip length 6 7mm The following conductors conductor cross sections are permitted 0 5 2 5mm2 solid 0 5 1 5mm2 finely stranded Mechanical data Housing plastic Dimensions WxHxD 190 x 156 x 58mm Mounting depth in flush type box 52mm In...

Страница 3: ...is inserted in the corre sponding terminal locator on the right hand side of the housing The learning button and the programming LED are located on the left next to the module slot for the bus terminal The terminal for the power supply is on the left hand side of the device The terminal must be withdrawn in order to connect the power supply cables A6 A6 for adjusting the contrast The contrast of t...

Страница 4: ... the bus terminal and the power supply terminal to the cables the terminals are inserted in the corresponding openings on the touch panel Once the bus voltage has been applied the learning button can be pressed and the physical device address can be pro grammed The LED should be extinguished when the physical address has been programmed The device is then screwed into the box using the four screws...

Страница 5: ... and C3 3 each with four terminal contacts Care should be taken not to damage the two test sockets C3 1 either by accidentally connecting them to the bus conductor or with the screwdriver when trying to remove the bus terminal Carefully insert the screwdriver in the wire entry slot of the grey section of the bus terminal C3 3 and pull the bus terminal C3 out of the built in device When the red sec...

Страница 6: ...anel UP 588 21 5WG1 588 2AB21 Accessories Design frame anodised aluminium 5WG1 588 8AB01 Technical Manual UP 588 6 pages Siemens AG Automation and Drives Group Update http www siemens de gamma Siemens AG 2006 Electrical Installation Technology Subject to change without prior notice P O Box 10 09 53 D 93009 Regensburg 2 3 1 4 6 Notes ...

Отзывы: