42/54
Siemens
TX-I/O™ Module system – Functions and operation
CM110561en_08
Building Technologies
Digital output functions
2018-10-25
5.9 Three-position control signal
(BO 3-Pos Relay,
BO-3-Pos Triac / Y250T))
For open/close control of three-position actuators without feedback (position
potentiometer), e.g. for
– Valve actuators
– Damper actuators
– Third-party actuators
The function uses two I/O points which must be on the same module and adjacent to
each other. I/O point (n) = Open, I/O point (n + 1) = Close.
•
The function converts the process value into 3-position positioning signals.
An internal
stroke algorithm
calculates the required length of the OPEN or CLOSE
pulses from the actuator runtime and the position specified in the process value.
No position feedback is required from the actuator.
•
The function supports
asymmetrical actuators
with different opening and closing
runtimes. However, this function can only be used if it is also supported by the bus
master.
Value
Description
Value range
(Default)
Rise Time
Time to OPEN
6.3 … 6553.5 s
(150.0 s)
Fall Time
Time to CLOSE
6.3 … 6553.5 s
(150.0 s)
Break time
Pause between opening
and closing
0...25.5 s
(0.1 s)
Reaction Time
(Series D and higher)
Additional runtime when
traveling to or from 0 %
0...50.0 s
(0.0 s)
Nz
Dead band
0...10%
(1 %)
Hys
Hysteresis
0...10%
(2 %)
Backup mode
Response of process value
in the event of bus failure
Keep = Last active value
No = 0%
(No)
Value = Backup Value
Backup Value
Backup value if
Backup Mode
= Value
0.01...100%
(0 %)
Synchronization
Synchronization mode
Details see below
Direction
(Series D and higher)
Inversion of the outputs to
fix incorrect wiring
False (normal)
(False)
True (inverted)
Asymmetric runtimes
can be set as parameters (if supported by the bus master).
Delay time before the actuator changes direction
Additional runtime when traveling to or from 0 % (clearance between motor and drive).
Note: Reaction Time is not part of the stroke model.
Application
Hardware
Function
Configurable / fixed
variables
Parameter details
Runtime
Pause
Reaction Time
(Series D and higher)