background image

 

GAMMA 

instabus

 

Technical product information 

February 2012 

UP 258D11 OPTISENS OFFICE Presence detector / motion detector with lighting control 

5WG1 258 2DB11 

 

 

Siemens AG 

UP 258D11, 8 pages 

Technical manual 

Infrastructure & Cities Sector, Building Technologies 
Control Products and Systems 

© Siemens AG 2012 

Update: http://www.siemens.com/gamma 

P.O. Box 10 09 53, D 93009 Regensburg 

Subject to change without further notice 

 

 

2.13.1.6/1 

Product and functional description 

 

 

 
The UP 258D11 is a presence/motion detector with inte
grated 2 point light control. The UP 258D11 device com
municates  via  KNX/EIB  with  actuators  or  other  KNX  de
vices.  It is designed  for mounting  on  the  ceiling.  Owing 
to its tilting sensor head, the UP 258D11 can be aligned 
with the required capture area. The main application for 
the  device  is  automatic  lighting  control  in  an  office 
workplace. 
The  UP 258D11  senses  the  presence of  a person  or that 
there  is  no  longer  anyone  in  its  detection  area.  The  de
tector signal can be analyzed via two separate communi
cation  channels,  termed  motion  detector  and  presence 
detector. 
Additionally, the UP 258D11 provides an output for con
trol of HVAC applications. For example, this function can 
switch systems that are used for heating, ventilating and 
air conditioning  control  (HVAC)  of  the  room  from  “En
ergy saving mode” in an unused room to “Comfort mode” 
in  an  occupied  room  and  back  to  “Energy  saving  mode” 
when the room is again unoccupied. 
For  each  detector  function  block  (presence,  motion, 
HVAC) 4 communication objects are available, in total 12 
different communication objects. Depending on configu
ration, one or two KNX telegrams are sent onto the bus 
when  motion  is  first  detected  and  when,  after  the  last 
motion  was  detected,  an  overshoot  time  has  expired. 
The values of the communication objects are configured 
for  each  functional  block  (motion  detector,  presence 
detector, HVAC detector) via corresponding parameters. 

Each time a presence is detected, the overshoot time is 
started. Its duration is separately configurable for each 
functional block. The end of presence is determined by 
the end of the overshoot time. 
The duration of the dead time is also configurable per 
functional block. It is used to protect the actuators that 
are connected to the detector. If a presence is detected 
during the dead time, neither telegrams are sent nor the 
overshoot time is started. 
In the following the telegrams, which are sent at the 
beginning of a presence, are called 

and 

B

, the tele

grams, which are sent at the end of a presence, are 
called 

C

 and 

D

 

Operating Sequence 

After the device has detected a presence, telegram 

A

 is 

sent immediately. If it has been configured to send also a 
telegram 

B

, then telegram 

B

 is sent after the configured 

time (optionally also cyclically). 
If there are no motions any more, at the end of the over
shoot time telegram 

C

 and (if configured) telegram 

D

 are 

sent. Telegram 

D

 can also be sent cyclically. 

If there are motions while the overshoot time is running, 
the overshoot time is restarted. 
 
Flowchart: 

motion 

bus telegrams 

 

dead time 

overshoot time 

 

 

Use as single device or as main detector (master), 
respectively secondary detector (slave) 

The detector can be operated as an independent device, 
as the main or secondary detector. 
According to the requirement, additional presence detec
tors  can  be  connected  with  the  “main  detector”  via 
KNX/EIB as “secondary detectors” to extend the presence 
detection  zone.  “Secondary  detectors”  supply  motion 
information only to the main detector. 
 

Brightness measuring – adjustable via KNX/EIB 

The  UP  258D11  contains  an  independent  light  sensor. 
The  signal  measured  there  is  available  both  at  the 
KNX/EIB and internally. 
Because  the  light  sensor  measures  directly,  it  must  be 
possible to calibrate it for indirect measurement, so that 
it can be adapted to the different installation sites. Rapid 

Содержание UP 258D11 OPTISENS OFFICE

Страница 1: ...ach functional block motion detector presence detector HVAC detector via corresponding parameters Each time a presence is detected the overshoot time is started Its duration is separately configurable for each functional block The end of presence is determined by the end of the overshoot time The duration of the dead time is also configurable per functional block It is used to protect the actuator...

Страница 2: ... to control other devices The IR decoder can be controlled only with one of the Siemens IR remote controls shown in figure 1 The re mote controls have a range of 5 meters maximum The IR decoder cannot distinguish between remote con trols The functionality of button pairs A to F see dia gram in figure 1 will be configured via the ETS Figure 1 IR remote control units for UP 258D11 Commissioning Fact...

Страница 3: ... Engineering Tool Software ETS version 3 0 f is required to load the application program Installation notes V V V V DANGER The device must be mounted and commissioned by an authorized electrician When connecting the device it should be ensured that the device can be isolated The device must not be opened For planning and construction of electric installations the relevant guidelines regulations an...

Страница 4: ...ording to IEC 60664 1 III Bus safety extra low voltage SELV DC 24 V Device complies with EN 60669 2 1 EMC requirements Complies with EN 50428 Environmental conditions Climatic withstand capability EN 50090 2 2 Ambient operating temperature 5 45 C Storage temperature 20 70 C Relative humidity not condensing 5 to 93 Reliability Failure rate 410 fit at 40 C Markings KNX EIB CE mark In accordance with...

Страница 5: ...g Basics The PIR sensor reacts to temperature differences The lower the temperature difference between the ambient temperature and the moving object the less sensitive the analysis In other words moving objects will not then be detected as efficiently and the catch ment area is restricted Note There must be an unobstructed line of sight to the person in the catchment area People behind walls etc i...

Страница 6: ...ews E1 UP 258D device E2 Socket fixing screws E3 UP socket Depth min 40 mm 60 mm E4 Additional fixing holes offset by 90 Mounting the fixing clamps for mounting the device in suspended ceilings Extend the fixing claws slightly and push over the lugs on the UP 258D Figure 6 Mounting the fixing clamps for mounting the device in suspended ceilings G1 UP 258D device G2 Fixing clamp Installation in sus...

Страница 7: ... protec tion for the tilting sensor head It can be removed before mounting the detector Separate the snaplock hooks on the shade with a screw driver and fold the shade down If you want to constrain the detection area you can cut out the shade The shade can be clipped back on if need after mounting the detector Figure 9 Mounting Dismounting the shade K1 UP 258D device K2 Shade K3 Screwdriver Cuttin...

Страница 8: ... Ac cordingly be gentle while working Figure 12 Dismounting the design cover N1 UP 258D device N2 Design cover N3 Screwdriver caution Dimension drawing Dimensions in mm General notes The operating instructions must be handed over to the client Any faulty device is to be sent together with a return delivery note of the local Siemens office If you have further questions concerning the product please...

Отзывы: