Technical product information 

February 2012 

UP 258D11 OPTISENS OFFICE Presence detector / motion detector with lighting control 

5WG1 258 2DB11 

  

Technical manual 

UP 258D11, 8 pages 

Siemens AG  

 

 

Infrastructure & Cities Sector, Building Technologies 

Update: http://www.siemens.com/gamma 

© Siemens AG 2012 

Control Products and Systems 

 

Subject to change without further notice 

P.O. Box 10 09 53, D 93009 Regensburg 

2.13.1.6/4 

A1 

A2 

A3 

A4  A5

A6 

A7 

A8 

A10 

A11 

A9 

 

Fire load: approx. 2480 kJ  

 

Installation: in flush mounting box, ceiling opening, or 
in surface mounting box (see accessories) 

 

Electrical safety 

 

Degree of pollution (according to IEC 60664 1): 2 

 

Type of protection (according to EN 60529): IP 20 

 

Overvoltage category (according to IEC 60664 1): III 

 

Bus: safety extra low voltage SELV DC 24 V 

 

Device complies with: EN 60669 2 1 

 

EMC requirements 

 

Complies with EN 50428 

 

Environmental conditions 

 

Climatic withstand capability: EN 50090 2 2 

 

Ambient operating temperature:   5 ... + 45 

°

 

Storage temperature:   20 ... + 70 

°

 

Relative humidity (not condensing): 5 % to 93 % 

 

Reliability 

 

Failure rate:  410 fit at 40

°

 

Markings 

 

KNX 

EIB

  

 

CE mark 

 

In accordance with the EMC guideline (residential and 
functional buildings), low voltage guideline 

 

 
 
Accessories 

IR   remote control 

5WG1 255 – 7AB11 

AP   housing 

 

5WG1 258 – 7EB01 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Location and function of the display and  
operating elements  

 

 

                               

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
    
 
 

 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Figure 2: Display and operating elements 
 
A1  UP 258D device 
A2  Fixing clamps 
A3  adjustable sensor head 
A4  PIR   sensor 
A5  Brightness sensor 
A6  IR receiver for remote controls 
A7  LED (red) and programming key 
A8  Shade 
A9  Design cover 
A10  Bus terminal 
A11  Barcode label with KNX serial number and supplier  
 

   code 

 
 
 
 
 

Содержание UP 258D11 OPTISENS OFFICE

Страница 1: ...ach functional block motion detector presence detector HVAC detector via corresponding parameters Each time a presence is detected the overshoot time is started Its duration is separately configurable for each functional block The end of presence is determined by the end of the overshoot time The duration of the dead time is also configurable per functional block It is used to protect the actuator...

Страница 2: ... to control other devices The IR decoder can be controlled only with one of the Siemens IR remote controls shown in figure 1 The re mote controls have a range of 5 meters maximum The IR decoder cannot distinguish between remote con trols The functionality of button pairs A to F see dia gram in figure 1 will be configured via the ETS Figure 1 IR remote control units for UP 258D11 Commissioning Fact...

Страница 3: ... Engineering Tool Software ETS version 3 0 f is required to load the application program Installation notes V V V V DANGER The device must be mounted and commissioned by an authorized electrician When connecting the device it should be ensured that the device can be isolated The device must not be opened For planning and construction of electric installations the relevant guidelines regulations an...

Страница 4: ...ording to IEC 60664 1 III Bus safety extra low voltage SELV DC 24 V Device complies with EN 60669 2 1 EMC requirements Complies with EN 50428 Environmental conditions Climatic withstand capability EN 50090 2 2 Ambient operating temperature 5 45 C Storage temperature 20 70 C Relative humidity not condensing 5 to 93 Reliability Failure rate 410 fit at 40 C Markings KNX EIB CE mark In accordance with...

Страница 5: ...g Basics The PIR sensor reacts to temperature differences The lower the temperature difference between the ambient temperature and the moving object the less sensitive the analysis In other words moving objects will not then be detected as efficiently and the catch ment area is restricted Note There must be an unobstructed line of sight to the person in the catchment area People behind walls etc i...

Страница 6: ...ews E1 UP 258D device E2 Socket fixing screws E3 UP socket Depth min 40 mm 60 mm E4 Additional fixing holes offset by 90 Mounting the fixing clamps for mounting the device in suspended ceilings Extend the fixing claws slightly and push over the lugs on the UP 258D Figure 6 Mounting the fixing clamps for mounting the device in suspended ceilings G1 UP 258D device G2 Fixing clamp Installation in sus...

Страница 7: ... protec tion for the tilting sensor head It can be removed before mounting the detector Separate the snaplock hooks on the shade with a screw driver and fold the shade down If you want to constrain the detection area you can cut out the shade The shade can be clipped back on if need after mounting the detector Figure 9 Mounting Dismounting the shade K1 UP 258D device K2 Shade K3 Screwdriver Cuttin...

Страница 8: ... Ac cordingly be gentle while working Figure 12 Dismounting the design cover N1 UP 258D device N2 Design cover N3 Screwdriver caution Dimension drawing Dimensions in mm General notes The operating instructions must be handed over to the client Any faulty device is to be sent together with a return delivery note of the local Siemens office If you have further questions concerning the product please...

Отзывы: